Joints between CPVC plastic pipe or fittings for ground-source heat pump systems must be what two specific types of joints?
1210.6.4
An indirect open-spray system is not required to be classified as a high-probability system if the pressure of the secondary coolant is at all times greater than what other pressure?
1103.3.2 Exception
A thermostat in which the thermostatic valve travels instantly from the closed to the open position, and vice versa, is a:
Chapter 2 – Definitions
Where gas piping systems for other than dry gas conditions have condensate, a drip shall be provided with ready access to permit:
408.3
Piping, tubing, and fittings must be tested by an approved third-party testing agency or certified by which other type of agency?
301.5
What is the minimum required depth for a grease duct reservoir?
506.3.7.1
Where commercial cooking appliances are vented by a fan-powered exhaust hood system, the appliances must be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating.
505.1.1
Decorative appliances for installation in approved solid fuel-burning fireplaces shall be listed in accordance with which ANSI/CSA standard?
602.1
For appliances in a dwelling unit basement, the unobstructed passageway must be large enough to allow removal of the largest appliance and measure not less than what minimum width?
306.2 (Exception)
Compressed gas containers and tanks, except for small volume units, shall be used in an upright position where the container axis is inclined as much as what maximum angle from the vertical?
704.2
For appliances in attics, the continuous solid flooring of the passageway must be not less than what minimum width?
306.3
What is the minimum duration required for the hydrostatic test on hydronic piping systems?
1208.1
For intake openings in residential occupancies, the maximum opening size in louvers, grilles, and screens must be less than or equal to what dimension?
Table 401.5
CSST gas piping systems (without an arc-resistant jacket) must be electrically continuous and bonded to the electrical service grounding electrode system or, where provided, which other system?
310.2
For a mechanically ventilated refrigerant pipe shaft with a cross-sectional area of 30 square inches, what is the minimum ventilation velocity required?
Table 1109.3.2
The remaining space surrounding a chimney liner installed within a masonry chimney flue is prohibited from being used to vent another appliance.
503.5.10
If there is insufficient evidence of compliance with the provisions of this code, the code official shall have the authority to require what as evidence of compliance?
104.2.2.4
Smoke detectors are not required in the return air system if all portions of the building served by the air distribution system are protected by what type of system?
606.2.1 Exception
Pollution-control units must be listed and labeled in accordance with which standard?
506.5.2
An installation regulated by this code constituting a hazard to health, safety, or welfare by reason of inadequate maintenance, fire hazard, or abandonment is declared to be a(an):
113.6
The pressure difference created by the action of a fan, blower or ejector that is located between the appliance and the chimney or vent termination is defined as:
Chapter 2 – Definitions
Any person commencing work on a mechanical system before obtaining necessary permits shall be subject to a fee that is:
108.4
What must an approved agency periodically perform to verify that labeled equipment and appliances are representative of those tested?
301.8.2
A valve located in the piping system, used to isolate individual appliances for purposes such as service or replacement, is a(an):
Chapter 2 – Definitions
Brazed joints in fuel oil piping systems must use a filler metal conforming to which AWS standard?
1303.3.1
What is the minimum flash point for Fuel Oil?
Chapter 2 – Definitions
If manufacturer’s instructions for a refrigerator are unavailable, what is the minimum clearance required above the top of the refrigerator?
625.1
Work shall not be done beyond the point indicated in each successive inspection without first obtaining whose approval?
111.2.3
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a listed appliance with a draft hood?
503.10.5; Table 503.10.5
Combustion air intake openings located on the exterior of a building shall have the lowest side of such openings located not less than what distance vertically from the adjoining finished ground level?
304.11
Reports not complying with Section 104.2.3.6.1 must describe criteria and justify:
104.2.3.6.2
How many members shall the board of appeals consist of?
113.1
Any apparatus or device that utilizes a fuel or a raw material as a fuel to produce light, heat, power, refrigeration or air conditioning is a(an):
Chapter 2 – Definitions
Official records related to this code shall be retained for not less than 5 years or for as long as:
104.7
For institutional occupancies, the maximum allowable refrigerant amounts shown in Table 1103.1 must be reduced by what percentage?
1104.2.1
The pressure of the weight of air and water vapor on the surface of the earth, approximately 14.7 psi (101 kPa absolute) at sea level, is defined as:
Chapter 2 – Definitions
For a single-appliance venting configuration, if the height (H) is less than 6 feet or greater than shown in the tables, what method must be used to calculate the vent capacity?
504.2.16
For an Elevator car in public spaces, what is the required Exhaust Airflow Rate in CFM/ft squared?
Table 403.3.1.1
In a Balanced Ventilation System, the mechanical supply airflow rate and mechanical exhaust airflow rate must each be within what percentage of the average of the two airflow rates?
Chapter 2 – Definitions
Clothes dryer exhaust ducts must terminate not less than how many feet in any direction from openings into buildings, where the manufacturer’s instructions do not specify a location?
504.4.1
A hazardous exhaust system is required if a flammable vapor, gas, fume, mist, or dust is present in concentrations exceeding what percentage of the lower flammability limit (LFL)?
509.2
A change in a mechanical system that involves an extension, addition, or change to the arrangement, type, or purpose of the original installation is defined as what?
Chapter 2 – Definitions
If a greater quantity of air is supplied by a mechanical ventilating supply system than is removed by a mechanical exhaust for a room, adequate means shall be provided for what?
501.4
Factory-built chimneys for medium-heat appliances producing flue gases above 1,000°F (538°C) measured at the entrance to the chimney must comply with which UL standard?
805.6, 39
A Class B Toxicity classification for a refrigerant indicates what characteristic?
Chapter 2 – Definitions
Which constituent is specifically excluded from the definition of Combustion Products?
Chapter 2 – Definitions
Electric motors driving exhaust fans in spray-finishing operations shall not be placed in which locations?
502.7.3.6
A valve used in conjunction with an automatic gas shutoff device to shut off the gas supply to a water-heating system is a(an):
Chapter 2 – Definitions
The code official is authorized to revoke a notice of approval if it is determined that the building or structure is in violation of what?
107.2
High-probability systems used for human comfort must use which refrigerant safety groups?
1104.3.1
A flame, spark or hot surface capable of igniting flammable vapors or fumes is a(an):
Chapter 2 – Definitions
A Thermoplastic is a plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature. What is the characteristic of a Thermosetting plastic?
Chapter 2 – Definitions
A gas having a moisture and hydrocarbon dew point below any normal temperature to which the gas piping is exposed is defined as:
Chapter 2 – Definitions
Installations that are part of buildings moved into or within the jurisdiction shall comply with the provisions for:
102.7
A joint made in thermoplastic piping by heating the parts sufficiently to permit fusion of the materials when the parts are pressed together is a:
Chapter 2 – Definitions
Which two piping materials shall not be used in contact with R-40 (methyl chloride)?
1107.3
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 6-inch radius smooth 90-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
Factory-built cremation furnaces and commercial direct-fed incinerators must be listed and labeled in accordance with which UL standard?
907.1
What is the capacity in cfh for CSST Flow Designation 48 at 200 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(17)
For double-wall heat exchangers, an air gap open to the atmosphere must be provided between the two walls, and the discharge location from the heat exchanger must be what?
1402.8.4.1, 16
A water heater pan constructed of plastic must have a minimum thickness of not less than what dimension?
1002.4
Clothes dryer installations exhausting more than how many CFM shall be provided with makeup air?
504.7
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 12 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Any person who continues work after being served with a stop work order shall be subject to what?
115.4
Solder joints in a metal pipe transitioning to PE-RT pipe shall not occur within what minimum distance of the transition point?
1203.16.2
An alternative material or design must be equivalent to that prescribed in this code with respect to strength, effectiveness, durability, safety, and which other criterion?
104.2.3.4
When soldering on the metal portion of a PEX ground-source system, the solder joints shall be performed not less than what minimum distance from a plastic-to-metal adapter in the same water line?
1210.6.5.2
Acceptable to the code official is the definition of which term?
Chapter 2 – Definitions
A Drain-Back System is a solar thermal system in which the fluid in the solar collector loop is gravity drained into a holding tank under what circumstances?
Chapter 2 – Definitions
Active or engineered smoke control systems must be capable of continued operation after detection of the fire event for a period of not less than 20 minutes or what alternative duration?
512.4.6
Mechanical ventilation systems for enclosed parking garages shall operate continuously or shall be automatically operated by means of carbon monoxide detectors applied in conjunction with what other detector type?
404.1
Where two or more meters are installed on the same premises but supply separate consumers, interconnection is prohibited on which side of the meters?
401.6
Which ASSE standard is listed as applicable for Copper and copper alloy fittings in Table 1202.5?
Table 1202.5
Devices used for making CSST bonding connections shall be listed for the application in accordance with which UL standard?
310.2.5
What is required for the assertion of certification when a product is Third-Party Certified?
Chapter 2 – Definitions
Domestic booster fans are prohibited from being installed in dryer exhaust systems.
614.6
What must an organization concerned with product evaluation maintain for the Labeled items?
Chapter 2 – Definitions
Pressure relief devices, fusible plugs, and purge systems located within the machinery room shall terminate outside the structure not less than how many feet above the adjoining grade level?
1105.7
An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer’s quality control system is a:
Chapter 2 – Definitions
What is the minimum separation distance required for the atmospheric venting of CNG from lot lines?
413.10.2.3; Table 413.10.2.3
A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under positive static vent pressure is a:
Chapter 2 – Definitions
Appliances installed in outdoor locations must be either listed for outdoor installation or provided with protection from:
303.6
Which fluid is explicitly excluded from the definition of Heat Transfer Liquid?
Chapter 2 – Definitions
One ton of Refrigeration Capacity Rating is equivalent to how many Btu/h?
Chapter 2 – Definitions
Field drilling and tapping of pipe fittings must only be performed on systems having operating pressures of what maximum amount?
403.9.5
A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under nonpositive static vent pressure is a:
Chapter 2 – Definitions
If a replacement refrigerant is classified into a different safety group, what additional requirement must the system comply with, besides meeting new installation requirements?
1101.7
Protective assemblies shall not be placed less than how many inch(es) from the mechanical appliances, devices, or equipment?
308.3
Basements or pits in bulk plants or terminals where Class I liquids are stored or used must be provided with ventilation designed to prevent what?
502.9.5.5.2
Construction or work for which a permit is required shall be subject to inspection by the code official and shall remain visible and able to be accessed for inspection purposes until when?
111.1
Diffusers, registers, and grilles are prohibited in the floor or its upward extension within toilet and bathing rooms, except in which type of space?
603.18.2 Exception
For buildings more than two stories in height, construction documents shall indicate where penetrations will be made for installations and shall indicate the materials and methods for maintaining required structural safety, fireblocking, and:
106.1
A self-contained, automatically controlled, vented, fuel-gas-burning, space-heating appliance, intended for installation in the space to be heated without the use of ducts, and having integral means for circulation of air, is a:
Chapter 2 – Definitions
Access points for dampers must be permanently identified on the exterior by a label having letters not less than what height?
607.4.2
All of the written, graphic and pictorial documents prepared or assembled for describing the design, location and physical characteristics of the elements of the project necessary for obtaining a mechanical permit are:
Chapter 2 – Definitions
Ozone gas generators having a maximum ozone-generating capacity of 1/2 pound (0.23 kg) or more over a 24-hour period must be mechanically ventilated at a rate of not less than how many air changes per hour?
502.9.9
A natural gas, manufactured gas, liquefied petroleum gas or mixtures of these gases is defined as:
Chapter 2 – Definitions
Packaged electric boilers must be listed and labeled in accordance with which UL standard?
1004.1
Products of combustion plus excess air in appliance flues or heat exchangers are defined as:
Chapter 2 – Definitions
Guards shall be constructed so as to prevent the passage of a sphere of what maximum diameter?
304.11
An Evaporative Cooler is a device used for reducing the sensible heat of air for cooling by the process of evaporation of water into what?
Chapter 2 – Definitions
A heater in which all the products of combustion generated by the burners are released into the air stream being heated, with the purpose of offsetting building heat loss by heating only outdoor air, is a:
Chapter 2 – Definitions
Exhaust ventilation for powder-coating operations must be sufficient to maintain the atmosphere below what concentration of the minimum explosive concentration?
502.7.6
The organization publishing a list of materials, products, or services must be acceptable to whom for the item to be considered Listed?
Chapter 2 – Definitions
Limited spraying spaces must have positive mechanical ventilation that provides not less than how many complete air changes per hour?
502.7.2
Alterations resulting in the addition of loads to a truss, such as HVAC equipment, shall not be permitted without verification that the truss is capable of supporting what?
302.4
Air that is conveyed to or from occupied areas through ducts that are NOT part of the heating or air-conditioning system is defined as what?
Chapter 2 – Definitions
In a dwelling unit, if an appliance is installed in a closet, the unobstructed passageway must measure not less than how many inches wide?
306.2 Exception
The required level platform on a sloped roof must be not less than how many inches in any dimension?
306.5.1
The code official is authorized to give permission for temporary service utilities in accordance with which section?
110.3
The opening provided in a draft hood to permit the ready escape of flue products in the event of no draft, back draft or stoppage, and to permit air into the draft hood in the event of a strong chimney updraft, is the:
Chapter 2 – Definitions
Closed-type expansion tanks for systems designed to have an operating pressure in excess of 30 psi (207 kPa) must be constructed and certified in accordance with which standard?
1009.2
Coverage for piping systems extends from the point of delivery to the outlet of which component?
101.2.3
What is the minimum clearance to combustibles required for connectors serving oil and solid-fuel domestic-type appliances?
Table 803.10.6, 30
A permanent mechanical joint incorporating an elastomeric seal and made with a pressing tool and jaw or ring approved by the fitting manufacturer is a:
Chapter 2 – Definitions
For piping systems having a volume of more than 24,000 cubic feet (680 m3), the duration of the pressure test shall not be required to exceed what maximum period?
705.3.5
Which of the following is not one of the criteria against which an alternative material, design, or method of construction must be found equivalent?
104.2.3.4
Where two or more openings are provided into one chimney flue or vent, the connectors must be attached to the vertical portion at an angle of not more than how many degrees relative to the vertical?
503.10.4.1
Required test and inspection records shall be available to the code official at all times during the erection of the building and the fabrication of the:
111.2.5.3
Balancing baffles must be mechanically locked in the desired position before placing the appliance in operation.
503.13.1
The passageway of domestic dryer exhaust duct terminals shall be undiminished in size and shall provide an open area of not less than what minimum size?
614.4.2
The minimum mechanical ventilation rate determined by Equation 4-9 can be reduced by 30 percent if the system supplies ventilation air directly to each bedroom and to one or more of which specific rooms, AND the system is a balanced ventilation system?
403.3.2.1 Exception 2
Which category of condensing appliances must be provided with an auxiliary drain pan where damage to any building component will occur as a result of a stoppage?
307.5
Hydrogen piping located inside of buildings must be installed in exposed locations and provided with ready access for visual inspection, except for which condition?
704.1.2.3.2
Exhaust inlets for manicure and pedicure stations must be located not more than how many inches horizontally and vertically from the point of chemical application, if a factory-installed inlet is not provided?
502.2
Which classification of Dry Cleaning Systems uses Class I flammable liquid solvents?
Chapter 2 – Definitions
Mechanically extracted outlets for mechanically formed tee fittings must have a height not less than what multiple of the thickness of the branch tube wall?
1203.3.8
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 9 inches, and the protection is 0.024-inch sheet metal over 1-inch glass fiber or mineral wool batts with ventilated airspace?
308.2; Table 308.2
Who must sign the application for a permit?
105.3
The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction, provided the alternative is not specifically prohibited by this code and has been what?
104.2.3
What is the minimum clearance required above an appliance or horizontal connector where the original required clearance was 36 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Elevation of the ignition source is not required for appliances that are listed as being resistant to what hazard?
305.3 (Exception)
Which inert gas is permitted as the test medium for R-744 refrigeration systems?
1110.3
If manufacturer’s instructions for a refrigerator are unavailable, what is the minimum clearance required between the back of the refrigerator and the wall?
625.1
The termination of concealed condensate piping must be marked to indicate whether the piping is connected to which two types of drain?
307.1.1
Access to equipment on a roof shall not require walking on roofs having a slope greater than what ratio?
306.5
The permit or a copy shall be kept on the site of the work until the:
105.5.7
The prohibition of fuel-fired appliances in certain rooms does not apply to direct-vent appliances that obtain all combustion air from where?
303.3 Exception
Where a fire alarm system is required, the actuation of a duct smoke detector must activate what type of signal at a constantly attended location?
606.4.1
If a room without openings to the outdoors is ventilated through an adjoining room, what is the minimum required unobstructed area of the opening to the adjoining room?
402.3
A timer provided to control main burner operation of a sauna heater shall have a maximum operating time of what duration?
615.6.1
Where openings below grade provide required natural ventilation, the outdoor horizontal clear space measured perpendicular to the opening shall be what multiple of the depth of the opening?
402.4
Where earthquake loads are applicable, supports for appliances must be designed and installed for seismic forces in accordance with the requirements of the:
301.12
Requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas are regulated by the:
101.2.6
When two or more appliances are connected, the vent connector length for a 12-inch diameter connector shall not exceed what maximum horizontal length?
504.3.2; Table 504.3.2
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 18 inches, and the protection is 3 1/2-inch-thick masonry wall without ventilated airspace?
308.2; Table 308.2
What is the Refrigerant Safety Group Classification for R-290 (propane)?
Table 1103.1
Piping run from a pressure-regulating device to the outdoors, designed to provide a reference to atmospheric pressure, is defined as:
Chapter 2 – Definitions
Exhaust ducts for commercial clothes dryers must have a minimum clearance of what distance to combustible materials?
614.1
Appliance connections to a chimney or vent equipped with a power exhauster must be made on which side of the exhauster?
501.1
What are the accepted standards used to determine the Flash Point of a liquid?
Chapter 2 – Definitions
If work authorized by a permit is suspended or abandoned for a period of 180 days, the permit shall expire. If a new permit is required, what fraction of the original fee shall be charged, provided the abandonment has not exceeded 1 year and changes have not been made?
105.4.3
A commercial kitchen grease duct serving a Type I hood must be enclosed when it penetrates what feature?
506.3.11
The cutting, notching, and boring of holes in structural steel framing members shall be as prescribed by whom?
302.5.1
Reports of inspection conducted by approved agencies or individuals shall be submitted in writing and certified by:
104.7.2
Hydronic piping systems must be tested hydrostatically at what minimum pressure?
1208.1
Where single-appliance venting tables show a lateral length (L) of zero (0), how many elbows are included in the venting configuration capacity listed in the table?
504.2.3
Where valves are identified by a numbering or lettering system, where must the legend(s) or key(s) for the valve identification be located?
1109.6.4
The portion of an appliance within which combustion occurs is the:
Chapter 2 – Definitions
What is the minimum dimension allowed for combustion air openings used to connect indoor spaces?
304.5.3.1
For a single appliance vented by a masonry chimney using a single-wall metal connector (Table 504.2(4)), if the height (H) is 8 feet and the lateral (L) is 8 feet, what is the maximum input rating (NAT Max) for a 12-inch connector?
504.2; Table 504.2(4)
What is strictly prohibited in hazardous exhaust ducts?
509.6.1
For a Private dwelling, single and multiple, what is the required continuous exhaust rate for a Kitchen?
Table 403.3.1.1 Note f
Commercial cooking appliances installed on casters must be connected to the piping system with an appliance connector listed as complying with which standard?
411.1.1
Fire dampers are classified for use in either static systems or dynamic systems, where a dynamic system is one that continues to operate during what event?
Chapter 2 – Definitions
Alterations resulting in the addition of loads to any truss member, such as HVAC equipment or water heaters, are prohibited without verification that the truss is capable of supporting such additional loading by a:
302.4
A hood and exhaust system is not required for protection from refrigerant decomposition if the refrigerant detector is used to automatically stop the combustion process in the event of what?
1104.3.4 Exception 3
Equipment, materials, products or services included in a list published by an organization acceptable to the code official that maintains periodic inspection of production or evaluation of services is defined as:
Chapter 2 – Definitions
Which of the following is NOT one of the required labeling descriptions for heat exchangers?
1404.4, 23
What is strictly prohibited from being used to line ducts or plenums from the exit of a cooling coil to the downstream end of the drain pan?
604.13
The provisions of this code are prohibited from nullifying the provisions of:
102.1
Gasket and sealing materials for cleanout doors in grease ducts must be rated for not less than what temperature?
506.3.8
A device for the final conveyance of the gas, or a mixture of gas and air, to the combustion zone is a:
Chapter 2 – Definitions
For PEX piping systems, testing with a compressed gas is permitted as an alternative to hydrostatic testing only if specifically authorized by what documentation?
1208.1 Exception
A structure utilized or intended for supporting or sheltering any occupancy is defined as what?
Chapter 2 – Definitions
Unless otherwise approved, pressure vessels must be constructed and certified in accordance with which standard?
1003.1
What is the minimum outside diameter (O.D.) tube size for corrugated stainless steel tubing (CSST) that is approved for a gas flow of 245 cfh at 25 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(16)
A room or space in which nonfuel-fired mechanical equipment and appliances are located is defined as what?
Chapter 2 – Definitions
The total of all Group A2, B2, A3, and B3 refrigerants in all occupancies shall not exceed what maximum weight, except where approved?
1104.3.3
Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where what occurs?
304.4
If the Maximum Primary Outdoor Air Fraction [$Max (Z_p)$] for a multiple zone recirculating system is 0.15 or less, what is the System Ventilation Efficiency ($E_v$)?
Table 403.3.1.1.2.3.2
What is the purpose of a Draftstop?
Chapter 2 – Definitions
Air that is introduced into a draft hood and is mixed with the flue gases is defined as:
Chapter 2 – Definitions
The board of appeals shall be appointed by whom?
112.1
Permit fees for work requiring a permit shall be paid in accordance with the schedule established by the:
108.2
What is the maximum acceptable average optical density for combustible electrical wires and cables exposed within a plenum, when tested in accordance with NFPA 262?
602.3.3
Fuel gas devices, equipment, and appliances used with refrigeration systems must be installed in accordance with which code?
1101.5
Dampers provided to balance airflow in hazardous exhaust systems must have securely fixed minimum-position blocking devices to prevent restricting the flow below what two required factors?
509.5.1
Vented gas fireplace heaters shall be listed in accordance with which ANSI/CSA standard?
605.1
What is the Refrigerant Safety Group Classification for R-1234yf?
Table 1103.1
Apparatus, material, and labor required for testing a mechanical system shall be furnished by whom?
111.3.2
Pipe-joint compound or tape must be applied only on which threads of a threaded fuel oil pipe joint?
1303.3.3
Fuel oil pumps (not integral to an appliance) must be listed and labeled in accordance with which UL standard?
1302.7
The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for which type of chimneys?
308.4.2.2
Supply air ducts connecting to listed central heating furnaces must maintain the same minimum clearance to combustibles as required for the furnace plenum for a distance of not less than how far from the supply plenum?
308.4.5
Where enforcement of a code provision would violate the conditions of the listing of the equipment, what shall apply?
102.8 Exception
For a Type B double-wall vent serving two or more Category I appliances with single-wall metal connectors (Table 504.3(2)), if the vent height (H) is 10 feet and the connector rise (R) is 1 foot, what is the minimum input rating (FAN Min) for a 5-inch connector?
504.3; Table 504.3(2)
Where laboratory burners and gas lights are installed such that the aggregate input rating exceeds 20 Btu per hour per cubic foot of volume of the room, what must be provided?
501.8
To obtain a building permit, construction documents are required to be drawn to what characteristic?
Chapter 2 – Definitions
What authority does the code official have regarding temporary uses, equipment, or systems permits?
110.4
When installing a floor furnace, a distance of not less than 18 inches (457 mm) must be provided from two adjoining sides of the floor furnace register to walls for which reason?
609.2
A shaft enclosure for a grease duct must be sealed around the grease duct at the point of penetration and vented to the outside of the building through what means?
506.3.11.1
The height requirement for solar thermal equipment exposed to vehicular traffic does NOT apply if what condition is met?
1402.6 Exception, 10
Gas vents 12 inches or less in size and located not less than 8 feet from a vertical wall must terminate above the roof in accordance with Figure 503.6.5.
503.6.5
Flared joints shall be used only in systems constructed from what type of piping material?
403.9.4
Where provided within a dwelling unit, controls for outdoor air ventilation systems must include text or a symbol indicating what?
403.3.2.4
Pressurized water storage tanks must bear a label showing the manufacturer’s name and address, model number, serial number, and what specific characteristics related to operating conditions?
1404.2, 22
What is the maximum circuit length allowed for 3/4-inch nominal tube size snow- and ice-melt tubing from a supply-and-return manifold arrangement?
Table 1209.7.1
Internal combustion engines used as gas engine-powered air conditioners shall not be connected to the gas supply piping in what manner?
411.1.5
What must boiler rooms be equipped with for disposing of liquid waste?
1004.6
What is the maximum design temperature permitted for systems utilizing underground plastic duct and fittings?
603.8.3
Heat-fusion joints for polypropylene (PP) pipe and tubing joints in ground-source systems must be installed in accordance with which ASTM standard?
1210.6.7.1
Solar thermal collectors and panels must be listed and labeled in accordance with which specific standard?
1401.4.1, 12
What is the minimum clearance required from noncombustible construction and gypsum wallboard attached to noncombustible structures for a shaft enclosure used for a grease duct?
506.3.11.1
What is NOT included in the calculation of Net Floor Area?
Chapter 2 – Definitions
In the One-Permanent-Opening Method (304.6.2), what is the minimum free area required for the single opening per 3,000 Btu/h of total appliance input rating?
304.6.2
What is the minimum distance required between the lowest edge of a grease filter and an exposed charcoal and charbroil type cooking surface?
Table 507.2.8
Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at what percentage or less?
403.2.1
Under what static vent pressure state does a Natural Draft System remove flue or vent gases?
Chapter 2 – Definitions
Full-face flange gaskets must be used with all flanges made of which type of material?
403.12
Who has the authority to waive the submission of construction documents, calculations, or other data if review is not necessary to determine compliance?
106.1 (Exception)
The payment of the fee for work authorized by a permit shall not relieve the applicant or holder of the permit from paying what?
108.5
A Dwelling contains not more than how many dwelling units?
Chapter 2 – Definitions
What is the required People Outdoor Airflow Rate in the Breathing Zone in CFM/person for a Booking/waiting area in a correctional facility?
Table 403.3.1.1
For ducts having a static pressure classification of less than 2 inches of water column (500 Pa), additional closure systems are not required for continuously welded joints and seams and locking-type joints and seams, but this exception does not apply to which joint types located outside of conditioned spaces?
603.9 Exception
For service access, what is the minimum required depth and width of the level working space provided in front of the control side of an appliance?
306.1
Appointment of a deputy code official requires the concurrence of the:
103.3
If intake openings are located less than 10 feet horizontally from streets, alleys, parking lots, and loading docks, they must be located not less than how many feet vertically above such locations?
401.4
The occupant load utilized for the design of a ventilation system shall be not less than the number determined from what source?
403.3.1.1
Concealed piping is prohibited from being located in solid partitions and solid walls unless installed in:
404.4
A primarily vertical structure containing one or more flues, for the purpose of carrying gaseous products of combustion and air from an appliance to the outside atmosphere is a:
Chapter 2 – Definitions
A free-standing heating unit used for direct heating of the space in and adjacent to that in which the unit is located is a:
Chapter 2 – Definitions
What must masonry chimneys be provided with, and this material must be compatible with the type of appliance connected?
801.16, 9
Air being removed from any space, appliance, or piece of equipment and conveyed directly to the atmosphere by means of openings or ducts is known as what?
Chapter 2 – Definitions
Where a venting system passes through an above-ceiling air-handling space and joints are installed within that space, the joints must be sealed in accordance with the appliance or vent manufacturer’s instructions, or the venting system must be installed in a sealed conduit or enclosure.
503.3.6
Roof and wall penetrations for solar thermal systems must be flashed and sealed to prevent the entry of water, rodents, and what other pests, in accordance with Section 302?
1402.7.2, 11
An unvented heating appliance designed for stationary installation and utilized to provide comfort heating, providing radiant or convection heat directly from the heater without utilizing ducts, is a(an):
Chapter 2 – Definitions
Exhaust outlets serving Type II hoods must terminate not less than how many feet in any direction from openings into the building?
506.4.2
What is an assembly of connected ducts, plenums, fittings, registers, grilles and hoods through which air is conducted from the space and exhausted to the outdoor atmosphere?
Chapter 2 – Definitions
Hearth extensions of approved factory-built fireplaces must be installed in accordance with the listing and must comply with which UL standard?
903.2
Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system must be designed for what type of pressure application?
501.6
Solid fuel furnaces must be tested in accordance with which UL standard?
918.1
Connectors shall connect to a chimney flue at a point not less than how many inches above the lowest portion of the interior of the chimney flue?
801.12, 7
A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment, is a:
Chapter 2 – Definitions
Shutoff valves shall be installed at connections to which type of expansion tank in ground-source loop piping systems?
1210.7.6
Each individual radiant tubing circuit must have a tag or label affixed to each manifold outlet to indicate the areas served and what other specific information?
1209.6.2
For vertical 3/4-inch steel pipe, how often must supports be spaced?
415.1; Table 415.1
Alterations such as cuts, notches, and holes bored in trusses or I-joists are prohibited except where permitted by the manufacturer’s recommendations or where the effects are specifically considered in the design of the member by whom?
302.3.1
Liquid fuel vent pipes shall terminate outside buildings not less than what minimum distance from any building opening?
1305.7
For an appliance connected by rigid metallic pipe, what is the maximum distance the union fitting can be located from the appliance?
411.1.6
An Induced-draft venting system uses a fan or other mechanical means to cause the removal of flue or vent gases under what static vent pressure condition?
Chapter 2 – Definitions
What is the minimum thickness required for a chimney connector serving a medium-heat appliance with an equivalent round diameter of 17 inches (Area 202–254 sq in), according to Table 803.9(2)?
Table 803.9(2), 24
What is the capacity in cfh for 1/2-inch nominal semirigid copper tubing at a length of 70 feet, for natural gas at less than 2 psi inlet pressure and 0.3 in. w.c. pressure drop?
402.4; Table 402.4(8)
An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn which type of fuel?
503.5.7.1
A combination flashback arrestor and backflow check valve shall be installed at an approved location on both the fuel gas and oxygen supply lines where fuel gas is used with oxygen in which operation?
410.5
Underground fuel oil piping systems must be listed and labeled in accordance with which UL standard?
1302.9
Gaskets and sealing materials used for grease duct-to-exhaust fan connections must be rated for continuous duty at a minimum temperature of what?
506.3.2.3
If motor vehicles are capable of passing under an appliance in a public garage, the appliance must be installed at least 1 foot (305 mm) higher than what other measurement?
304.6
The approval and installation of fuel gas distribution piping, equipment, fuel gas-fired appliances, and their venting systems shall be in accordance with which other code?
301.6
A valve installed after the point of delivery to shut off the entire piping system is a:
Chapter 2 – Definitions
Remote control of refrigeration compressors, refrigerant pumps, and normally closed, automatic refrigerant valves located in the machinery room must be provided by a clearly identified switch of the break-glass type or with what other device?
1106.5.1
Periodic testing is required for which of the following emergency devices and systems?
1111.1
New mechanical systems and parts of existing systems that have been altered, extended, renovated, or repaired shall be tested as prescribed to disclose what?
111.3.1
That which enables a device, appliance or equipment to be reached by ready access or by a means that first requires the removal or movement of a panel, door, or similar obstruction is defined as:
Chapter 2 – Definitions
Where multiple air-handling systems share common supply or return air ducts or plenums, smoke detectors are required if the combined design capacity is greater than what rate?
606.2.2
Exhaust duct terminations for clothes dryers, where the manufacturer’s instructions do not specify a location, shall terminate not less than what minimum distance in any direction from openings into buildings?
614.4.1
Motors driving fans in smoke control systems must have a minimum service factor of what value?
512.10.5
The use of gypsum boards to form plenums is limited to systems where the air temperatures do not exceed what maximum temperature?
602.2
Media-type air filters used in non-dwelling units must comply with which UL standard?
605.2
Mechanical ventilation shall be provided by a method of supply air and what other air type, except for certain residential occupancies?
403.1
Metal chimneys shall be constructed and installed in accordance with which specific NFPA standard?
806.1, 41
If outdoor air intake openings front on a street or public way, the 10-foot horizontal distance shall be measured from where?
401.4
The air velocity limitations in grease ducts do not apply within transitions used to connect to differently sized or shaped openings, provided such transitions do not exceed what maximum length?
506.3.4 Exception
A Push-Fit Joint is a type of mechanical joint consisting of elastomeric seals and what other component?
Chapter 2 – Definitions
Furnaces and boilers installed in closets and alcoves must be listed for what specific application?
303.5
What type of metallic pipe is strictly prohibited from use in piping systems?
403.3.1
Gas piping is prohibited from being used as which type of electrical component?
309.1
Horizontal upper combustion air ducts shall not slope in which direction toward the source of combustion air?
304.11
The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be not less than how many inches?
306.5
A gas-tight joint obtained by the joining of metal parts in molten state is a:
Chapter 2 – Definitions
A floor furnace must be placed so that a door, drapery, or similar object cannot be nearer than what minimum distance to any portion of the register of the furnace?
609.2
What is the capacity in thousands of Btu/h for 2-inch nominal Schedule 40 metallic pipe at 500 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 3.0 psi pressure drop?
402.4; Table 402.4(26)
Pumps that are not part of an appliance must be of what specific type?
1302.7
Duct smoke detectors must report only as a supervisory signal, not as a fire alarm, in facilities required to be monitored by what location?
606.4.1
Rodentproofing construction must be in accordance with the International Building Code for spaces where persons live, sleep, or work, or where what is stored, prepared, processed, served, or sold?
301.17
Protective steel shield plates for tubing containing Groups A2, A3, B2, and B3 refrigerants and located in concealed framing spaces must have a minimum thickness of what gauge?
1109.3.1.1
For non-residential occupancies, the maximum opening size in louvers, grilles, and screens protecting air intake openings must be less than or equal to what dimension?
Table 401.5
A method of interlock between an exhaust hood system and cooking appliances shall NOT involve or depend on what component?
507.1.1
Nonmetallic pipe utilized for fuel oil systems must conform to which standard listed in Table 1302.3?
1302.3
A separate grease duct system is NOT required for each Type I hood if all interconnected hoods are located in the same story, the same or adjoining rooms, do not penetrate fire-resistance-rated assemblies, and do not serve what type of appliances?
506.3.5
What type of fluid must be used as the heat transfer fluid in single-wall heat exchangers?
1402.8.4.2, 17
What is the minimum depth required for an auxiliary drain pan?
307.2.3
These regulations, subsequent amendments thereto or any emergency rule or regulation that the administrative authority having jurisdiction has lawfully adopted, is the definition of which term?
Chapter 2 – Definitions
For an uninhabited space, if a mechanical exhaust and supply air system is used, the system must be automatically controlled to operate when the relative humidity in the space served exceeds what percentage?
406.1
The installation of liquid-fueled stationary internal combustion engines and gas turbines, including exhaust and fuel piping, must meet the requirements of which standard?
915.1
Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in what structure?
1109.2.5
Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be based on a listed occupancy classification most similar in terms of occupant density, activities, and what third factor?
403.3.1.1
If attics or structural spaces are part of a passive solar system, what is not required if other approved means of controlling condensation are provided?
1402.7.1, 11
The code official is authorized to require the owner or owner’s authorized agent to provide what document to determine compliance with this code?
104.2.2
The content of a technical opinion and report shall analyze the properties of the design, operation, or use of the building or premises to identify and propose what?
104.2.2.3
Vented appliances are generally required to be installed with draft hoods, except for which type of appliance?
503.12.1
High-density polyethylene (HDPE) pipe used for ground-source heat pump ground-loop systems must conform to which specific ASTM standard?
Table 1210.4
Domestic cooking exhaust equipment with integral downdraft exhaust systems must be listed and labeled in accordance with which standard?
505.2
A manually operated solid fuel ignition appliance for installation in a vented solid fuel-burning fireplace is a:
Chapter 2 – Definitions
Venting systems are prohibited from extending into or passing through any fabricated air duct or what other air-handling component?
503.3.5
Every steam boiler must have a pressure gauge and what other component?
1010.2
In coastal high-hazard areas and coastal A zones, mechanical systems and equipment shall not be mounted on or penetrate walls intended to do what under flood loads?
301.16.1
What is the maximum allowable quantity of refrigerant determined by Section 1104 based on?
1102.1
For exhaust openings that terminate outdoors, the openings in screens, louvers, and grilles must be sized not less than what minimum dimension?
501.3.2
If the code official has obtained a proper inspection warrant, what must the person having charge or control of the structure permit?
104.4.1
At the point where tee or wye fittings connect to a common vent, the opening size of the fitting must be equal to the size of which component?
504.3.9
Gas piping systems constructed entirely of pipe or tubing not meeting the size and length criteria for displacement must have a design operating pressure of what maximum amount to be purged indoors or outdoors?
406.7.2
The point at which a gas-fired appliance connects to the gas piping system is the:
Chapter 2 – Definitions
Appliances constructed and installed so that all air for combustion is derived directly from the outdoor atmosphere and all flue gases are discharged directly to the outdoor atmosphere are defined as:
Chapter 2 – Definitions
To confirm its objectivity, an approved agency must disclose all possible:
301.4.2.1
For a Pet shop (animal areas), recirculation of air is prohibited and mechanical exhaust is required based on which Table 403.3.1.1 note?
Table 403.3.1.1 Note b
Joints and piping on the positive pressure side of a power exhauster must be listed for positive pressure applications as specified by what documentation?
801.14, 8
The code official shall have the authority to suspend or revoke a permit if it was issued on the basis of incorrect, inaccurate, or what other type of information?
105.4.5
The length of the bonding jumper between the connection to a gas piping system and the connection to a grounding electrode system shall not exceed what maximum length?
310.2.3
Which type of vent is listed and labeled for use with appliances with draft hoods and other Category I appliances that are listed for use with that specific vent type?
Chapter 2 – Definitions
Under what condition can the minimum required rate of outdoor air be reduced from the rate determined in Section 403.3?
403.2 Exception
In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to which specific location?
403.3.1.1
For an appliance connected to a chimney flue serving a fireplace, what must be provided for access to the flue?
801.10.1, 5
Unfired pressure vessels having a volume of 5 cubic feet or less operating at pressures not exceeding 250 psi (1724 kPa) are exempt if located in all of the following occupancies EXCEPT:
1001.1 Exceptions
The use of ventilating hoods and exhaust systems to vent appliances is generally limited to industrial appliances and appliances installed in which type of application?
503.2.1
Collectors and separators for dust, stock, and refuse systems must be located on the exterior of the building or structure and not nearer than how many feet to combustible construction or unprotected wall/floor opening?
510.1.1
What is the maximum vertical spacing allowed for supporting Copper or copper-alloy pipe?
Table 305.4
What must be provided in an attic passageway to an appliance, which must be not less than 24 inches (610 mm) wide?
306.3
Which classification of clothes dryer is used in business with direct intercourse of the function with the public, and is not designed for use in individual family living environment?
Chapter 2 – Definitions
Where a connector passes through an unheated space, what type of construction shall the connector NOT be?
803.2, 19
Which type of floor furnace is equipped with a fan that provides the primary means for circulating air?
Chapter 2 – Definitions
Which type of hood is NOT allowed to be used over extra-heavy-duty cooking appliances?
507.2.10.1
In accordance with a decision from the board of appeals, the code official shall take action without what?
112.4
A location that cannot be accessed without damaging permanent parts of the building structure or finish surface is a:
Chapter 2 – Definitions
Above-grade underfloor spaces or basements in LP-gas distribution facilities where portable containers are used or stored must be provided with what?
502.9.10.1
A record of approvals shall be maintained by the code official and made available for public inspection during business hours in accordance with:
104.7.1
For kitchens in Group R-2, R-3, and R-4 occupancies, what is the required intermittent exhaust rate capacity?
Table 403.3.2.3
The meter, valve, regulator, piping, fittings and equipment installed by the service gas supplier before the point of delivery is the:
Chapter 2 – Definitions
When sizing a single appliance vent where the maximum capacity determined from the tables is used, and an additional elbow up to and including 45 degrees is added, the maximum capacity listed must be reduced by what percentage?
504.2.3
Floor registers shall resist, without structural failure, a concentrated load of how many pounds?
603.18.1
Which of the following piping materials is listed in Table 1107.4 for use as refrigerant pipe?
Table 1107.4
The required minimum indoor temperature must be maintained at what specific point above the floor on the design heating day?
309.1
What electrical requirement must be provided at or near the appliance location in an attic?
306.3.1
Scrubbing tubs, scouring, brushing or spotting operations in dry cleaning plants must be located such that solvent vapors are captured and exhausted by which system?
502.6.3
Mechanical draft systems must be listed and labeled in accordance with which UL standard?
804.3, 32
The maximum amount of gas input required per unit of time, usually expressed in cubic feet per hour, or Btu/h, is defined as:
Chapter 2 – Definitions
Which of the following details is NOT required to appear on the permanent factory-applied nameplate affixed to appliances?
301.9
Duct coverings shall not penetrate a wall or floor required to have what specific characteristic?
604.6
The imposition of penalties prescribed shall not preclude the legal officer from instituting appropriate action to prevent unlawful construction or to:
113.5
The code official shall keep a record of tests conducted to comply with the requirements for tests used as evidence of compliance and tests required for:
104.7.4
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe must conform to which ASTM standard?
Table 1202.4
In a Retail store, sales floor, or showroom, what is the required Exhaust Airflow Rate in CFM/ft squared for Dressing rooms?
Table 403.3.1.1
Protective shield plates must be placed where there is less than what minimum distance between the clothes dryer exhaust duct and the finished face of the framing member?
614.8
What is the maximum overall length permitted for a listed appliance fuel connector?
411.1.3.1
Where a closet is designed for a clothes dryer, what is the minimum area required for the opening in the closet enclosure for makeup air?
504.7
What must Type L vents terminate with?
802.4, 16
Where must mechanical fasteners penetrate when installing radiant heating panels on wood or steel framing?
927.3
Where two bottom blowoff valves are provided, consisting of one quick-opening valve and one slow-opening valve in series, which valve must be installed closest to the boiler?
1008.1
For a round galvanized steel duct with a diameter of 18 inches operating at 1-inch water gauge static pressure in a single dwelling unit, what is the minimum sheet metal thickness required?
Table 603.4
A Type B-W gas vent shall terminate not less than what minimum vertical height above the bottom of the wall furnace?
503.6.6
The purpose of a Transition Fitting, Plastic to Steel, is to provide what type of connection between the two materials?
Chapter 2 – Definitions
What is the approximate length of the threaded portion required to be cut for a 1 1/4-inch iron pipe size?
403.8.2; Table 403.8.2
Air intake openings on structures in flood hazard areas must be located at or above the elevation required by which section of the International Building Code?
401.4
Where an additional appliance is to be served by an existing piping system, what must be done if the existing system is determined to be inadequate?
401.4
For smoke control systems using the exhaust method in large enclosed volumes, the height of the lowest horizontal surface of the accumulating smoke layer must be maintained not less than how many feet above any walking surface that forms a portion of a required egress system?
512.8.1
In industrial occupancies and refrigerated rooms, where a machinery room would otherwise be required, refrigerant detectors are not required in unoccupied areas that contain only what type of piping?
1104.2.2 Exception
Screws, rivets and other fasteners are prohibited from penetrating the inner wall of double-wall gas vents, except at the transition from an appliance draft hood outlet, flue collar or what other component?
503.6.14
Underground inspection shall be made after trenches or ditches are excavated and bedded, piping installed, and before what action is taken?
111.2
For an appliance to be classified as Vented, how are the products of combustion conveyed to the outdoor atmosphere?
Chapter 2 – Definitions
What is the minimum clearance required above an appliance where the original required clearance was 12 inches, and the protection is 0.024-inch sheet metal with ventilated airspace over 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Motorized louvers must be interlocked with the appliance to ensure they are proven to be in the full open position prior to:
304.1
What is the minimum weight of steel pipe required for Group A2, A3, B2, and B3 refrigerants for sizes 1 1/2 inches or less in diameter?
1107.4.1
A permit issued by the code official for temporary uses, equipment, and systems shall not be permitted for more than how many days?
110.1
Which of the following is prohibited when taking return air from a crawl space?
601.5
What is the minimum exhaust distance required for air discharged from mechanical ventilation systems from a property line or openings into buildings?
1105.6.1
In all clearance reduction systems using a ventilated airspace, what is the minimum air gap required between the clearance reduction system and combustible walls and ceilings?
308.2
Which regulator reduces gas pressure from the range of greater than 0.5 psig (3.4 kPa) and less than or equal to 5 psig (34.5 kPa) to a lower pressure?
Chapter 2 – Definitions
Where one chimney flue serves gas appliances and liquid fuel-burning appliances, and two or more openings are provided into the flue, they must be located at different:
503.5.7.2
Solar thermal system components containing pressurized fluids must be protected against pressures and temperatures exceeding design limitations using what devices?
1402.3, 5
This code shall not require changes to the construction documents or construction of a structure for which a lawful permit was issued, provided the construction was pursued in good faith within how many days after the effective date of this code?
105.5.6
If roof-mounted solar collectors also serve as a roof covering, they must conform to the requirements for roof coverings in accordance with which code?
1402.8.1.3, 13
Factory-built chimneys for building heating appliances producing flue gases having a temperature not greater than 1,000°F must be listed and labeled in accordance with which UL standard?
506.1
Log lighters shall be listed in accordance with which standard?
603.1
What is the minimum clearance required from combustible materials for ducts serving commercial clothes dryers?
504.1
A vertical pipe supplying fuel gas is defined as a:
Chapter 2 – Definitions
The code official is authorized and directed to perform which primary action regarding the provisions of this code?
104.1
Mechanical systems shall be tested as required in this code and observed by whom?
111.3
Potable water supplies to solar systems must be protected against contamination in accordance with which code?
1401.2
What is the capacity in cfh for 1-inch nominal Schedule 40 metallic pipe at 500 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(7)
The opening in a cap, spud or other device whereby the flow of gas is limited and through which the gas is discharged to the burner is the:
Chapter 2 – Definitions
Who shall defend any suit or criminal complaint instituted against an officer or employee acting in the lawful discharge of duties under this code?
104.8.1
An appliance used to reduce combustible refuse material to ashes and that is manufactured, sold and installed as a complete unit is an:
Chapter 2 – Definitions
What is the capacity in cfh for 3-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 100 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(21)
In areas designated as Zone AO where a depth number is not specified on the flood hazard map, the depth number used for the Design Flood Elevation shall be taken as equal to what value?
Chapter 2 – Definitions
What is the minimum clearance required to a mechanical air supply inlet (Clearance I) for a vent terminal?
503.8; Table 503.8
For appliance shutoff valves located at a manifold, what is the maximum distance allowed between the manifold and the appliance served?
409.5.3
Steam piping must be installed to drain to the boiler or what other system component?
1206.8
Water supply and discharge connections associated with refrigeration systems must be made in accordance with this code and which other specific code?
1101.4
What is the minimum height required for a cleanout opening in a masonry chimney flue?
801.13, 7
Joints between polyethylene plastic pipe and tubing for ground-source heat pump loop systems must be heat-fusion joints, electrofusion joints, or what third type of joint?
1210.6.6
When granting modifications due to practical difficulties, the code official must first find that the modification does not lessen which requirement?
104.2.4
Mechanical ventilation for indoor storage areas exceeding maximum allowable quantities shall be provided at a rate of not less than how many CFM per square foot of floor area?
502.8.1.1
If the lower 6-inch portion of a floor furnace is sealed by the manufacturer to prevent the entrance of water, what is the minimum clearance required from grade level?
609.4
For Group A2L and B2L refrigerant detectors, if the concentration is less than or equal to the refrigerant concentration level (RCL), the alarm reset must be what type?
Table 1106.4.2
When replacing an existing heating appliance serving an occupied portion of a structure, a request for inspection must be filed with the department within how many hours after replacement work is completed to avoid prohibiting the operation of the appliance?
111.2
Nonrecirculating direct-fired industrial air heaters shall be listed to which standard?
611.1
Ducts shall not be installed in or within what minimum distance of the earth, unless they comply with Section 603.8 (Underground Ducts)?
603.14
A manually operated valve in the gas line for the purpose of completely turning on or shutting off the gas supply to the appliance, except to pilot(s) provided with independent shutoff, is a(an):
Chapter 2 – Definitions
A plastic water heater pan material must have a flame spread index of not more than 25 and a smoke-developed index of not more than what value when tested in accordance with ASTM E84 or UL 723?
1002.4
What is a pipe that connects a fuel-burning appliance to a chimney?
Chapter 2 – Definitions
A single booster-type automatic instantaneous water heater used solely for sanitizing rinse in a commercial kitchen must have its draft hood outlet located not less than 36 inches vertically and what minimum distance horizontally from any surface other than the heater?
501.8
The interlock requirement for dampers in combustion air openings serves to prevent operation of any appliance that draws combustion air from the room or space when what condition is true?
701.2
In a Private dwelling, single and multiple, if the exhaust system for a Toilet room operates intermittently, what is the required exhaust rate in CFM?
Table 403.3.1.1 Note f
What is the minimum clearance required above an appliance where the original required clearance was 36 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
An air dispersion system is a diffuser system designed to convey air and diffuse air into a space while operating under what pressure characteristic?
Chapter 2 – Definitions
Guards shall be provided where components requiring service are located within what distance of a roof edge or open side of a walking surface located more than 30 inches above the surface below?
306.6
The person to whom an annual permit is issued shall keep a detailed record of alterations made under such permit that shall be accessible to the code official at all times or:
105.1.2
Threads used for threaded joints in hydronic piping systems must conform to which ASME standard?
1203.3.5
What is defined as a single unit providing complete, independent living facilities, including permanent provisions for living, sleeping, eating, cooking and sanitation?
Chapter 2 – Definitions
What is the exception for the minimum average air velocity into an open face or open front spray booth using fixed or automated electrostatic spray application equipment?
502.7.3.3.1 Exception
Each exhaust outlet located within a hood shall serve not more than what maximum linear length of hood?
507.1.5
Where are manual dampers prohibited from being installed in connectors?
803.5, 21
What type of hazardous production materials (HPM) are allowed to have their gas cabinet ventilation system connected to a workstation ventilation system?
502.10.1
A Smoke Damper is installed to operate automatically, controlled by what system?
Chapter 2 – Definitions
Which type of chimney is composed of factory-made components, assembled in the field in accordance with the manufacturer’s instructions?
Chapter 2 – Definitions
Soft annealed copper tubing larger than what outside diameter shall not be used for field-assembled refrigerant piping unless it is protected from mechanical damage?
1107.4
Vents for Category II and III appliances shall be tested in accordance with which UL standard?
502.1
Approved smoke and heat vents must be installed in the roofs of one-story buildings where required by which code?
311.1
Connectors shall connect to a masonry chimney flue at a point not less than what vertical distance above the lowest portion of the interior of the chimney flue?
501.9
What is the minimum clearance required from the grade level to the lowest portion of a floor furnace?
609.4
Where grease duct enclosures are not required, what is the minimum clearance required from combustible construction for Type I hood grease duct systems?
506.3.6
Piping and components subject to manual gravity draining in drain-back systems must maintain a horizontal slope in the direction of flow of not less than what minimum value?
1402.4.1, 7
Mechanical ventilation for ambulatory care facilities and Group I-2 occupancies shall be designed and installed in accordance with this code, NFPA 99, and which other standard?
407.1
Where the scope of a referenced standard includes subject matter also within the scope of this code, the provisions of this code shall:
102.8.2
When entering an occupied structure or premises for inspection, the code official must first present credentials to the occupant and do what?
104.4
Sauna heaters must be equipped with a thermostat that will limit room temperature to what maximum temperature?
615.6
How is an Unvented Alcohol Fuel-Burning Decorative Appliance intended to be secured?
Chapter 2 – Definitions
What is a Pressure-Limiting Device designed to stop automatically?
Chapter 2 – Definitions
Power exhausters serving automatically fired appliances must be electrically connected to each appliance to prevent appliance operation when the power exhauster is not operating. This is referred to as what type of connection?
804.3.2, 32
Low-pressure boilers operate at pressures less than or equal to 15 pounds per square inch (psi) (103 kPa) for which medium?
Chapter 2 – Definitions
Where solar thermal equipment is exposed to vehicular traffic, what is the minimum height it must be installed above the finished floor?
1402.6, 10
With the exception of smoking lounges, the ventilation rates in Table 403.3.1.1 are based on the absence of what in occupiable spaces?
403.3.1.1
Hangers and anchors for piping support must be attached to the building construction in what manner?
305.3
In a Plastic Adhesive Joint, the adhesive substance forms a continuous bond between mating surfaces without doing what to either surface?
Chapter 2 – Definitions
Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending not less than how many inches above adjoining grade?
304.1
Fuel-burning appliances and fireplaces in Group I-2, Condition 2 occupancies must be in accordance with which section?
303.9
The working pressure rating of solar system components must be not less than what specific pressure?
1402.3, 5
When granting a modification due to practical difficulties, the code official must ensure the modification does not lessen which requirement?
104.2.4
For the purposes of this code, if a word is used in the present tense, it includes which other tense?
201.2
The cutting and notching of holes in cold-formed steel framing members designated as structural members shall be in accordance with which standard?
302.6
Requirements necessary for the strength, stability, or proper operation of a mechanical system not specifically covered by this code shall be determined by whom?
102.9
Which of the following conditions permits the use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum?
601.2.1
Constituents resulting from the combustion of a fuel with the oxygen of the air, including inert gases, but excluding excess air, are defined as:
Chapter 2 – Definitions
Gas composed predominately of propane, propylene, butanes or butylenes, or mixtures thereof that is gaseous under normal atmospheric conditions, but is capable of being liquefied under moderate pressure at normal temperatures, is defined as:
Chapter 2 – Definitions
Freeze protection for system components must be provided in accordance with which standard?
1402.4, 6
A Bathroom is defined as a room containing a water closet and which other fixture?
Chapter 2 – Definitions
What is the minimum length (in feet) of nominal 2 1/2-inch piping that, when removed from service, must have its residual fuel gas displaced with an inert gas?
406.7.1.1; Table 406.7.1.1
Plastic fire sprinkler piping exposed within a plenum shall be used only in which type of fire suppression system?
602.3.4
Which ASTM standard applies to Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) plastic pipe?
Table 1202.4
What specific type of gauge is prohibited on a fuel oil tank if, when broken, it would permit the escape of oil?
1306.5
A self-contained vented appliance designed for incorporation in or permanent attachment to the structure, furnishing heated air circulated by gravity or by a fan directly into the space, excluding floor furnaces, unit heaters and central furnaces, is a:
Chapter 2 – Definitions
Valves in hydronic piping systems must be constructed of materials compatible with the piping material and fluids, and rated for what two system characteristics?
1202.6
Connecting offices, waiting rooms, ticket booths, and similar uses accessory to a public garage must be maintained at what specific pressure condition?
404.2
Outdoor air inlets serving the residential portion of a building must be covered with a screen having what maximum size openings?
618.4
Commercial electric cooking appliances must be listed and labeled in accordance with which UL standard?
917.1
The board of appeals shall not have the authority to:
112.2
What is the capacity in thousands of Btu/h for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(27)
Upon activation, smoke detectors in air distribution systems shall shut down all operational capabilities of the system in accordance with what criteria?
606.4
The term House Piping is defined as:
Chapter 2 – Definitions
What is the maximum horizontal length allowed for a single-wall connector?
803.10.2, 25
Which appliance type is classified as a Light-Duty Cooking Appliance?
Chapter 2 – Definitions
Ignition of gas at the burner(s) when the gas controlling device is turned on, including reignition if the flames have been extinguished by means other than by the closing of the gas controlling device, is defined as:
Chapter 2 – Definitions
Semirigid conduit of copper, copper-alloy aluminum, plastic or steel is defined as:
Chapter 2 – Definitions
The greater of the following two areas: the area within a floodplain subject to a 1 percent or greater chance of flooding in any given year, or the area designated as a flood hazard area on a community’s flood hazard map, is the definition of:
Chapter 2 – Definitions
When using Type B double-wall gas vent connected by a single-wall metal connector to a single Category I appliance, if the vent height (H) is 20 feet, the lateral (L) is 20 feet, and the vent diameter (D) is 12 inches, what is the maximum input rating (NAT Max) for a Natural Draft appliance?
504.2; Table 504.2(2)
Openings into fire-resistance-rated construction for exit enclosure ventilation systems shall be limited to those needed for maintenance and operation and protected by what?
601.3
Return air openings shall not be located less than what minimum distance from an open combustion chamber or draft hood of another appliance in the same room?
601.5
Openings through concrete or masonry building elements for pipe penetrations must be protected by what?
1206.4
Where conflicts occur between this code and the conditions of listing or manufacturer’s instructions, which provisions shall generally apply?
304.2
Requirements for gas appliances and related accessories must include installation, venting, connections to piping systems, and:
101.2.4
Pellet fuel-burning appliances must be listed and labeled in accordance with which standard?
904.1
For electrofusion joints, joint surfaces must be clean and free from moisture, and scoured to expose what material?
1210.6.6.2
Where must cleanouts serving horizontal sections of grease ducts be located if other locations are not available?
506.3.9
If an appliance creates a positive pressure in the venting system using a forced or induced draft system, the venting system must be designed and listed for what specific application?
801.9
Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than what multiple of the test pressure?
406.4
The entire length of a vent connector must be provided with what type of access for inspection, cleaning and replacement?
503.10.12
Means for interrupting the electrical supply to an air-conditioning appliance and its remote cooling tower must be provided within sight of and not over what maximum distance from the equipment?
627.1
To determine compliance with this code, the code official is authorized to require the owner or owner’s authorized agent to provide a:
104.2.2
Minor alterations to existing mechanical systems shall meet the provisions for new construction unless the work is done in the same manner as the existing system, is not hazardous, and is what?
102.4
Chimneys shall extend not less than what minimum vertical distance above the highest connected appliance draft hood outlet or flue collar?
503.5.4
According to Table 509.8, what is the minimum nominal thickness required for a duct diameter of 19–30 inches conveying abrasive materials?
Table 509.8
What is the approximate length of the threaded portion required to be cut for a 1-inch iron pipe size pipe?
403.8.2; Table 403.8.2
After an installation has been ordered disconnected by the code official, a person may not make energy source connections until who authorizes the reconnection and use of the installation?
113.6.3
A balanced damper device attached to a chimney, vent connector, breeching or flue gas manifold to protect combustion appliances by controlling chimney draft is known as a:
Chapter 2 – Definitions
Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air, except under which condition?
403.2.1
Where an oil-fired appliance is connected to an existing masonry chimney, the chimney flue shall be repaired or relined in accordance with which standard?
801.18.2, 12
What are prohibited from being exhausted through the same hazardous exhaust system?
509.4
If different provisions specify different methods of construction in a specific case, which requirement shall govern?
102.1
Disconnection of utility service is authorized by the code official in case of emergency where necessary to eliminate which condition?
109.3
Ducts for domestic cooking exhaust equipment must be constructed of sheet metal and equipped with what flow control device?
505.3
Reduced clearance protective assemblies, including structural and support elements, must be constructed of what type of material?
308.3
Boilers shall be mounted on floors of noncombustible construction, unless what condition is met?
1004.5
The minimum distance through air measured between the heat-producing surface of the mechanical appliance, device or equipment and the surface of the combustible material or assembly is defined as:
Chapter 2 – Definitions
What is the capacity in cfh for 1 1/4-inch nominal semirigid copper tubing at 200 feet in length, operating at less than 2 psi inlet pressure with a 1.0 in. w.c. pressure drop?
402.4; Table 402.4(12)
Flexible air connectors are prohibited from passing through which building elements?
603.6.2.2
A Floor Furnace takes air for combustion from where?
Chapter 2 – Definitions
What must be provided for existing chimneys and vents in accordance with the International Building Code?
801.18.4.1, 14
The code official is authorized to accept reports of approved agencies, provided such agencies satisfy the requirements as to qualifications and what other factor?
111.2.4
Exhaust ducts under positive pressure, chimneys, and vents are prohibited from extending into or passing through which other duct components?
601.4
An enclosed portion of the building structure that is designed to allow air movement and serve as part of an air distribution system is defined as a Plenum, provided it is not what?
Chapter 2 – Definitions
Which method defines a Low-Probability Pump designed to prevent atmospheric release of the pumped fluid?
Chapter 2 – Definitions
A valve in a line shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure.
406.1.4
A permanently mounted, manually operated device that provides the means for connecting and disconnecting an appliance to the supply piping, and is designed so that disconnection only occurs when the manually operated valve is in the closed position, is a:
Chapter 2 – Definitions
When two or more appliances are connected, what is the maximum horizontal length permitted for a 7-inch diameter connector?
504.3.2; Table 504.3.2
Vent outlets for purging gaseous hydrogen systems shall be located at least what minimum distance from building openings and lot lines of properties that can be built on?
705.5.3.1
Vented wall furnaces shall be located so that a door cannot swing within what minimum distance of an air inlet or air outlet of such furnace, measured at right angles to the opening?
608.4
A Type L vent is listed and labeled for use with oil-burning appliances and which type of gas-fired appliances?
Chapter 2 – Definitions
Where must the exhaust from stationary local contaminant sources discharge?
401.6
Which of the following appliances is not required to be vented?
501.8
When two or more connectors enter a common vent or chimney, where shall the smaller connector enter?
803.7, 22
For electrical equipment and appliances, the required label information must include the electrical rating in volts, amperes, and motor phase, and what other essential rating?
301.9
For a hydrostatic leak test of a gaseous hydrogen system, what is the minimum required test pressure?
705.3.1
In System D for combustible wall pass-through, what is the required minimum clearance to combustibles?
Table 803.10.4, 27
External duct insulation, except spray polyurethane foam, must be legibly printed or identified at intervals not greater than what maximum distance?
604.7
What is the minimum clearance required from combustible construction for a Type I hood?
507.2.6
What are the specified materials for Tubing, as defined in Piping?
Chapter 2 – Definitions
In concealed locations, protective steel shield plates for vents installed through holes or notches in framing members must have a minimum thickness of 0.0575 inch, which corresponds to what gauge?
502.7
Energy recovery ventilation systems shall not be used in commercial kitchen exhaust systems serving which type of hood?
513.2
When are permit applications for appliance and equipment replacements and repairs required to be submitted if the work was performed in an emergency situation?
105.1 (Exception)
An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere is a(an):
Chapter 2 – Definitions
Where are fuel oil test wells strictly prohibited from being installed?
1306.2
A Pollution-Control Unit (PCU) is manufactured equipment installed in a grease exhaust duct system for the purpose of extracting smoke, grease particles and what other contaminants?
Chapter 2 – Definitions
Masonry chimneys used to vent fuel-fired appliances shall be located, constructed and sized as specified in what documentation?
801.15, 8
Condensate drains shall not discharge into a plumbing fixture other than a floor sink, floor drain, trench drain, mop sink, hub drain, standpipe, utility sink or which other sink type?
307.2.1.1
Refrigeration systems using a refrigerant other than ammonia must comply with Chapter 11, the International Fire Code, and which specific ASHRAE standard?
1101.1.1
Grease ducts must be constructed of steel having a minimum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) or stainless steel not less than what minimum thickness?
506.3.1
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 9 inches, and the protection is 3 1/2-inch-thick masonry wall with ventilated airspace?
308.2; Table 308.2
The loss in pressure due to friction or obstruction in pipes, valves, fittings, regulators and burners is defined as:
Chapter 2 – Definitions
What must be provided to solar thermal equipment for maintenance purposes?
1402.2, 4
For ozone cabinets, what is the minimum average ventilation velocity required at makeup air openings with the cabinet doors closed?
502.9.9
What is the Zone Air Distribution Effectiveness for a configuration with Ceiling supply of warm air and ceiling return?
Table 403.3.1.1.1.2
Which type of system is exempt from the requirement for an expansion tank in a hot water system?
1009.1 Exception
In which specific occupancy and condition are solid fuel-burning fireplaces and appliances prohibited?
901.4
For “other product-conveying outlets,” what is the minimum termination distance from exterior walls and roofs?
501.3.1
Unvented room heaters shall not have an input rating in excess of what maximum amount?
621.3
The vent termination point for a horizontal mechanical draft system shall not be located closer than what minimum distance to an interior corner formed by two perpendicular walls?
804.3.4, 33
Plastic plumbing piping and tubing within plenums must have a flame spread index not greater than 25 and a smoke-developed index not greater than 50 when tested in accordance with which standard?
602.3.8
Which type of temperature relief valve automatically opens a relief vent at a predetermined temperature and must be manually returned to the closed position?
Chapter 2 – Definitions
Which of the following is an example of work for which a permit is not required?
105.2
Nonrecirculating direct-fired industrial air heaters shall not be used to supply any area containing what type of room?
611.2
Every boiler or modular boiler must have a shutoff valve in which two piping components?
1005.1
For undiluted propane calculations using the equation factors listed, what is the value designated as Cr?
402.4; Table 402.4
A condition where thermal energy is not transferred from a solar thermal collector by means of the flow of a heat transfer fluid is known as what?
Chapter 2 – Definitions
During the brazing operation, the inert gas supply must be maintained through the piping at a minimum pressure of 1.0 psi (6.89 kPa) and what maximum pressure?
1108.3.1
What is the minimum exhaust rate per lamp for xenon motion picture projectors without an exhaust connection?
502.11.2
Liquid adhesive coatings used on air filters must have a flash point not lower than what minimum temperature?
605.1
Food-grade fluid used as a heat transfer fluid containing additives must be third-party listed by an approved agency to the appropriate section of which regulations?
1403.3, 20
Where must the permit or a copy be kept until the completion of the project?
105.4.7
Which commercial appliances are an exception to the general requirement to discharge products of combustion to a vent, factory-built chimney, or masonry chimney?
801.2 Exception, 507
What is the required Exhaust Airflow Rate in CFM/ft squared for a Wood/metal shop in an education facility?
Table 403.3.1.1
A sediment trap must be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical, except for which common appliance?
408.4
A Ceiling Radiation Damper is a listed device installed in a ceiling membrane of a fire-resistance-rated assembly to automatically limit what?
Chapter 2 – Definitions
For a chimney serving low-heat appliances (1,000°F normal operation), what is the minimum required clearance to combustible construction for interior installation?
Table 510.2
Solar thermal equipment and appliances must conform to the requirements of Chapter 14 and which specific standard?
1401.4
For structures located in flood hazard areas, appliances, equipment, and system installations must be located at or above the elevation required by which section of the International Building Code?
301.11
The code official shall have the authority to authorize temporary connection of a system to a utility for what purpose?
109.2
What is the minimum diameter for a Large-Diameter Ceiling Fan?
Chapter 2 – Definitions
It shall be unlawful for a person to erect, construct, alter, repair, remove, demolish or utilize an installation in conflict with or in violation of:
113.1
What is the function of an Evaporator in a refrigeration system?
Chapter 2 – Definitions
A pressure relief valve installed on the low-pressure side of a hydronic piping system (where pressure has been reduced) must be set at what pressure?
1205.2
A pressure regulator set in series with another pressure regulator for the purpose of preventing an overpressure in the downstream piping system is a:
Chapter 2 – Definitions
Solid fuel-burning appliances must be provided with combustion air in accordance with what documentation?
701.1
What must the code official carry when inspecting structures or premises in the performance of duties under this code?
104.5
What nominal pipe size requires displacement with an inert gas for any length of piping removed from service?
406.7.1.1; Table 406.7.1.1
Lead pipe requires continuous support in the horizontal direction and what maximum spacing in the vertical direction?
Table 305.4
Flue lining systems for Category I appliances shall include flue lining systems complying with Section 501.12 or chimney lining systems listed and labeled for use with Type B vents.
501.13
From which of the following spaces shall return air for heating or air-conditioning systems NOT be taken?
601.5
What identification must each length of pipe and tubing and each pipe fitting utilized in a mechanical system bear?
301.3
The operating mechanism for natural ventilation openings shall be provided with ready access so that the openings are readily controllable by whom?
402.1
Liquid combustion byproducts of condensing appliances must be discharged to an approved plumbing fixture or disposal area in accordance with whose instructions?
307.2
If an alternative material, design, or method of construction is not approved, the code official shall respond in writing stating what?
104.2.3.2
Evaporative cooling equipment must be installed on level platforms in accordance with which section of this code?
928.1
Where piping passes through concrete or masonry walls, what must be provided for protection?
704.1.2.3.7
Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances is defined as what?
Chapter 2 – Definitions
What is the equivalent length reduction for a 4-inch radius mitered 90-degree elbow in a domestic dryer exhaust duct?
Table 504.9.4.1
An alternative material, design, or method of construction must comply with the what of the provisions of this code?
104.2.3.3
Which term refers to the means that first requires the removal or movement of a panel or similar obstruction to reach a device or equipment?
Chapter 2 – Definitions
If a term is not defined through the authorized methods, what meaning shall it have?
201.4
If a request for an alternative material or design is not approved, how shall the code official respond?
104.2.3.2
Where is nonmetallic fuel oil pipe permitted to be installed?
1302.4
When vents pass through insulated assemblies, what must be installed to provide clearance between the vent and the insulation material?
802.8, 18
In an attic, what are the minimum clear access opening dimensions required to allow removal of the largest appliance?
306.3
What test medium is prohibited from use when pressure testing gas piping systems?
406.2
What is the maximum diameter allowed for a chimney connector for a domestic-type appliance that passes through a wall constructed of combustible material using one of the methods in Table 803.10.4?
803.10.4, 26
The point of discharge of condensate drains must be located within the same occupancy, tenant space, or dwelling unit as the source of the condensate, except where discharging to what location?
307.2.1.1
Where must the midpoint of the water-gauge glass be installed on a steam boiler?
1010.2.1
An automatic shutoff valve installed in the gas supply piping that shuts off when unsafe conditions occur and remains closed until manually reopened is a(an):
Chapter 2 – Definitions
An automatic valve that opens and closes a relief vent, depending on whether the pressure is above or below a predetermined value, is a:
Chapter 2 – Definitions
What is the capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 900 feet in length, operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(5)
For residential-type appliances, if not installed in unconditioned areas, a vent connector made of aluminum (1100 or 3003 alloy) sheet must be not less than what minimum thickness?
503.10.2.3
A self-contained appliance for supplying steam or hot water is defined as a:
Chapter 2 – Definitions
What is the minimum required clearance from the top of a high-pressure steam boiler with steam generating capacity not exceeding 5,000 pounds per hour to the ceiling?
Table 1004.3.1
Protective steel shield plates must extend not less than how many inches above sole plates and below top plates?
305.5
Vent caps for liquid fuel vent pipes shall not employ screens finer than what mesh size?
1305.7
Where a device having an open flame or surface temperature greater than 800°F (427°C) is used in a room containing more than 6.6 pounds (3 kg) of refrigerant in a single independent circuit, what must be provided?
1104.3.4
The action of a control from its maximum to minimum position in either predetermined steps or increments of movement as caused by its actuating medium is defined as:
Chapter 2 – Definitions
Hydrogen-generating and refueling appliances must be installed and located in accordance with their listing and what other documentation?
304.5
Appliances, equipment, and systems regulated by this code are prohibited from being located in which area?
301.15
If a metal ventilating hood is installed above a cooking top to reduce vertical clearance to 24 inches, the hood must be constructed of sheet metal not less than what minimum thickness?
623.7
Taking return air from a kitchen is permitted if the return air openings serve the kitchen and are located not less than how far from the cooking appliances?
601.5 Exception 1
In the absence of recognized test standards, who shall approve the testing procedures?
104.2.2.4
What is the minimum required thickness for protective steel shield plates?
305.5.1
A listed smoke damper designed to resist the passage of smoke must be provided at each point a duct or air transfer opening penetrates which two types of building assemblies?
607.5.4
Appliances equipped with draft hoods or atmospheric burners shall not be located in the same room or space containing a Type I or Type II hood unless the appliance is located in what?
507.1.3
What is the minimum clearance required on the control side of a floor furnace?
910.4
The connection of solid fuel appliances to chimney flues serving fireplaces must comply with which two specific sections?
905.2
How shall articles being sprayed be positioned within a spray booth?
502.7.3.4
For an MP regulator located indoors, what device must be equipped if the regulator is not vented to the outdoors?
410.2
What is the maximum length of overlap allowed for overlapping grease duct joints?
506.3.2.1
A ventilating hood shall be provided above a domestic open-top broiler unit, and a minimum clearance of what distance shall be maintained between the cooking top and combustible material above the hood?
623.5.1
An appliance shall not be connected to a flue serving a factory-built fireplace unless the appliance is specifically listed for such installation.
501.7.2
Where 150-pound pressure-rated steel flanges are bolted to Class 125 cast-iron flanges, which feature of the steel flange must be removed?
403.11.6
What is the maximum height above grade plane for Group R-2, R-3, and R-4 occupancies that must be provided with outdoor air and local exhaust in accordance with Section 403.3.2?
403.3
For Group A2L and B2L refrigerant detectors, at a concentration less than or equal to the OEL, what is the maximum required response time in seconds to signal an alarm?
Table 1106.4.2
The underground inspection shall be made after trenches or ditches are excavated and bedded, and piping is installed, but prior to:
111.2
What is the maximum capacity in cubic feet per hour (cfh) for 1 1/4-inch nominal Schedule 40 metallic pipe at a length of 50 feet, for natural gas at less than 2 psi inlet pressure and 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
When are exhaust fans serving separate dwelling or sleeping units permitted to be connected to a common duct or shaft?
501.6
A relief device must be located so that a section of the pressurized system cannot be valved off or otherwise isolated from what component?
1402.3.1, 5
When connecting an appliance to an existing chimney or vent, the flue gas passageway must be free from obstructions, combustible deposits, and must be cleaned if previously used for venting what type of appliance?
801.18.2, 12
Products of combustion from appliances plus excess air plus dilution air in the vent connector, gas vent or chimney above the draft hood or draft regulator are defined as:
Chapter 2 – Definitions
Appliances shall not be located in a hazardous location unless they are listed and approved for the:
303.2
Which components are generally exempt from field testing requirements for refrigeration piping systems?
1110.1 Exception
High-probability equipment using Group A2L, A2, A3, or B1 refrigerant must comply with UL 484, UL/CSA 60335-2-40, or which other standard?
1101.2.1
A Limit Control is a device responsive to changes in pressure, temperature, or what other factor, for turning on, shutting off, or throttling the gas supply to an appliance?
Chapter 2 – Definitions
Where any cooking appliance under a single hood requires a Type I hood, what type of hood must be installed?
507.1
What does a notice of violation or order issued by the code official direct the responsible person to do?
114.2
Piping installed downstream of the point of delivery is prohibited from extending through any townhouse unit other than:
404.3
For appliances located in attics, the required unobstructed passageway must be not less than 30 inches high and 22 inches wide and not more than what length measured along the centerline?
306.3
What is defined as the rapid oxidation of fuel accompanied by the production of heat or heat and light?
Chapter 2 – Definitions
Equipment and appliances installed at grade level must be supported on a level concrete slab or other approved material extending not less than what distance above adjoining grade?
305.7
In indirect solar thermal hot water heating systems, what is prohibited from being connected to the solar heating loop?
1402.5.1, 8
What is the estimated maximum occupant load rate per 1,000 square feet for a General examination room in an outpatient healthcare facility?
Table 403.3.1.1
A permit is not required for a self-contained refrigeration system provided it contains no more than 10 pounds (4.5 kg) of refrigerant or is actuated by motors of what maximum size?
105.2
Catwalks installed to provide required access shall be not less than what minimum width?
306.5
Where is a Double Island Canopy Hood placed?
Chapter 2 – Definitions
Solar thermal systems are intended to utilize solar energy for which purposes?
1401.1
What is the minimum finished dimension required for a cleanout opening located at the base of the shaft in a common multistory duct system for clothes dryers?
504.11
When testing at a pressure greater than 100 psig (689.5 kPa gauge), the testing gauge must have increments of what maximum amount?
705.3.6
Joints between steel pipe or fittings are required to be mechanical joints made with an approved elastomeric seal, or which two other types of joints?
1203.11
Appliances such as coffee brewers and coffee urns, food and dish warmers, hot plates, griddles, and waffle bakers designed for installation on or in a counter are defined as:
Chapter 2 – Definitions
An existing chimney flue liner, inner wall, or vent inner wall must be continuous and free of cracks, gaps, perforations or other damage that would allow the escape of combustion products, including gases, moisture and:
501.15.2
For compensating hoods with makeup air supplied only from the front face discharge and side face discharge openings, what labeling information is NOT required?
508.2 Exception
Hot water storage tanks must be insulated with an R-value of not less than what minimum value?
1402.8.5.1, 17
In a Brazed Joint, the metallic mixtures or alloys used to join metal parts must melt at a temperature above what threshold?
Chapter 2 – Definitions
A nonadjustable device built into an appliance, or made as part of the vent connector from an appliance, that is designed to provide for ready escape of flue gases in the event of no draft, backdraft, or stoppage is a:
Chapter 2 – Definitions
Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), where must the permanent label or tag identifying the length be located?
504.9.5
A completely self-contained furnace suspended from the floor of the space being heated, taking air for combustion from outside such space and with means for observing flames and lighting the appliance from such space, is a:
Chapter 2 – Definitions
What is the minimum slope required toward the hood or a grease reservoir for grease duct systems serving a Type I hood?
506.3.7
Mechanical systems shall not be located in which specific building element?
303.8
Type I hoods must be constructed of steel having a minimum thickness of 0.0466 inch (1.181 mm) (No. 18 gage) or stainless steel not less than what minimum thickness?
507.2.3
An appliance shall not be connected to a flue serving a factory-built fireplace unless what condition is met?
801.10.2, 5
Large mercantile occupancy is defined as premises where more than how many persons congregate on levels above or below street level to purchase personal merchandise?
1103.2
Fireplace stoves must be tested in accordance with which UL standard?
905.1
What is the minimum thickness required for galvanized steel vent connectors?
803.8, 22
A ventilation opening into a sauna room shall be provided, and the opening must be not less than what minimum size?
615.7
Noncanopy-type hoods shall be located not greater than how many feet above the cooking surface?
507.1.6.2
A device or group of devices essentially forming an integral unit for the final conveyance of gas or a mixture of gas and air to the combustion zone, and on which combustion takes place to accomplish the function for which the appliance is designed, is a:
Chapter 2 – Definitions
What is strictly prohibited from being installed in a machinery room if they use combustion air from the room?
1105.5
Used refrigerants shall not be reused in a different owner’s equipment unless tested and found to meet the purity requirements of which AHRI standard?
1102.2.2.3
An installation of pipe, valves or fittings installed on a premises or in a building and utilized to convey fuel gas is defined as:
Chapter 2 – Definitions
Draft hoods and barometric draft regulators must be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the hood or regulator and which system?
503.12.5
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter of 15 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
For structures located in flood hazard areas, plenum spaces located below the required elevation must be capable of resisting what loads and stresses?
602.4
For permanent ladders installed to provide roof access, what is the maximum spacing allowed for rungs on center?
306.5
The code official is authorized to accept reports of approved agencies provided such agencies satisfy the requirements for qualifications and:
111.2.4
Where refrigerants of Groups A2, A3, B2, and B3 are used, the machinery room must conform to what hazardous location classification requirements of NFPA 70?
1106.3
Threaded fittings in metallic piping systems shall not be used in sizes larger than what dimension?
403.9.5
For permanent ladders installed to provide roof access, the side railing shall extend above the parapet or roof edge not less than what minimum height?
306.5
A through-the-wall direct-vent terminal serves an appliance rated at 40,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
Who is authorized to make or require other inspections of construction work to ascertain compliance with the provisions of this code?
111.2.1
What documentation must an approved testing laboratory provide when a product is Third-Party Tested?
Chapter 2 – Definitions
What is the minimum exhaust rate per lamp for electric arc motion picture projectors without an exhaust connection?
502.11.2
Which type of vent is listed and labeled for use with wall furnaces?
Chapter 2 – Definitions
Copper and copper alloy pipe shall not be used if the gas contains more than what average amount of hydrogen sulfide per 100 standard cubic feet of gas?
403.3.3
What is the primary function of the code compliance agency?
103.1
A manually or automatically controlled device to regulate draft or the rate of flow of air or combustion gases is a:
Chapter 2 – Definitions
For ducts conveying explosive or flammable vapors, fumes or dusts, what is the minimum termination distance from combustible walls and operable openings into buildings that are in the direction of the exhaust discharge?
501.3.1
An agency seeking approval must disclose all possible conflicts of interest to confirm its what?
301.8.2.1
An operation performed to verify the gastight integrity of gas piping following its installation or modification is a:
Chapter 2 – Definitions
Which term is NOT an alternate name for a backshelf hood?
Chapter 2 – Definitions
If horizontal grease ducts exceed 75 feet (22 860 mm) in length, what is the minimum required slope?
506.3.7
Who regulates additions, alterations, renovations, or repairs related to building or structural issues in existing buildings?
102.2.1
What is the maximum temperature for hot water furnished by a Low-Pressure Hot-Water-Heating Boiler?
Chapter 2 – Definitions
Pipe and duct insulation contained within plenums must have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with which mounting procedures?
602.3.9
Appliances serving different areas of a building than where they are installed must be permanently marked in an approved manner that uniquely identifies the appliance and what else?
304.12
A draft hood supplied with or forming a part of a listed vented appliance must be installed without alteration, exactly as furnished and specified by the appliance manufacturer.
503.12.2
The amount of supply air in a mechanical ventilation system shall be approximately equal to the amount of what other air component?
403.1
An occupant or person having charge of a premises shall not fail or neglect to permit entry by the code official if the code official has first obtained a:
104.4.1
Where must manufacturer’s installation instructions be available at the time of inspection?
304.1
Guards are required where components that require service are located within 10 feet (3048 mm) of a roof edge and that edge is located more than how many inches above the floor, roof, or grade below?
304.11
Masonry chimneys without the required airspace clearances are permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with which UL standard?
801.18.4 Exception, 13
An appliance designed and installed in such a manner that all of the products of combustion are conveyed directly from the appliance to the outdoor atmosphere through an approved chimney or vent system is a(an):
Chapter 2 – Definitions
Where chemicals that generate corrosive or flammable products are routinely used, fired appliances where these chemicals can enter combustion air shall be located in a mechanical room that is partitioned off and provided with combustion air from:
304.12
Every hot water boiler must have which two gauges, or a combination gauge?
1010.1
A water-level detection device conforming to UL 508 must be provided to shut off the equipment served if installed in which location?
307.2.3
A Fireplace Stove is designed to be operated with the fire chamber doors in which position(s)?
Chapter 2 – Definitions
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than what maximum degree from vertical at any point in the assembly?
805.4, 38
A person shall not make energy source connections to mechanical systems that have been disconnected or ordered to be discontinued until whom authorizes the reconnection and use?
114.6.3
What is the maximum length allowed for a transition duct connecting a domestic dryer to the exhaust duct system?
504.9.3
What is the capacity in cfh for 2-inch nominal Schedule 40 metallic pipe at 500 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(4)
If a new permit is obtained after a permit has expired due to suspension or abandonment, and the work recommences, the fee shall be one-half the amount required for a new permit provided the suspension or abandonment has not exceeded how long?
105.5.3
Heat transfer fluids must be rated to withstand the system’s maximum design temperature under operating conditions without what?
1403.2, 20
The test pressure measuring device must have an accuracy of what maximum percentage of the test pressure?
1110.5
Additions, alterations, renovations, or repairs shall not cause an existing mechanical system to become what?
102.4
Ducts used in systems exhausting nonflammable corrosive fumes or vapors must be constructed of nonmetallic materials that exhibit what maximum flame spread index?
509.8
A machinery room is not required for listed equipment containing not more than what maximum weight of refrigerant, regardless of the safety classification?
1104.2 Exception 1
A Water Heater is any heating appliance or equipment that heats potable water and supplies such water to what system?
Chapter 2 – Definitions
In an Indirect Refrigeration System classified as a Closed System, the secondary fluid is circulated how?
Chapter 2 – Definitions
Where vibration isolation of equipment and appliances is employed, what means shall be used to accomplish the required support and restraint?
301.13
Steel, stainless steel, and wrought-iron pipe shall be not lighter than which schedule?
403.3.2
Underground ducts must have a minimum slope to allow drainage to a point provided with access of not less than what slope?
603.8.1
What is the maximum spacing of supports required for vertical 1-inch O.D. smooth-wall tubing?
415.1; Table 415.1
What is strictly prohibited from connecting to a chimney passageway venting another appliance?
801.11, 6
As applied to gas, the ratio of the weight of a given volume to that of the same volume of air, both measured under the same condition, is defined as:
Chapter 2 – Definitions
A pipe in a hydronic piping system in which the exterior temperature exceeds 250{F} must have a minimum clearance of what distance to combustible materials?
1206.5
The unique identifying alphanumeric value assigned to an individual refrigerant is published in which standard?
Chapter 2 – Definitions
A field-constructed chimney composed of solid masonry units, bricks, stones or concrete is a:
Chapter 2 – Definitions
A pilot that operates during the lighting cycle and discontinues during main burner operation is a(an):
Chapter 2 – Definitions
Where must the makeup air supply system for a commercial kitchen be automatically controlled to start and operate?
508.1
Which occupancy group is exempt from the requirement to provide space-heating systems capable of maintaining 68°F (20°C)?
309.1 Exception
A vented appliance designed for installation within the fire chamber of a vented fireplace, wherein the primary function lies in the aesthetic effect of the flames, is defined as a:
Chapter 2 – Definitions
Fuel oil piping and equipment located in flood hazard areas must be capable of resisting hydrostatic and hydrodynamic loads and stresses, including what specific effect?
1305.2.1
The code official is authorized to issue a stop work order where work is being performed in a manner contrary to the provisions of this code or in a(an):
114.1
What is the Occupational Exposure Limit (OEL) in ppm for R-134a?
Table 1103.1
Chimney connectors are prohibited from passing through which building elements?
803.10.4, 26
Air dispersion systems must be utilized in systems operating under what pressure characteristic?
603.17
As an alternative to prescriptive ventilation methods for hydrogen-generating operations, air supply for ventilation and dilution of flammable gases may be provided by what type of system?
304.5.3
Appliances located in public garages or repair garages shall be installed not less than what distance above the floor?
305.4
For the reduction of required clearances to combustible materials, the allowable reduction must be based on one of the methods specified in Table 308.2 or shall utilize a reduced clearance protective assembly listed and labeled in accordance with which standard?
308.2
What is the minimum internal area (in square inches) required for a clay-tile-lined exterior masonry chimney flue for a 5-inch diameter Type B double-wall connector when used for single appliance venting?
504.2; Table 504.2(3)
When the design and free area of louvers and grilles are unknown, what free area percentage is assumed for metal louvers and grilles in combustion air calculations?
304.1
The code regulates the design, installation, maintenance, and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. What is the fourth regulatory action specified?
101.2
Where Class I liquids are pumped, used, or transferred in bulk plants or terminals, where shall adequate openings for natural ventilation in outside walls be provided?
502.9.5.5.1
What components are strictly prohibited in the rigid metal ductwork of a common multistory exhaust system for clothes dryers?
504.11
A technical opinion and report required by the code official shall be provided to the jurisdiction:
104.2.2.1
A Unit Heater is designed for the delivery of warm air where?
Chapter 2 – Definitions
Masonry fireplaces must be constructed in accordance with which code?
902.1
If factory inspections have been performed on an installation, the system shall have an identifying label permanently affixed indicating:
111.2.5.2
If a person violates a provision of this code after due notice has been served, how is the continuation of that violation measured?
114.4
What is the minimum test duration required for a gaseous hydrogen system test?
705.3.5
For a chimney venting system serving a single appliance with a draft hood, the effective area of the chimney flue shall be not less than the area of the draft hood outlet nor greater than what multiple of the draft hood outlet area?
503.5.5
What is the capacity in cfh for 2-inch nominal OD Polyethylene plastic pipe at a length of 500 feet, for natural gas with an inlet pressure of 2.0 psi and a 1.0 psi pressure drop?
402.4; Table 402.4(22)
For gas cabinets and exhausted enclosures containing highly toxic or toxic compressed gases, what ventilation function are they specifically prohibited from serving?
502.9.7.1, 502.9.7.2
Equipment, materials or products to which have been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory or approved agency is defined as:
Chapter 2 – Definitions
Where a combination system requires water for space heating at temperatures higher than 140F, a temperature-actuated mixing valve conforming to ASSE 1017 must be provided to temper the potable hot water distribution system water to what maximum temperature?
1002.2.2
Air transported to occupied spaces through dust-producing materials by means other than natural convection shall be treated in what manner before entering the occupied space, in accordance with Section 605?
1402.8.2.1, 14
Appliance and equipment vent terminals must be located such that doors cannot swing within what minimum horizontal distance of the vent terminals?
802.9, 19
An employee charged with the enforcement of this code is relieved from personal liability for damages if acting for the jurisdiction in good faith and without:
104.8
The required thickness for hydronic piping insulation shall conform to the requirements of which code?
1204.2
A vented appliance wherein the primary function lies in the aesthetic effect of the flames is a:
Chapter 2 – Definitions
What must be provided prior to placing a gaseous hydrogen system into operation to displace the air in the piping system?
705.5.2
Single-wall metal pipe shall be constructed of galvanized sheet steel not less than what minimum thickness?
503.7.1
For a multiple zone recirculating system, if the Maximum Primary Outdoor Air Fraction [$Max (Z_p)$] is 0.40, what is the System Ventilation Efficiency ($E_v$)?
Table 403.3.1.1.2.3.2 Note b
For flammable vapor areas, the spraying equipment shall be interlocked with the ventilation such that spraying operations cannot be conducted unless the ventilation system is in operation. This system must be kept in operation until when?
502.7.3.1
Temporary uses, equipment, and systems must conform to the requirements of this code as necessary to ensure health, safety, and:
110.2
What concentration characteristic defines highly abrasive particulate that is classified as Abrasive Materials?
Chapter 2 – Definitions
Who is authorized and directed to enforce the provisions of this code?
104.1
Where vents pass through attic space, the insulation shield must terminate not less than what vertical distance above the insulation materials?
502.4
What are the parts of a refrigerating system subject to condenser pressure?
Chapter 2 – Definitions
The holder of a permit for partial construction proceeds at risk without assurance that the permit for the entire installation will be granted, provided that adequate information and detailed statements have been filed complying with all pertinent requirements of this code, and the partial permit has been issued by the:
105.5.1
Where a solar thermal system directly heats potable water for a potable water distribution system, the pipe, fittings, valves and other components must comply with the requirements of which code?
1402.5.2, 9
An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and the roof, is a:
Chapter 2 – Definitions
In a parking garage, connection to a room with a fuel-fired appliance must be by means of a vestibule providing a two-doorway separation, except that a single door is permitted if the sources of ignition in the appliance are what?
304.3.1
To verify compliance with listing standards, the listing standard and manufacturer’s instructions shall be made available to the code official when required to verify:
104.2.1
For undiluted liquefied petroleum gas systems, the point of delivery shall be considered to be the outlet of which device?
Chapter 2 – Definitions
If an emergency exists, what is the code official not required to give prior to stopping the work?
115.3
For a copper brazed swaged fitting connection with a size of 1/2 inch, what is the required minimum cup depth?
Table 1107.5.1
Labeling procedures are set forth in Sections 301.8.1 through which final subsection?
301.8
For Type IV and V dry cleaning systems, the automatically activated exhaust ventilation system must maintain a minimum air velocity of not less than how many feet per minute through the loading door when the door is opened?
502.6.2
In a laboratory space provided with two or more gas outlets, the single dedicated shutoff valve must be located adjacent to which building feature?
409.6
For an exterior masonry chimney serving a single space-heating appliance in a climate zone with a Local 99% Winter Design Temperature of 5 to 16°F, with a vent height of 15 feet and an internal area of 113 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.2; Table 504.2(6)
Which portion of the piping is NOT required to be insulated in a solar thermal system?
1402.8.3.1 Exception, 15
When calculating the installed thickness (R-value) for duct wrap, the installed thickness shall be assumed to be what percentage of the nominal thickness (representing 25 percent compression)?
604.7
To ensure reliability, approved agencies must have adequate equipment to perform all required tests and must periodically perform what action to that equipment?
301.8.2.2
What is a device that transfers heat from one medium to another?
Chapter 2 – Definitions
What Zone Air Distribution Effectiveness is permitted for systems with a floor supply of cool air and ceiling return, provided displacement ventilation achieves unidirectional flow and thermal stratification?
Table 403.3.1.1.1.2 Note e
Where rooms are ventilated through an adjoining room, the minimum openable area to the outdoors shall be based on what total area?
402.3
Where must circulating air for fuel-burning, forced-air-type, warm-air furnaces be conducted into the blower housing from outside the furnace enclosure?
918.4
A valve, installed by the serving gas supplier between the source of supply and the point of delivery, to shut off the entire piping system, is a:
Chapter 2 – Definitions
Electrical connections between appliances and building wiring, including grounding of the appliances, must conform to which standard?
309.2
Repair garages for lighter-than-air fuels (other than hydrogen) shall have air supply inlets and exhaust outlets arranged to provide uniformly distributed air movement, with outlets located where?
502.16.2.1
Which of the following is defined as an Ignition Source?
Chapter 2 – Definitions
A Toilet Room is a room containing a water closet and sometimes a lavatory, but not what other fixture?
Chapter 2 – Definitions
Access to a dedicated enclosure containing an appliance (where combustion air is taken directly from the outdoors) shall be through a solid door equipped with what type of closing device?
303.3 Exception
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a medium-heat appliance?
503.10.5; Table 503.10.5
Indoor mechanical exhaust intake openings must be located where refrigerant leakage is likely to concentrate based on the refrigerant’s relative density to air and what other factors?
1105.6.1.1
A Type B or L gas vent shall terminate not less than what minimum vertical height above the highest connected appliance draft hood or flue collar?
503.6.6
Exemption from permit requirements shall not grant authorization for work to be done in violation of:
105.2
What is the minimum required dimension of the ventilation opening into the sauna room located near the top of the door?
914.5
A listed and labeled chimney composed of factory-made components, assembled in the field in accordance with manufacturer’s instructions and the conditions of the listing, is a:
Chapter 2 – Definitions
A change in a system that involves an extension, addition or change to the arrangement, type or purpose of the original installation is a(an):
Chapter 2 – Definitions
What is the maximum horizontal spacing allowed for supporting steel tubing?
Table 305.4
Condensate piping shall maintain a minimum slope in the direction of discharge of not less than what unit vertical in 12 units horizontal?
307.2
Mechanical systems can be located below the required flood elevation if they are designed and installed to prevent water from entering or accumulating within components and to resist what other loads and stresses?
301.16 Exception
The person issued an annual permit must keep a detailed record of alterations made under the permit, and the code official shall have what level of access to such records?
105.1.2
Joints used underground in ground-source heat pump loop systems shall be of what type?
1210.6
Nonmetallic ducts shall be constructed with which classes of duct material?
603.5
Where the maximum horizontal length of a connector (for multiple appliances) is exceeded, the maximum capacity (FAN Max or NAT Max) of the vent connector must be reduced by what percentage for each additional multiple of the allowed length?
504.3.3
If a roof-mounted pollution-control unit is installed, what is the minimum distance it must be mounted above the roof?
506.5.2
What must be installed as an alternative to required guards?
304.11 Exception
That portion of an appliance designed for the attachment of a draft hood, vent connector or venting system is the:
Chapter 2 – Definitions
Relief valve discharge piping must terminate not more than how many inches above the floor or flood level rim of the waste receptor?
1006.6
A device that will prevent the backflow of one gas into the supply system of another gas and prevent the passage of flame into the gas supply system is a:
Chapter 2 – Definitions
The cross-sectional area of a flue serving a solid-fuel-burning appliance shall be no greater than what multiple of the cross-sectional area of the appliance flue collar?
801.7
The total horizontal distance of a vent plus the horizontal vent connector serving draft-hood-equipped appliances shall be not greater than what percentage of the vertical height of the vent?
503.6.10.2
When using Type B double-wall gas vent connected directly to a single Category I appliance, if the vent height (H) is 6 feet and the vent diameter (D) is 4 inches, what is the maximum input rating (NAT Max) for a Natural Draft appliance?
504.2; Table 504.2(1)
Welding on pressure vessels must be performed by an R-Stamp holder in accordance with the National Board Inspection Code, Part 3, or what other requirement?
1003.3
When considering modifications in flood hazard areas, the code official must determine that the granting of a variance will not cause fraud on or victimization of the public or:
104.2.4.1
Refrigeration systems containing more than what weight of refrigerant require additional stop valves at locations like the inlet of each liquid receiver?
1109.6.2
For a corrugated metallic chimney liner system installed in a masonry chimney, the maximum capacity determined from the Type B vent tables shall be reduced by what percentage?
504.2.7
Where ducts used for cooling are externally insulated, the insulation must be covered with a vapor retarder having a maximum permeance of what value, unless the insulation itself meets this standard?
604.11
For vertical terminations of mechanical draft systems, the vent shall terminate not less than how many feet above any forced air inlet located within 10 feet horizontally?
804.3.5, 34
What is the purpose of a Flue Liner (Lining)?
Chapter 2 – Definitions
When automatically operated, the ventilation system for an enclosed parking garage must cycle to a “Full-on” mode at an airflow rate of not less than how many CFM per square foot of floor area served?
404.1
Smoke detectors required in air distribution systems must be listed and labeled for installation in air distribution systems, and duct smoke detectors must comply with which UL standard?
606.1
Stud wall cavities utilized as air plenums shall not convey air from more than how many floor levels?
602.2.1
Supply and exhaust ducts to the machinery room must be covered with corrosion-resistant screen of not less than what mesh size?
1105.6.2
In areas where stationary motor vehicles are operated, a source capture system must be provided that connects directly to what?
502.14
Stationary fuel-cell power systems having a power outlet not exceeding 10 MW shall be tested in accordance with which ANSI/CSA standard?
633.1
A boiler not listed by a nationally recognized testing agency is a(an):
Chapter 2 – Definitions
For a rectangular aluminum duct with a dimension of 17 inches operating at 1/2-inch water gauge static pressure in a single dwelling unit, what is the minimum sheet metal thickness required?
Table 603.4
A specific heating, or heating and ventilating, furnace incorporating an integral total enclosure and using only outside air for combustion is a(an):
Chapter 2 – Definitions
A nontoxic, gaseous hydrogen system mixture must contain not more than what maximum percentage of oxygen by volume?
702.1
In conjunction with a request to use an alternative material, the code official is authorized to require submittal of a report prepared by a peer reviewer acceptable to the code official. What type of report is this?
104.2.3.7
If an installation is maintained in violation of this code and in violation of a notice, the code official shall institute appropriate action to prevent, restrain, correct, or:
113.6.3
Roof-mounted solar thermal equipment shall not obstruct or interfere with the operation of which items?
1402.2, 4
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 9 inches, and the protection is 1-inch glass fiber or mineral wool batts sandwiched between two sheets of 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Occupiable spaces may be combined into a single Zone if they share similar occupancy classification (Table 403.3.1.1), occupant density, zone air distribution effectiveness, and what fourth factor?
Chapter 2 – Definitions
The code official is authorized to suspend or revoke a notice of approval where it is determined that the building, structure, or premises is in violation of:
107.2
If the vapor concentration monitor shuts down during unmanned spray operations where recirculation is permitted, what volume of air specified in Section 509 must be automatically exhausted?
502.7.3.2 Exception 1
What is the minimum test duration required for each 500 cubic feet (14.2 m3) of pipe volume or fraction thereof in a gaseous hydrogen system?
705.3.5
Fuel oil piping must be tested in accordance with which NFPA standard?
1308.1
Appliances located in private garages shall be installed with a minimum clearance of what distance above the floor?
305.5
What is the minimum net airflow required for a Wall-mounted Canopy Hood used for medium-duty cooking appliances?
507.2.10.3
Where enclosures are not required, what is the minimum clearance required from noncombustible construction and gypsum wallboard attached to noncombustible structures for Type I hood grease duct systems?
506.3.6
What is the required continuous exhaust rate capacity for bathrooms and toilet rooms in Group R-2, R-3, and R-4 occupancies?
Table 403.3.2.3
Machinery rooms larger than what minimum area must have not less than two exits or exit access doorways?
1105.9
When the design and free area of louvers and grilles are unknown, what free area percentage is assumed for wood louvers in combustion air calculations?
304.1
Appliances using forced draft venting and incorporating integral venting means must maintain what minimum clearance between vent terminals and openings through which combustion products enter the building?
804.2.1, 31
What is excluded from being construed as air ducts in the definition of a Duct?
Chapter 2 – Definitions
What must an approved agency do periodically with its test equipment?
301.4.2.2
When a change in occupancy is made, who must certify that the structure meets the intent of governing law for the proposed new occupancy and does not result in any hazard?
102.5
A listed smoke damper designed to resist the passage of smoke shall be provided at each point that a duct or air transfer opening penetrates a fire wall or fire barrier that serves as what?
607.5.1.1, 607.5.2.1
Ducts in a private garage that penetrate a wall or ceiling separating a dwelling from the garage must be constructed of sheet steel having a minimum thickness of not less than what gauge?
603.7
Exhaust outlets for grease ducts must be located not less than how many feet above adjoining grade level?
506.3.13.3
Discrete electrical, plumbing, and mechanical products having exposed combustible material and located in a plenum must be listed and labeled for such use in accordance with which UL standard?
602.3.6
The flash point of the heat transfer fluid utilized in a solar system must be not less than what minimum temperature above the design maximum nonoperating (no-flow) temperature of the fluid attained in the collector?
1403.1, 19
In an Indirect Refrigeration System classified as an Open-Spray System, the secondary coolant is circulated in what kind of contact with the air or other substance to be cooled or heated?
Chapter 2 – Definitions
The maximum horizontal length of a single-wall connector shall be what percentage of the height of the chimney or vent?
503.10.9
In fuel-dispensing areas, the bottom of an air inlet or exhaust opening shall be located not more than how many inches above the floor?
502.1.2
Refrigerant piping and tubing greater than what maximum diameter shall be tested in accordance with ASHRAE 15?
1110.6
Where a listing standard is not specified by the code for equipment, materials, products, or services, the listing shall be based on what?
104.2.1
Brazed joints must be made with a filler metal conforming to which AWS standard?
1203.3.1
Once issued, approved construction documents shall not be changed, modified, or altered without authorization from the:
105.5.1
In a return air system, where must the smoke detector be installed relative to filters, exhaust air connections, and outdoor air connections?
606.2.1
What is the minimum clearance required from the sides and rear of a single-wall metal pipe where the original required clearance was 18 inches, and the protection is 1-inch glass fiber or mineral wool batts sandwiched between two sheets of 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
What is the minimum wall thickness required for copper tubing used as a fuel oil line?
1305.1
Which type of vent is listed and labeled for use with appliances that are listed for use with Type L or Type B vents?
Chapter 2 – Definitions
Commercial refrigerators, freezers, beverage coolers, and walk-in coolers must be tested in accordance with UL 471 or which other standard?
Table 1101.2
The top of a guard required on a roof or elevated structure shall be located not less than how many inches above the elevated surface adjacent to the guard?
304.11
An annual permit may be issued for alterations to an already approved system upon application to any person, firm, or corporation regularly employing at least how many qualified tradespersons?
105.1.1
Pipe insulation installed in buildings must have a maximum flame spread index of what value when tested in accordance with ASTM E84 or UL 723?
1204.1
What phenomenon is NOT listed as a cause of pressure differences resulting in infiltration?
Chapter 2 – Definitions
Oil-fired floor furnaces must be tested in accordance with which UL standard?
910.1
Exhaust outlets that terminate through exterior walls shall not be located within what minimum horizontal distance of any opening in the exterior wall?
506.3.13.2
Corridor dampers must have a minimum fire-resistance rating of what duration?
607.3.2.4
Air intake openings and living space exhaust air openings of an individual dwelling unit can use a factory-built intake/exhaust combination termination fitting if the separation distance is less than what distance?
501.3.1
Where a single appliance has more than one draft hood outlet or flue collar, and manufacturer instructions are absent, the vent connectors must have a minimum rise of what distance?
503.10.3.2
Stainless steel pipe and tubing for hydronic systems must conform to which specific set of ASTM standards?
Table 1202.4
Listed and labeled fireplace accessories must comply with which UL standard?
902.2
Combustion air ducts that are not provided with dampers and that pass through rated construction must be enclosed in a shaft in accordance with which code?
701.2
For all environmental air exhaust, what is the minimum termination distance from a property line?
501.3.1
In Group H occupancies, fire dampers are not required at penetrations of fire partitions where the partition is penetrated by a duct system having a maximum area of what size?
607.5.3 Exception 3
In institutional occupancies, the total of all Group A2, B2, A3, and B3 refrigerants shall not exceed what maximum weight in occupied areas or machinery rooms?
1104.2.1
External hood joints, seams, and penetrations for Type I hoods must be made with a continuous external liquid-tight weld or braze to where?
507.2.5
Evaluation reports issued to support approval of materials or assemblies not specifically provided for in the code must be issued by whom?
104.2.3.6.1
Where appliances requiring service are installed on a sloped roof (3 units vertical in 12 units horizontal or greater) and the roof edge is more than 30 inches above grade, how large must the level platform be on the service side?
306.5.1
Common venting systems for appliances located on more than one floor level are prohibited, except where all served appliances are located in rooms that are accessed only from where?
801.19, 14
A technical opinion and report required by the code official shall be provided without charge to whom?
104.2.2.1
A floor furnace (excluding wall register models) shall not be placed closer than what minimum distance to the nearest wall?
910.2
Which system is an exception to the requirement that air removed by mechanical exhaust systems must be discharged outdoors?
501.3 Exception
Combustion air includes what two components?
Chapter 2 – Definitions
A steel vent connector for a medium-heat appliance with a vent gas temperature exceeding 1,000°F and a diameter of 18 inches or less must be lined with medium-duty fire brick that is not less than how thick?
503.10.2.5
In the “Standby” mode of operation for automatically controlled enclosed parking garage ventilation systems, the minimum airflow rate shall be not less than how many CFM per square foot of floor area served?
404.1
Condensate pumps located in uninhabitable spaces, such as attics and crawl spaces, must be connected to the appliance served such that when the pump fails, the appliance will be prevented from what?
307.3
Drain-back systems must be designed and installed to allow for manual gravity draining of fluids from areas subject to freezing to locations not subject to freezing, and what else?
1402.4.1, 7
In the exception for adjoining spaces, if an exterior opening opens into a thermally isolated sunroom addition, what is the minimum openable area required between the sunroom and the interior room?
402.3 Exception
For Group R-2, R-3, and R-4 occupancies, mechanical ventilation air requirements shall be provided by which system configuration?
403.1
When installing or repairing gas piping, the finished floors, walls, and ceilings that are required to be changed or replaced must be left in a safe structural condition in accordance with the requirements of the:
302.1
What is a factory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant?
Chapter 2 – Definitions
Who is responsible for furnishing the apparatus, instruments, material, and labor required for testing an installation?
111.3.2
A conductor installed to electrically connect metallic gas piping to the grounding electrode system is a:
Chapter 2 – Definitions
Metallic ducts for air distribution systems (other than those within single dwelling units) must be constructed as specified in which standard?
603.4
The connector shall not be smaller than what dimension provided by the appliance manufacturer?
803.3, 20
Piping and piping system components for hydronic systems shall be sized based on what factor?
1201.2
Where shall the listing and labeling of equipment and appliances used for refrigeration be in accordance with?
301.7 Exception
Connections from a utility, source of energy, fuel, or power to any system regulated by this code for which a permit is required shall not be made until authorized by whom?
109.1
Additives contained in a Food-Grade Fluid must be listed in accordance with what code reference?
Chapter 2 – Definitions
Grease duct-to-hood joints must be made with continuous internal or external liquid-tight welded or brazed joints that are smooth, without grease traps, and available for what?
506.3.2.2
What is the minimum closed cup flash point for Class IIIB Combustible Liquids?
Chapter 2 – Definitions
For smoke barriers in non-sprinklered buildings using the pressurization method, the pressure difference across the smoke barrier must be not less than what value relative to the maximum calculated pressure difference produced by the design fire?
512.6.1
Subslab soil exhaust system ducts shall have a minimum slope in the direction of discharge of not less than what slope?
511.3
Explosion control systems must be designed and installed in accordance with which section of the International Fire Code?
310.1
What is the minimum temperature of the products of combustion at the point of entrance to the flue for a High-heat appliance under normal operating conditions?
Chapter 2 – Definitions
Which method allows a venting system (chimney or vent) to pass through a plenum, provided it is installed such that fittings and joints between sections are not installed in the above ceiling space?
601.4 Exception 2
Piping run from a pressure-regulating or pressure-limiting device to the outdoors, designed to provide for the safe venting of gas in the event of excessive pressure in the gas piping system, is defined as:
Chapter 2 – Definitions
What is the capacity in thousands of Btu per hour for CSST Flow Designation 31 at 25 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(33)
For chimney connector wall pass-through systems, insulation material that is part of the system shall be noncombustible and have a thermal conductivity of what maximum value?
Table 803.10.4 Note, 28
Which venting system is required for unlisted appliances?
503.4; Table 503.4
In a repair garage for liquid or odorized gas fueled vehicles, mechanical exhaust systems that are electrically interlocked with the lighting circuit are allowed as an exception to what general requirement?
502.16.2.2 Exception 2
A device that functions to maintain a desired draft in the appliance by automatically reducing the draft to the desired value is a:
Chapter 2 – Definitions
TABLE 614.9.4.1 QUESTION: What is the longest equivalent length required by the table for a single duct fitting in a domestic dryer exhaust duct system?
614.9.4.1; Table 614.9.4.1
Apparatus and devices other than appliances are defined as:
Chapter 2 – Definitions
What specific type of damper is explicitly prohibited from being installed in combustion air ducts?
701.2
What must a clearly identified switch of the break-glass type or with an approved tamper-resistant cover provide for the machinery room ventilation fans?
1106.5.2
The pipe that connects an appliance to a chimney or vent is the:
Chapter 2 – Definitions
Performing work on a mechanical system in conflict with or in violation of any provision of this code shall be deemed what type of act?
114.1
Flexible connectors, expansion, and vibration control devices and fittings must be of what specific characteristic?
1202.7
Structures occupied for purposes involving explosion hazards must be provided with explosion control where required by which code?
310.1
Condensate piping from condensing fuel-burning appliances must maintain a minimum horizontal slope in the direction of discharge of not less than what slope?
307.1
What is the minimum clearance required for radiant panels from an element when mounted on wood or steel framing?
927.3
If appliances or equipment are subject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment, and insulation must be installed where?
307.2.3.2
The side railing of a permanent ladder providing roof access must extend above the parapet or roof edge or landing platform not less than how many inches?
306.5
Subslab soil exhaust system duct material must be air duct material listed and labeled to the requirements of UL 181 for which air duct class?
511.2
Tests required by this code shall be made by the permit holder and observed by the:
111.3
Ambient air that enters a building through a ventilation system, intentional openings for natural ventilation, or by infiltration is defined as what?
Chapter 2 – Definitions
What are the parts of a refrigerating system subject to evaporator pressure?
Chapter 2 – Definitions
A pressure regulator for controlling pressure to the manifold of the appliance is a:
Chapter 2 – Definitions
The treatment of air so as to control simultaneously the temperature, humidity, cleanness, and distribution of the air is known as what?
Chapter 2 – Definitions
In the definition of Commercial Cooking Appliances, what is the criteria regarding the preparation of food?
Chapter 2 – Definitions
Single-wall metal pipe is prohibited from passing through any attic, inside wall, concealed space or:
503.7.6
Shutoff valves are not required in the supply and return piping for a system having which specific type of boiler?
1005.1 Exception
Defective material or parts must be replaced or repaired in a manner that preserves which characteristic?
301.9
The officer or other designated authority charged with the administration and enforcement of this code, or a duly authorized representative, is the:
Chapter 2 – Definitions
For permanent ladders installed to provide roof access, what is the minimum clear width required between rails?
306.5
The maximum length of a domestic clothes dryer exhaust duct shall be 35 feet (10 668 mm) from the connection to the transition duct to the outlet terminal, before reductions for fittings.
614.9.4.1
To prevent the accumulation of flammable vapors during floor resurfacing, what is the minimum mechanical ventilation rate required per square foot of area being finished?
502.7.7
In the One-Permanent-Opening Method (304.6.2), the single opening must commence within what distance of the top of the enclosure?
304.6.2
Refrigeration System Classification is based on the degree of probability that leaked refrigerant will enter an occupied area based on what primary factor?
Chapter 2 – Definitions
The assembled ground-source loop system must be pressure tested with water at 100 psi (689 kPa) for a minimum of how long before backfilling connection header trenches?
1210.1
Flue lining systems for use with residential-type and low-heat appliances shall be limited to clay flue lining complying with ASTM C315 or equivalent, listed and labeled chimney lining systems complying with UL 1777, and what other approved materials?
801.16.1, 10
If a commercial electric dishwasher incorporates a self-contained condensing system listed and labeled in accordance with UL 921, is a hood required?
507.1 Exception 2
A blower or fan used for the purpose of distributing supply air to a room, space or area is a(an):
Chapter 2 – Definitions
Which type of space is explicitly excluded from the definition of an Occupiable Space?
Chapter 2 – Definitions
Transition ducts connecting a domestic dryer to the exhaust duct system shall not be more than what maximum length?
614.9.3
The mechanical ventilation system must also exhaust a volume required to limit the room temperature rise to what maximum differential?
1105.6.3.1
For a roof slope of Flat to 6/12, what is the minimum required vertical height (H) above the roof to the lowest discharge opening?
503.6.5; Figure 503.6.5 (Table)
A Pressure Relief Valve is held closed by a spring or other means and designed to relieve pressure automatically in excess of what?
Chapter 2 – Definitions
What type of valve is a Safety Valve used in a steam boiler?
Chapter 2 – Definitions
What type of fitting may be used to separate air streams between intake air openings and living space exhaust air openings of an individual dwelling unit where the separation distance is less than 3 feet?
401.4
Appliances shall not be installed in a location where subject to mechanical damage unless protected by what?
303.4
Where an emergency exists, the code official is not required to provide a written notice prior to:
114.3
What type of concentration is the Occupational Exposure Limit (OEL) based on?
Chapter 2 – Definitions
A system designed to act to shut off the gas supply to the main and pilot burners if the oxygen in the surrounding atmosphere is reduced below a predetermined level is a(an):
Chapter 2 – Definitions
For natural ventilation in hydrogen-generating locations, the maximum rated output capacity of hydrogen-generating appliances shall not exceed 4 standard cubic feet per minute (0.00189 m3/s) of hydrogen for each how many square feet of floor area?
304.5.1
Smoke damper leakage ratings must be Class I or II, and the elevated temperature ratings shall be not less than what minimum temperature?
607.3.2.2
Electric pool and spa heaters must be tested in accordance with which UL standard?
916.1
In a Low-Probability System, where will a leakage of refrigerant from a failed connection NOT enter?
Chapter 2 – Definitions
Mechanical outdoor air intake openings shall be located not less than how many feet horizontally from any hazardous or noxious contaminant source?
401.4
Connectors must rise vertically to the chimney or vent with a minimum pitch equal to what slope?
803.10.5, 29
Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, handling, or dispensing of which materials occurs?
305.2
For equipment with a capacity over 125 tons up to 250 tons of refrigeration, what is the minimum required condensate pipe diameter?
Table 307.2.2
A Permanent Mechanical Joint that incorporates an elastomeric seal and corrosion-resistant grip or bite ring is called a what?
Chapter 2 – Definitions
What type of appliance is strictly prohibited from being installed within a plenum?
602.1
Air intake openings that terminate outdoors must be protected with corrosion-resistant screens, louvers, or what other devices?
401.5
When required, design submittals must be prepared by, and bear the stamp of, which professional?
104.2.2.2
Materials, equipment, and devices may be reused only if they are in good working condition and:
104.9.1
Which piece of information is required to appear on a permanent factory-applied nameplate affixed to an appliance?
301.5
Plastic ducts used for underground installation must be constructed of PVC having a minimum pipe stiffness of what value at 5-percent deflection?
603.8.3
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 18 inches, and the protection is 3 1/2-inch-thick masonry wall with ventilated airspace?
308.2; Table 308.2
Which material is exempted from carrying the identification of the manufacturer on each length of pipe and tubing?
401.9 (Exception 1)
When required for alternative materials or designs, a peer review report must be prepared by a peer reviewer who is approved by the:
104.2.3.7
Which types of equipment or appliances require condensate drain systems?
307.2
What must be provided for water heaters and hot water storage tanks to ensure easy removal?
1002.1
Where appliances are installed in pits or excavations, the walls of the pit or excavation must be held back not less than what distance from the appliance?
303.7
Ground-source heat pump loop system piping must be marked where it enters a building, indicating “GROUND-SOURCE HEAT PUMP LOOP SYSTEM” and what two other pieces of information?
1210.8.9
Refrigerants reprocessed to the same specifications as for new refrigerants by means including distillation are classified as what?
Chapter 2 – Definitions
If treatment of exhaust for air pollution control is necessary, manifolding of ducts is allowed if what finishing material is specifically prohibited from being used?
502.7.3.5 Exception 2
For existing buildings in flood hazard areas, the code official must determine if proposed work for reconstruction or repair constitutes:
104.3.1
Corridors and other common areas within the conditioned space of Group R-2, R-3, and R-4 occupancies shall be provided with outdoor air at what minimum rate per square foot of floor area?
403.3.2.2
New installations and parts of existing installations that have been altered, extended, renovated, or repaired shall be tested to disclose:
111.3.1
Required test and inspection records for prefabricated mechanical systems shall be available to the code official at all times during the fabrication of the system and what other process?
111.2.5.3
Before a permit is issued, the code official is authorized to inspect and evaluate the systems, equipment, buildings, devices, premises and spaces or areas to be used in a procedure known as a:
105.4
What is the minimum clearance to combustibles required for chimney connectors serving medium-heat oil and solid-fuel appliances?
Table 803.10.6, 30
Which type of appliance must be used in a dwelling unit kitchen where the kitchen and living spaces are in a single room, and return air is taken within 10 feet of the cooking appliance?
601.5 Exception 2
If a portion of this code is held to be unconstitutional, what effect does this decision have on the validity of the remaining portions?
101.4
A pipe or other conduit composed of factory-made components, containing a passageway for conveying combustion products and air to the atmosphere, listed and labeled for use with a specific type or class of appliance, is a:
Chapter 2 – Definitions
Which type of floor furnace depends primarily on circulation of air by gravity and includes those equipped with booster-type fans that do not materially restrict free circulation when not operating?
Chapter 2 – Definitions
A connection from a utility, source of energy, fuel, or power shall not be made to any regulated building or system for which a permit is required until authorized by the:
109.1
A permittee holding an unexpired permit shall have the right to apply for an extension of time. Provided there is reasonable cause, the code official shall extend the time for a period not exceeding how many days?
105.4.4
If the depth of an appliance pit or excavation exceeds 12 inches (305 mm) below adjoining grade, the pit walls must be lined with concrete or masonry extending not less than how far above adjoining grade?
303.7
What is the minimum testing standard for electric residential clothes dryers?
913.1
A medium-heat appliance has products of combustion temperatures at the point of entrance to the flue that are more than 1,000°F (538°C) but not greater than:
Chapter 2 – Definitions
Floor furnaces installed in upper stories must be separated from the nonhabitable space below by an enclosure constructed of what type of material?
609.6
Space within a dwelling unit utilized for living, sleeping, eating, cooking, bathing, washing and sanitation purposes is defined as:
Chapter 2 – Definitions
When using the Two-Permanent-Openings Method (304.6.1) and communicating with the outdoors through horizontal ducts, what is the minimum free area required for each opening per 2,000 Btu/h of total appliance input rating?
304.6.1
Interpretations, policies, and procedures adopted by the code official shall not have the effect of:
104.2
A connector entering a masonry chimney must be cemented to the masonry in an approved manner, and where thimbles are installed to facilitate removal, the thimble must be permanently cemented in place with what?
803.10.3, 25
The fuel input rate for an appliance shall not be increased or decreased beyond the limit rating for what specific environmental factor?
301.12
Vent connectors are generally prohibited from being covered with insulation, except when the connectors are:
503.10.2.3 (Exception)
If a code provision is less restrictive than the conditions of the listing or the manufacturer’s instructions, which provisions shall apply?
304.2 Exception
A device responsive to changes in pressure, temperature or level for turning on, shutting off or throttling the gas supply to an appliance is a:
Chapter 2 – Definitions
Gas-fired appliances shall be vented in accordance with which other code?
801.1
Which type of LP-gas appliances and equipment is generally outside the scope of this code?
101.2.5
Semirigid metallic tubing used to connect an appliance to the piping system must be located entirely in the same room as the appliance and shall not exceed what maximum length?
411.1
Which portions of a hydronic piping system are an exception to the requirement that the entire system must be designed and installed to permit draining?
1206.2 Exception
Vented gas fireplaces shall be listed in accordance with which ANSI/CSA standard?
604.1
What is the minimum air gap required between a clearance reduction system using a ventilated airspace and combustible walls and ceilings?
308.2
A valve of the plug and barrel type designed for use with gas, and equipped with a lever handle for manual operation and a dial to indicate the percentage of opening is a:
Chapter 2 – Definitions
Liquid-level indicating gauges for fuel oil systems must comply with which UL standard?
1306.4
Vent pipe outlets for purging gaseous hydrogen systems shall be located not less than what minimum height above the adjacent ground level?
705.5.3.1
Elevation of the ignition source is NOT required for appliances that are listed as what?
304.3 Exception
Foam plastic used as interior wall or ceiling finish or interior trim in plenums is permitted to exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less if it is separated from the airflow by corrosion-resistant steel having a base metal thickness of not less than what dimension?
602.3.7 Exception 2
In a common multistory duct system for clothes dryers, the exhaust fan must run continuously and be connected to what?
504.11
An appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber or heat exchanger is a(an):
Chapter 2 – Definitions
Which valve controls the gas supply to an individual main burner?
Chapter 2 – Definitions
When calculating Net Occupiable Floor Area, how shall obstructions such as furnishings, display or storage racks, whether temporary or permanent, be treated?
Chapter 2 – Definitions
What must be done to abandoned inlet openings in chimneys and vents?
801.8
Where vents pass through insulated assemblies, an insulation shield must be installed, constructed of steel having a minimum thickness of what gauge (0.0187 inch)?
502.4
What is the minimum required clearance from the top of a high-pressure steam boiler having heating surface in excess of 1,000 square feet to the ceiling?
Table 1004.3.1
Where terms are not defined in this code, they shall have meanings ascribed to them as defined in which other referenced code?
201.3
When testing at a pressure of 10 psig (68.95 kPa gauge) or less, the testing gauge must have increments of what maximum amount?
705.3.6
What is the minimum distance required between the lowest edge of a grease filter and an exposed flame or burner cooking surface?
Table 507.2.8
Who is the designated authority charged with the administration and enforcement of this code?
Chapter 2 – Definitions
What is the minimum separation distance required for the atmospheric venting of Compressed Natural Gas (CNG) from buildings?
413.10.2.3; Table 413.10.2.3
The code official shall be appointed by which authority?
103.2
Vented wall furnaces must be located so that a door cannot swing within what minimum distance of an air inlet or air outlet of the furnace?
909.3
What is the minimum letter height required for the permanent warning notice attached to the outside of a commercial sauna room?
914.5.1
What is the minimum clearance required to combustibles for hazardous exhaust ducts conveying flammable vapors?
Table 509.8.2
Penetrations of floor/ceiling assemblies and assemblies required to have a fire-resistance rating must be protected in accordance with the:
302.2
A Type B-W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected.
503.6.3
A permit shall not be valid until:
108.1
Electrical wiring, controls, and connections to equipment and appliances regulated by this code must be in accordance with which standard?
301.1
What is the maximum acceptable flame spread distance for combustible electrical wires and cables exposed within a plenum when tested in accordance with NFPA 262?
602.3.3
Rigid metallic pipe and fittings, semirigid metallic tubing and fittings or a listed and labeled device that connects an appliance to the gas piping system is a(an):
Chapter 2 – Definitions
A Duct Furnace depends on a blower not furnished as part of the furnace for what purpose?
Chapter 2 – Definitions
Additions, alterations or repairs shall not cause an existing installation to become:
102.4
If the outdoor air ventilation system in a dwelling unit does not operate continuously, what is the minimum required operation time within each 4-hour period?
403.3.2.1 Exception 1
In the brazing process, how is the filler material distributed between the closely fitted surfaces of the joint?
Chapter 2 – Definitions
Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with which code?
301.11
Type L vents shall terminate not less than how many feet above the highest point of the roof penetration?
802.5, 17
A single unit providing complete, independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation, is a:
Chapter 2 – Definitions
If the depth of an underfloor passageway or service space exceeds 12 inches (305 mm) below adjoining grade, the walls of the passageway must be lined with what material?
306.4
Stationary fuel cell power systems having a power output not exceeding 10 MW must be tested in accordance with which standard?
924.1
What is the maximum capacity in cfh for 3/4-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 500 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(20)
If the quantity of refrigerant in an independent circuit exceeds the amounts in Table 1103.1, all components containing the refrigerant shall be located either outdoors or where?
1104.2
An adapter for joining plastic pipe to steel pipe, providing a permanent, pressure-tight connection between two materials that cannot be joined directly one to another, is defined as:
Chapter 2 – Definitions
For connection to a masonry fireplace flue, the connector shall extend from the appliance such that the flue gases are exhausted directly into the flue, and the connector must be provided with access or be what?
801.10.3, 6
Shutoff valves must be installed at connections to which type of expansion tanks?
1205.1.6
Uninsulated single-wall metal pipe is prohibited from being used outdoors for venting appliances in regions where the 99-percent winter design temperature is below what temperature?
503.7.2
The use of gypsum boards to form air shafts (ducts) is limited to which type of air system?
603.5.1
Who shall keep a record of each inspection made, including notices and orders issued?
104.7.2
Floor-mounted-type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not less than what minimum distance?
620.4
An Offset (Vent) is a combination of approved bends that makes how many changes in direction?
Chapter 2 – Definitions
Boilers shall be designed, constructed, and certified in accordance with the ASME Boiler and Pressure Vessel Code, Section I or which other section?
1004.1
What is the minimum termination distance required for chimneys or vents equipped with power exhausters from the lot line or adjacent buildings?
804.3.3, 33
Equipment or machinery at lumber yards that generates combustible dust must be provided with an approved dust-collection and exhaust system installed in accordance with this section and what other code?
509.2.1
When the code official finds work regulated by this code being performed in a manner contrary to the provisions of this code, the code official is authorized to issue what?
115.1
What is the minimum number of bottom blowoff valves required for a steam boiler where the maximum allowable working pressure exceeds 100 psig (689 kPa)?
1008.1
In a High-Probability System, leakage of refrigerant from a failed connection will enter where?
Chapter 2 – Definitions
What is required to be provided in each vertical riser of a clothes dryer exhaust duct?
504.3
Thread lubricant, pipe-joint compound or thread tape must be applied only on which part of a threaded joint?
1108.3.4
An airflow differential pressure control on a pollution-control unit must activate a visual alarm located where when the airflow is reduced below the design velocity?
506.5.2
Raised face flanges shall not be joined to which type of flat-faced flange?
403.11.5
In a Limited Charge System, with the compressor idle, the design pressure will not be exceeded when what condition occurs?
Chapter 2 – Definitions
Ladders over 30 feet (9144 mm) in height must be provided with offset sections and landings capable of withstanding what minimum load?
306.5
What is the minimum thickness required for steel construction of a Type II hood?
507.3.1
An application for a permit shall be deemed abandoned how many days after the date of filing, unless pursued in good faith or a permit has been issued?
105.3.2
What is the primary function of a Control device?
Chapter 2 – Definitions
A device placed in a gas line between the service pressure regulator and the appliance for controlling, maintaining or reducing the pressure in that portion of the piping system downstream of the device is a:
Chapter 2 – Definitions
Steam bath equipment must be listed and labeled in accordance with which UL standard?
931.1
Materials that, where tested in accordance with ASTM E136, meet criteria regarding temperature rise, flaming duration, and weight loss are defined as:
Chapter 2 – Definitions
An approved automatic fire suppression system is required in hazardous exhaust ducts, except where the largest cross-sectional diameter of the duct is less than how many inches?
509.7 Exception 3
If a single hood serves a combination of light-, medium-, and heavy-duty cooking appliances, which duty classification must the required exhaust rate be based on?
507.2.10
A gas-burning, automatically operated appliance for supplying cooled air, dehumidified air, or both, or chilled liquid is a(an):
Chapter 2 – Definitions
The category of combustible liquids does not include which of the following?
Chapter 2 – Definitions
What is the capacity in thousands of Btu per hour for CSST Flow Designation 37 at 300 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(32)
What type of exhaust systems are prohibited from sharing common shafts with other duct systems?
509.4
Which type of temperature relief valve automatically opens and closes a relief vent, depending on whether the temperature is above or below a predetermined value?
Chapter 2 – Definitions
Required ventilation systems for dip tank operations shall be arranged such that the failure of any ventilating fan will automatically stop what component?
502.7.4
What is the distinguishing fuel characteristic of an Extra-Heavy-Duty Cooking Appliance?
Chapter 2 – Definitions
If there is insufficient evidence of compliance, who has the authority to require tests as evidence of compliance?
104.2.2.4
For acceptance tests conducted on boilers and pressure vessels, the pressure gauge scale shall be graduated over a range of not less than one and one-half times and not greater than what multiple of the maximum test pressure?
1011.2
Exhaust ducts for domestic clothes dryers must have a smooth interior finish and be constructed of metal not less than what minimum thickness?
614.9.1
If an outdoor opening is rectangular, the size requirements for openings in louvers, grilles, and screens apply to which side?
Table 401.5
Which openings are NOT allowed in the combustion chamber of a Closed Combustion Solid-Fuel-Burning Appliance?
Chapter 2 – Definitions
When using compression-type mechanical joints on plastic piping, an internal tubular rigid stiffener shall be used and must be located flush with which part of the pipe?
403.1
The fuel gas piping, valves and fittings from the outlet of the point of delivery to the outlets of the appliance shutoff valves is defined as the:
Chapter 2 – Definitions
Refrigeration systems containing carbon dioxide (R-744) must also comply with which IIAR standard?
1101.1.1
Appliances and supports exposed to wind must be designed and installed to resist wind pressures in accordance with which code?
301.1
Shutoff valves used in fuel oil systems must comply with which UL standard?
1307.1
Smoke detectors are generally required for return air systems with a design capacity greater than how many CFM?
606.2.1
Tapes and mastics used to seal fibrous glass ductwork must be listed and labeled in accordance with which UL standard?
603.9
Where the refrigerant-containing parts of a system are located in one or more spaces that do not communicate through permanent openings or HVAC ducts, the volume of which space determines the permissible refrigerant quantity?
1104.4.1
Forced draft systems and portions of induced draft systems under positive pressure must be designed and installed to be what characteristic to prevent leakage of combustion products?
804.3.1, 32
What component of systems is NOT included in the definition of Equipment?
Chapter 2 – Definitions
Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, which requirements shall apply?
102.8 (Exception)
Appliances installed in other than indoor locations must be listed and labeled for what type of installation?
303.6
Tests conducted to demonstrate equivalency for an alternative material must be of a scale that is sufficient to predict what aspect of the end use configuration?
104.2.3.5
The container placed at a low point in a system of piping to collect condensate and from which the condensate is removable is a:
Chapter 2 – Definitions
What is a device actuated by another device, to govern succeeding operations of the same or allied devices?
Chapter 2 – Definitions
A person who continues any work after being served with a stop work order, except work directed to remove a violation, shall be subject to:
114.4
Before a change in occupancy is made that subjects the structure to any special provision of this code, what must first be obtained?
102.5
Requirements necessary for public safety, health and general welfare that are not specifically covered by this code shall be determined by the:
102.9
An automatic or semiautomatic device consisting essentially of a valve and operator that control the gas supply to the burner(s) during operation of an appliance is a(an):
Chapter 2 – Definitions
Commercial electric water heaters must comply with which UL standard?
1002.1
Pipe hangers and supports in direct contact with piping shall be of approved materials that are compatible with the piping and will not promote what type of action?
305.2
An unvented gas log heater can only be installed in a factory-built fireplace if the system has been specifically tested, listed, and labeled for such use in accordance with which standard?
903.3
Which appliance may be installed in a sleeping room if it is a direct-vent appliance?
303.3
Household cooking appliances shall have a vertical clearance above the cooking top of not less than 30 inches (760 mm) to combustible material and metal cabinets, unless the clearance is reduced to 24 inches (610 mm) and what minimum thickness of insulating millboard is used for protection?
623.7
During occupied conditions, the normal mechanical ventilation system must exhaust not less than 0.5 cfm per square foot (0.0025 m3/s × m2) of machinery room area or what other minimum rate per person?
1105.6.3.1
The maximum flame spread index and smoke-developed index requirements for pipe insulation do not apply to which specific building type?
1204.1 Exception
Where are fireplaces and solid fuel-burning appliances prohibited from being installed?
901.3
What is the minimum required thickness (in inches) for a steel vent connector serving a medium-heat appliance with a diameter of up to 14 inches?
503.10.2.5; Table 503.10.2.5
A Vented Room Heater burns which types of fuel?
Chapter 2 – Definitions
Shutoff valves serving movable appliances (such as cooking appliances) are considered provided with access when installed where?
409.5.1
What is the capacity in cubic feet per hour (cfh) for CSST Flow Designation 37 at a length of 50 feet, for natural gas with a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(16)
The flash point of transfer fluid in a hydronic piping system shall be not less than what minimum temperature above the maximum system operating temperature?
1207.1
In addition to being experienced in conducting and supervising tests, personnel employed by an approved agency must be educated in evaluating what?
301.8.2.3
Combination potable water-heating and space-heating systems must be sized to prevent the space-heating load from diminishing what other required capacity?
1002.2.1
Stop valves on copper tubing or aluminum tubing 1 inch (25.4 mm) outside diameter or larger shall not be supported by what?
1109.6.3
Interior spaces intended for human occupancy must be provided with active or passive space-heating systems capable of maintaining an indoor temperature of not less than how many degrees Fahrenheit?
309.1
Commercial-industrial-type incinerators shall be constructed and installed in accordance with which NFPA standard?
607.1
Outdoor or return air for forced-air heating and cooling systems shall not be taken closer than what minimum distance from an appliance vent outlet?
618.3
A Protective Assembly (Reduced Clearance) that is attached directly to a combustible assembly shall not be considered as part of what?
Chapter 2 – Definitions
Unless ready access is provided for complete inspection at the site, in-plant inspections of prefabricated systems shall be conducted by the code official or an independent, approved inspection agency to ensure conformance to the approved evaluation report.
111.2.5.2
Where natural draft venting systems for Category I appliances include offsets, the offsets shall not exceed what maximum angle from the vertical?
503.6.10.2
Outdoor Air is defined as air taken from the outdoors and is characterized as not having been previously circulated through what?
Chapter 2 – Definitions
Clearances to combustible construction must be reduced only in accordance with which section?
304.9
What is the LFL (Lower Flammability Limit) for R-1234yf in parts per million (ppm)?
Table 1103.1
For 3/4-inch Nominal OD Polyethylene plastic tubing (SDR 11) at a length of 500 feet, what is the capacity in cubic feet per hour (cfh) for natural gas with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(24)
Equipment, appliances, and supports that are exposed to wind must be designed and installed to resist wind pressures determined in accordance with which code?
301.15
Where a separate means is used to supply ventilation air to a direct-fired industrial air heater, what must be provided to ensure the main burner does not operate without the air supply?
612.5
A valve that automatically opens and closes a vent for relieving a vacuum within the hot water supply system, depending on whether the vacuum is above or below a predetermined value, is a:
Chapter 2 – Definitions
Where the space above a suspended ceiling is continuous and part of the supply or return air plenum system, how is this space treated in volume calculations?
1104.4.3
An appliance converted from the fuel specified on its rating plate for use with a different fuel requires reapproval from whom?
1301.3
If work fails an initial test or inspection, what must be done to the work or installation before resubmission to the code official?
111.3.3
What is the testing standard a material must pass to be classified as a Noncombustible Material?
Chapter 2 – Definitions
Plastic pipe, fittings, and components must be third-party certified as conforming to which standard?
301.4
Heat exchangers utilizing a nonfood-grade fluid must be separated from the potable water by what means?
1402.8.4.1, 16
An appliance vented by natural draft shall not be connected into a vent, chimney, or vent connector on which side of a mechanical flue exhauster?
804.3.6, 35
What is the combination of outdoor and transfer air intended to replace exhaust air and exfiltration?
Chapter 2 – Definitions
A Welded Joint is a gastight joint obtained by joining metal parts in what state?
Chapter 2 – Definitions
A space is considered indirectly heated or cooled if it is separated from conditioned spaces by what specific feature?
Chapter 2 – Definitions
For enclosed structures involving organic coating processes using Class I liquids, what is the minimum ventilation rate required per square foot of solid floor area?
502.12
Which type of vent is listed for use with oil-burning appliances and gas appliances listed for venting with Type B vents?
Table 802.2, 16
Within dwelling units, unobstructed stud and joist spaces are permitted to convey combustion air, provided that not more than how many required fireblocks are removed?
304.11
A fire chamber and hearth constructed of noncombustible material for use with solid fuels and provided with a chimney is a:
Chapter 2 – Definitions
Air from a swimming pool and associated deck areas shall not be recirculated to other spaces where more than what percentage of the resulting supply airstream consists of air recirculated from these spaces?
403.2.1
When using Type B double-wall gas vent connected by a single-wall metal connector to a single Category I appliance, if the vent height (H) is 8 feet, the lateral (L) is 5 feet, and the vent diameter (D) is 9 inches, what is the minimum input rating (FAN Min)?
504.2; Table 504.2(2)
A general form of gas-tight joints obtained by the joining of metal parts through a positive-holding mechanical construction is a:
Chapter 2 – Definitions
For the purposes of hazardous exhaust, what rating of materials, as specified in NFPA 704, is used to define volatile or airborne materials posing a health hazard?
509.1
Ducts shall not be attached to wall furnaces unless what condition is met?
608.5
The function of the code compliance agency is the implementation, administration, and enforcement of the provisions of this code, and the official in charge shall be known as the:
103.1
A self-contained appliance for heating air by transfer of heat of combustion through metal to the air, and designed to supply heated air through ducts to spaces remote from or adjacent to the appliance location, is a:
Chapter 2 – Definitions
If the proposed work conforms to code requirements and all fees have been paid, who shall issue the permit to the applicant?
105.5
Controls and safety devices for boilers with inputs greater than or equal to 12,500,000 must meet the requirements of which standard?
1004.1
When installing a floor furnace, what is the minimum clearance required on the control side of the unit?
609.4
Where a single meter supplies gas to more than one building or tenant, what type of valve must be provided for each building or tenant?
409.3
A burner that depends on draft induced by a fan that is an integral part of the appliance and is located downstream from the burner is a(an):
Chapter 2 – Definitions
What is the capacity in cfh for CSST Flow Designation 30 at 500 feet in length, operating at 2 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(18)
Overlapping duct joints in a grease duct system shall be installed to prevent ledges and obstructions from collecting grease or interfering with what process?
506.3.2.1
For an unlisted appliance having a draft hood, the ventilated metal thimble used where the single-wall metal pipe passes through a combustible exterior wall must be not less than how much larger in diameter than the metal pipe?
503.7.7
Steel pipe joints embedded in concrete must be welded by electrical arc method or what other method?
1209.3.1
If a safety/relief valve discharge termination point is not readily visible and observable, what is required?
1006.6
A joint made in thermoset plastic piping by the use of an adhesive substance that forms a continuous bond between the mating surfaces without dissolving either one of them is a:
Chapter 2 – Definitions
Alternative materials, designs, or methods of construction are permitted provided the alternative is not specifically prohibited by this code and has been:
104.2.3
A valve requiring one-quarter round turn or less to open completely is considered to be what type of valve?
Chapter 2 – Definitions
Domestic booster fans are prohibited from being installed in which system?
504.6
Recirculating direct-fired air heaters shall not be installed in buildings that contain flammable solids, liquids or gases, explosive materials, or substances that can become toxic when exposed to flame or heat.
612.2
The cutting, notching, and boring of holes in structural steel framing members shall be as prescribed by the:
302.5
For fumes or vapors that are heavier than air, exhaust for hazardous material storage shall be taken from a point within how many inches of the floor?
502.8.1.1
What is the capacity in thousands of Btu per hour for 1/2-inch nominal O.D. Polyethylene plastic tubing (SDR 7) at 200 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(37)
Fans providing exhaust or outdoor air in Group R-2, R-3, and R-4 occupancies shall be listed and labeled to provide the minimum required air flow in accordance with which standard?
403.3.2.5
Exhaust ducts for domestic clothes dryers must be constructed of metal with a minimum thickness of how many inches?
504.9.1
Which vented appliance category operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent?
Chapter 2 – Definitions
Insulation R-values for slab-on-grade and suspended floor installation for radiant heating systems must be in accordance with which code?
1209.5
For a nondirect-vent terminal, what is the minimum clearance required below or to the side of an openable window or door opening (Clearance B)?
503.8; Table 503.8
An air compartment or chamber to which one or more ducts are connected and that forms part of an air distribution system is a:
Chapter 2 – Definitions
The passage(s) within an appliance through which combustion products pass from the combustion chamber to the draft hood inlet opening or appliance outlet is the:
Chapter 2 – Definitions
Refrigerant piping systems erected in the field shall be pressure tested for strength and leak tested for tightness after installation and before being placed in operation, in accordance with which section?
1110.1
The furnace must be placed such that a drapery or similar combustible object will not be nearer than what minimum distance to any portion of the register of the floor furnace?
910.2
Any portions of construction that do not comply with this code shall be corrected and shall not be covered or concealed until authorized by the:
111.2.3
Ambulatory care facilities provide care to persons for less than how long?
Chapter 2 – Definitions
What NFPA standard dictates the exhaust ventilation requirements in public garages, private garages, repair garages, automotive motor fuel-dispensing facilities and parking garages that contain hydrogen-generating appliances or refueling systems?
703.1
The amount of gas that occupies 1 cubic foot (0.02832 m3) when at a temperature of 60°F (16°C), saturated with water vapor and under a pressure equivalent to that of 30 inches of mercury (101 kPa), is defined as a:
Chapter 2 – Definitions
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 36 inches, and the protection is 0.024-inch sheet metal over 1-inch glass fiber or mineral wool batts with ventilated airspace?
308.2; Table 308.2
Factory-built chimneys installed in dwelling units with solid fuel-burning appliances must comply with the Type HT requirements of which UL standard?
805.2, 37
A Flexible Air Connector is limited in its use, length, and location for transferring air between an air duct or plenum and what other components?
Chapter 2 – Definitions
What is the pipe that connects an approved fuel-fired appliance to a vent?
Chapter 2 – Definitions
Commercial clothes dryers (Type 2) installed in multiple installations require the exhaust fan to operate continuously or be interlocked to operate when what condition occurs?
614.1
Which plastic pipe material is specifically prohibited from use in supplying fuel gas?
403.5
Upon issuance of a stop work order, the cited work shall:
114.2
Stud wall cavities and joist space plenums are prohibited from being utilized for what specific air movement?
602.2.1
For Type II dry cleaning systems, the mechanical ventilation system must be designed to exhaust air at what minimum rate per square foot of floor area?
502.6.1
A completely self-contained heating unit that is designed to supply heated air to spaces remote from or adjacent to the appliance location is a:
Chapter 2 – Definitions
What type of firestop system is required for penetrations of a fire-resistance-rated assembly when using a field-applied grease duct enclosure?
506.3.11.2
Where a duct furnace conveys air to areas outside its space, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
610.2
Provisions in the appendices shall apply only when specifically what?
101.2.1
A venting system designed to remove flue or vent gases by mechanical means, consisting of an induced draft portion or a forced draft portion, is a:
Chapter 2 – Definitions
The termination of concealed condensate piping must be marked to indicate connection to which two types of drains?
307.2
Stop valves are required on refrigeration systems containing more than how many pounds of refrigerant?
1109.6.1
Which of the following pressure vessels are exempt from the scope of Chapter 10?
1001.1 Exceptions
An oxygen-depletion safety system on an unvented room heater shall shut off the gas supply when the oxygen in the surrounding atmosphere is depleted to the percent concentration specified by the manufacturer, but not lower than what minimum percentage?
621.6
According to Table 308.4.2, what is the reduced clearance for a vertical combustible assembly if the required clearance without protection is 18 inches and the protection is 3 1/2-inch brick wall against the combustible wall?
Table 308.4.2
Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used, and where a weld opens during the cutting or threading operation, that portion of the pipe shall not be used.
403.8.1
The code official is authorized to establish a:
108.6
The building or structure must be left in a safe structural condition in accordance with the International Building Code if which part of the structure is altered or replaced during system installation or repair?
302.1
The code official shall issue all necessary notices or orders to ensure:
104.6
The upper edge of a masonry chimney cleanout opening must be located not less than how many inches below the lowest chimney inlet opening?
801.13, 7
Condensate drains from venting systems serving Category II and IV appliances shall be installed in accordance with whose instructions?
503.9
A room heater of the type designed for insertion in or attachment to a wall or partition that discharges all products of combustion through the front into the room being heated is a:
Chapter 2 – Definitions
Ducts required for systems regulated by this code must be designed and installed in accordance with the:
301.13
In multistory common exhaust systems for clothes dryers, the rigid metal ductwork installed within the shaft shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.471 mm), which corresponds to what gauge?
614.11
A wall, floor, ceiling or other assembly constructed of one or more component materials that are not defined as noncombustible is a:
Chapter 2 – Definitions
Which general term includes salamanders, barbecues and other appliances cooking primarily by radiated heat, excepting toasters?
Chapter 2 – Definitions
What is the capacity in cfh for CSST Flow Designation 62 at 30 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(19)
What is the maximum acceptable smoke-developed index for duct coverings and linings, including adhesives?
604.3
The purpose for which a building, or portion thereof, is utilized or occupied is defined as the:
Chapter 2 – Definitions
Ducts used to convey dust, stock, and refuse must be supported at intervals not exceeding what maximum distance?
509.9
What is the primary purpose of a Chimney?
Chapter 2 – Definitions
The design and operation of a hazardous exhaust system must ensure that flammable contaminants are diluted to maintain concentrations in the exhaust flow below what percentage of the contaminant’s lower flammability limit (LFL)?
509.3
Exhaust outlets for grease ducts that terminate above the roof must have the discharge opening located not less than how many inches above the roof surface?
506.3.13.1
In an Absorption Refrigeration System, an Indirect System circulates a brine coil cooled by the refrigerant to the material or space refrigerated, or utilizes it to cool what?
Chapter 2 – Definitions
What is an alternative term sometimes used for Lower Flammable Limit (LFL)?
Chapter 2 – Definitions
A hearth and fire chamber of solid masonry units or reinforced concrete, provided with a suitable chimney, is a:
Chapter 2 – Definitions
What is the maximum capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(2)
A pressure regulator in series with one or more other pressure regulators is a:
Chapter 2 – Definitions
Where all combustion air is provided by a mechanical air supply system, what is the minimum required supply rate per 1,000 Btu/h of total appliance input rating?
304.9
Who shall perform fire tests conducted to demonstrate equivalent fire safety for an alternative material?
104.2.3.5.1
What is the flammability characteristic of a Class 1 refrigerant?
Chapter 2 – Definitions
What is the minimum thickness required for the steel insulation shield installed where factory-built chimneys pass through insulated assemblies?
805.8, 40
Gas piping systems other than CSST must be considered bonded where they are connected to one or more appliances that are connected to which conductor of the circuit supplying the appliance?
310.1
What is the capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, operating at 3.0 psi inlet pressure with a 2.0 psi pressure drop?
402.4; Table 402.4(6)
Ductless mini-split equipment that produces condensate must be provided with an inline check valve located in the drain line or what other device?
307.2.4.1
How must inside tanks that are provided with fill and vent pipes be gauged to indicate when the oil has reached a predetermined safe level?
1306.3
Institutional occupancy is defined as premises from which occupants cannot readily leave without the assistance of others because they are disabled, debilitated, or what other condition?
1103.2
Permanently fixed-in-place outdoor decorative appliances shall be listed in accordance with which ANSI standard?
635.1
Solid-fuel-fired water heaters must comply with which UL standard?
1002.1
All air handled by a nonrecirculating direct-fired industrial air heater, including combustion air, shall be ducted directly from which location?
611.4
A listed and labeled ductless range hood is permitted in Group I-1 and I-2 occupancies where a charcoal filter is provided for what purpose?
505.7 Exception, 505.8 Exception
What is the minimum diameter required for the overflow installed at the top of an open-type expansion tank?
1009.3
Which of the following is considered Solid Fuel for commercial cooking applications?
Chapter 2 – Definitions
Crimp joints for round and oval metal ducts must be lapped not less than what minimum dimension?
603.4.2
What are the maximum input ratings for an individual module of a Modular Boiler for oil fuel?
Chapter 2 – Definitions
What is the minimum clearance required above an appliance where the original required clearance was 6 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Linings must be interrupted at the area of operation of a fire damper and not less than how many inches upstream and downstream of electric-resistance and fuel-burning heaters?
604.8
Packaged oil-fired boilers must be listed and labeled in accordance with which UL standard?
1004.1
Appliances must not be located in a hazardous location unless they are listed and approved for what?
303.2
What type of organization must an Approved Agency be, in addition to being acceptable to the code official?
Chapter 2 – Definitions
According to Table 1009.2, what is the required pressurized diaphragm type expansion tank capacity in gallons for a system volume of 2,000 gallons?
Table 1009.2
What is the maximum difference allowed between the inside cross-sectional dimensions of overlapping sections of grease duct?
506.3.2.1
Flexible air ducts shall not be limited in length, but flexible air connectors shall be limited in length to what maximum dimension?
603.6.1.1, 603.6.2.1
When is cross-connection protection NOT required for potable water supplies to solar systems?
1401.2 Exception, 2
The board of appeals shall hold office at the pleasure of which entity?
112.1
For intake openings in residential occupancies, the minimum opening size in louvers, grilles, and screens must be greater than or equal to what dimension?
Table 401.5
For domestic kitchen cooking appliances with downdraft exhaust systems, PVC pipe and fittings are permitted under a concrete slab poured on grade, provided the underfloor trench is completely backfilled with what?
505.3 Exception 2
An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, is defined as what?
Chapter 2 – Definitions
An established and recognized organization that is regularly engaged in conducting tests, furnishing inspection services or furnishing evaluation or certification, where such organization has been approved by the code official, is a(an):
Chapter 2 – Definitions
A room primarily utilized for the installation of a boiler is defined as what?
Chapter 2 – Definitions
What is the maximum temperature for the metallic mixtures or alloys used in a Soldered Joint?
Chapter 2 – Definitions
A steam heating boiler generates steam that operates at a pressure not exceeding:
Chapter 2 – Definitions
What is the capacity in thousands of Btu/h for 2-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(28)
A manual or automatic device designed to regulate the gas, air, water or electrical supply to, or operation of, a mechanical system is a:
Chapter 2 – Definitions
Chimneys for residential-type or low-heat appliances must extend not less than 3 feet above the highest point where they pass through a roof and not less than what minimum height higher than any portion of a building within a horizontal distance of 10 feet?
503.5.4
An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the state or jurisdiction is a:
Chapter 2 – Definitions
Where an appliance is connected to a chimney flue serving a fireplace, what must be provided below the point of connection to prevent entry of room air into the flue?
801.10.1, 5
Plume discharges from cooling towers, evaporative condensers, and fluid coolers must be located not less than how many feet above or away from any ventilation inlet to a building?
908.3
If subject matter in a referenced standard is within the scope of this code, which provisions shall take precedence?
102.8.2
Documentation of the final decision of the code official regarding modifications shall be kept in the official records and shall be in what format?
104.7.3
Cleanouts in horizontal grease ducts must have opening dimensions of not less than what minimum size?
506.3.9
Cooling towers and evaporative condensers must be equipped with drift eliminators that have a maximum drift rate of what percentage of the circulated water flow rate?
908.8.2
A packaged and completely assembled appliance containing a toilet that incinerates refuse instead of flushing it away with water is a:
Chapter 2 – Definitions
For Type IV and V dry cleaning units, if an exhaust hood is installed immediately outside of and above the loading door, the required airflow rate is calculated by multiplying 100 by what factor?
502.6.2
Domestic clothes dryer installations exhausting more than what volumetric rate must be provided with makeup air?
614.7
A refrigerating system where the evaporator or condenser is in direct contact with the air or other substances to be cooled or heated is defined as what?
Chapter 2 – Definitions
Suspended-type unit heaters are prohibited in corridors, exit access stairways and ramps, exit stairways and ramps, and patient sleeping areas in which two specific occupancy types?
920.4
A device placed in a gas line for reducing, controlling and maintaining the pressure in that portion of the piping system downstream of the device is a:
Chapter 2 – Definitions
When a violation continues each day after due notice has been served, how is that classified?
113.4
What is the maximum height above grade personnel must climb to access equipment or appliances on a roof or elevated structure before an interior or exterior means of access is required?
306.5
Kerosene and oil-fired stoves must comply with NFPA 31 and which UL standard?
922.1
Ducts that operate at temperatures exceeding 120°F (49°C) must have sufficient thermal insulation to limit the exposed surface temperature to what maximum temperature?
604.2
What must be provided where a spill or accidental release of highly toxic liquids can be expected to release highly toxic vapors at normal temperature and pressure?
502.9.6.1
As an alternative to the provisions of Sections 1202 and 1203, hydronic piping shall be designed, installed, inspected, and tested in accordance with which standard?
1201.3
If not notified prior to utility disconnection, how soon thereafter shall the owner, owner’s authorized agent or occupant be notified in writing?
109.3
Hydrogen piping systems shall be marked with the name of the contents and a direction-of-flow arrow at intervals not exceeding what maximum distance?
704.1.2.2
Prior to the approval of a prefabricated construction assembly having concealed work and the issuance of a permit, the code official shall require the submittal of a(an):
111.2.5
Where conflicts occur between the provisions of this code and the referenced standards, which provisions shall apply?
102.8.1
A hand-operated device that provides a means for connecting and disconnecting an appliance or an appliance connector to a gas supply and is equipped with an automatic means to shut off the gas supply when disconnected is a:
Chapter 2 – Definitions
The provisions of this code shall not be deemed to nullify what?
102.1
A record of approvals shall be maintained by the code official and shall be available for public inspection during business hours in accordance with what?
104.7.1
If actual flow rate or pressure drop values in a ground-source loop system test differ from calculated design values by more than what percentage, must the cause be identified and corrective action taken?
1210.1
The aggregate input rating of all unvented appliances installed in a room or space shall not exceed what maximum Btu/h per cubic foot of volume of such room or space?
621.5
The content of the technical opinion and report shall analyze the properties of the design, operation or use of the building to identify and propose:
104.2.2.3
Where demand-controlled ventilation is employed, the minimum quantity of outdoor air shall not fall below that determined from which column of Table 403.3.1.1?
403.3.1.3
Air systems serving a plenum must be ducted directly from the boundary of the fire area served to what equipment?
602.1.2
In a common multistory exhaust system for clothes dryers, rigid metal ductwork must be constructed of sheet steel having what minimum thickness?
504.11
A burner in which gas, air or both are supplied at pressures exceeding, for gas, the line pressure, and for air, atmospheric pressure, with this added pressure being applied at the burner is a(an):
Chapter 2 – Definitions
Grease ducts shall be considered concealed where installed in shafts or covered by coatings or wraps that prevent visual inspection on how many sides?
506.3.2.5
The piping in a solar loop must be insulated in accordance with the requirements of which code?
1402.8.3.1, 15
An application for a permit shall be deemed abandoned how many days after the date of filing, unless pursued in good faith or a permit has been issued?
105.3.1
Appliance and equipment vent terminals must be located such that doors cannot swing within what minimum horizontal distance of the terminal?
502.7.1
What is the capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(5)
When calculating minimum capacity for a single appliance installed at high altitude, which input rating shall be used?
504.2.5
If a notice of violation is not complied with promptly, the code official shall request legal counsel to institute appropriate proceedings at law or in equity to perform what action?
114.3
Tests conducted to demonstrate equivalency in support of an alternative design application must be of a scale that is sufficient to predict the performance of the:
104.2.3.5
A cleanout must be provided on both the inlet and outlet sides of an in-line fan and located within what distance of the fan duct connections?
506.3.8.2
In areas designated as Zone AO where a depth number is not specified on the flood hazard map, the design flood elevation depth number shall be taken as being equal to:
Chapter 2 – Definitions
Plenum enclosure construction materials exposed to the airflow must have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with which standard?
602.2
Where corrosive materials exceeding the maximum allowable quantity are dispensed or used, what specific type of exhaust ventilation must be provided?
502.9.2
Cleanout openings in grease ducts are required to be spaced not more than how many feet from changes in direction greater than 45 degrees (0.79 rad)?
506.3.8
How long shall the code official retain one set of approved construction documents after the date of completion of the permitted work?
106.2
A metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare is defined as what?
Chapter 2 – Definitions
The abbreviation for British thermal unit is:
Chapter 2 – Definitions
For a Main entry lobby in an office occupancy, what is the required Area Outdoor Airflow Rate in the Breathing Zone in CFM/ft squared?
Table 403.3.1.1
Where must high-pressure-steam safety valves be vented?
1006.6
A vent connector installed without dips or sags must slope upward toward the vent or chimney not less than what minimum distance per foot?
503.10.8
Solar thermal systems must be listed and labeled in accordance with which standard?
1401.4, 4
What is a device or apparatus that is manufactured and designed to utilize energy and for which this code provides specific requirements?
Chapter 2 – Definitions
Approved plastic pipe or tubing for heating panels embedded in concrete must be rated at 100 psi (689 kPa) at what specific temperature?
1209.1
Which joint type is explicitly excluded from the first definition of a Mechanical Joint?
Chapter 2 – Definitions
What primary contaminants does a Type II Hood collect and remove?
Chapter 2 – Definitions
Pipe and duct insulation contained within plenums shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C411 at what minimum temperature?
602.3.9
Which component is generally NOT included in an air distribution system?
Chapter 2 – Definitions
System components that might be subjected to a vacuum during operation or shutdown must either be designed to withstand such vacuum or be protected with what?
1402.3.2, 6
A device for controlling and maintaining a uniform supply pressure, either pounds-to-inches water column (MP regulator) or inches-to-inches water column (appliance regulator), is a:
Chapter 2 – Definitions
Which repair garage is exempt from the requirement for a source capture system for motor vehicle operation?
502.14 Exception 2
Permits for temporary uses, equipment, and systems shall be limited as to time of service but shall not be permitted for more than how many days?
110.1
What type of hood must be installed over extra-heavy-duty cooking appliances?
507.2.2
Fasteners used to join domestic dryer exhaust ducts are prohibited from protruding more than what maximum distance into the inside of the duct?
614.9.2
Where equipment is located on a roof such that personnel must climb higher than 16 feet (4877 mm) above grade to access it, what type of access must be provided?
306.5
For underfloor spaces containing appliances, the unobstructed passageway from the access opening to the appliance shall be not more than what maximum length?
306.4
Which type of vent is listed and labeled for use with listed Category II, III and IV appliances?
Chapter 2 – Definitions
After prescribed tests and inspections indicate the work complies, who shall issue a notice of approval?
107.1
Taking return air from an indoor swimming pool enclosure is not prohibited if what condition is met?
601.5 Exception 1
What is the minimum clearance required to combustibles for hazardous exhaust ducts conveying exhaust gases with temperatures between 100°F and 600°F?
Table 509.8.2
Mechanically ventilated shafts using a refrigerant detector must activate the ventilation at a maximum refrigerant concentration of what percentage of the lower flammable limit (LFL) of the refrigerant?
1109.3.2
Return air taken from a closet smaller than 30 square feet (2.8 m2) shall require the closet door to be undercut not less than what dimension?
601.5
Heating and cooling system design loads must be determined in accordance with the procedures described in which standard?
312.1
Section 308 governs the reduction in required clearances to combustible materials and assemblies for vents, kitchen exhaust equipment, mechanical appliances, and what other component?
308.1
During what time period shall ventilation be provided for a room or space?
401.3
A draft hood must be located so its relief opening is not less than what minimum distance from any surface except that of the appliance it serves and the venting system?
503.12.7
When utilizing a combustible gas detector to monitor purging, when shall purging be stopped?
406.7.2.1
What is the Refrigerant Safety Group Classification for R-410A (R-32/125, 50.0/50.0)?
Table 1103.1
When shall a notice of approval be issued by the code official?
107.1
When does a permit become valid?
108.1
What is the maximum pressure for steam furnished by a Low-Pressure Steam-Heating Boiler?
Chapter 2 – Definitions
Group A2 and B2 refrigerants shall not be used in which type of refrigeration system?
1104.3.2
What is the maximum capacity in cubic feet per hour (cfh) for 1-inch nominal Schedule 40 metallic pipe at 150 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
For exterior masonry chimneys serving two or more Category I appliances (FAN+NAT) with Type B double-wall connectors, if the vent height is 30 feet and the internal area is 113 square inches, what is the maximum combined input rating in thousands of Btu per hour?
504.3; Table 504.3(7a)
For detached one- and two-family dwellings not more than three stories above grade plane, compliance shall be with the code or which other regulatory document?
101.2 Exception
An exception permits fuel-burning appliances in a machinery room if the combustion air is ducted from outside and sealed, or if what device is employed to automatically shut off the combustion process?
1105.5 Exception 2
Local exhaust to capture leakage from indoor portable tanks containing highly toxic or toxic compressed gases must be located where?
502.9.8.2
What is the maximum air temperature permitted within nonmetallic ducts?
603.5
What is the primary function of a Commercial Cooking Recirculating System?
Chapter 2 – Definitions
What is the minimum height required for the lettering of the identification label on refrigerant piping?
1109.2.7
What must be installed on drain and fill valves in the solar loop?
1402.8.6.2, 18
An automatically operated assembly of integrated systems for generating electrical energy and recoverable thermal energy that is permanently connected and fixed in place is a:
Chapter 2 – Definitions
Exemption from the permit requirements of this code shall not be deemed to grant authorization for work to be done in violation of what?
105.2
What is the closed cup flash point range for Class II Combustible Liquids?
Chapter 2 – Definitions
Rooms containing appliances must be provided with a door and an unobstructed passageway measuring not less than what width and height?
306.2
Automatic dampers shall be listed and labeled in accordance with which UL standard for oil-fired heating appliances?
803.6, 21
Solvent cement conforming to ASTM F493 shall be applied to all joint surfaces for which plastic pipe material?
1203.3.4
What is the minimum vertical height required for vents to terminate above the highest connected appliance flue collar?
802.6, 17
Rough-in inspection shall be made after the roof, framing, fireblocking, and bracing are in place and all ducting and other components to be concealed are complete, and prior to the installation of what?
111.2
The instrument installed to measure the volume of gas delivered through it is the:
Chapter 2 – Definitions
Who must obtain the required permit before beginning work regulated by this code?
105.1
A thermostat in which the motion of the valve is approximately in direct proportion to the effective motion of the thermal element induced by the temperature change is a:
Chapter 2 – Definitions
Where conflicts occur between provisions of this code and the referenced standards, which provisions shall apply?
102.8.1
The use of toxic fluids in solar thermal systems must comply with Chapter 60 of the International Fire Code and which federal act?
1403.4, 21
For a Type B double-wall vent serving two or more Category I appliances with Type B double-wall connectors (Table 504.3(1)), if the vent height (H) is 15 feet and the connector rise (R) is 6 feet (the max rise for R=6 ft row), what is the maximum combined input rating (NAT+NAT) for a 9-inch common vent diameter?
504.3; Table 504.3(1)
Where heat or radiant energy sensors are used in hood systems consisting of multiple hoods served by a single exhaust system, where must the sensors be provided?
507.1.1.1
If an attic passageway is unobstructed and not less than 6 feet (1829 mm) high and 22 inches (559 mm) wide, what is the maximum length allowed?
306.3 Exception
Which components are exempt from the requirement for locking access port caps if installed in controlled areas such as roofs with locked access hatches or doors?
1101.9 Exception
After a pressure test, minor repairs and additions shall not be required to be pressure tested provided the connections are tested with a noncorrosive leak-detecting fluid or what other method?
406.1.2
Safety and relief valve discharge piping shall discharge through what device located in the same room as the appliance?
1006.6
The procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements is defined as:
Chapter 2 – Definitions
What must be excluded from use when calculating required clearances to combustibles?
304.9
Interpretations, policies, and procedures adopted by the code official must comply with the intent and purpose of this code and must not have the effect of doing what?
104.2
Condensate drain lines must be configured to permit the clearing of blockages and performance of maintenance without requiring what action?
307.2.5
A water spray test performed on a grease duct system must use a water pump capable of a flowing outlet pressure of not less than how many PSI?
506.3.2.5.2
When calculating reduced clearances using Table 308.4.2, reduced clearances shall not be derived by what process below the range of the table?
308.4.2
Condensate pumps located in uninhabitable spaces shall be connected to the appliance served such that when the pump fails, the appliance or equipment will be prevented from:
307.7
When split-style piping insulation is used in a solar loop, what must be sealed?
1402.8.3.1, 15
A through-the-wall direct-vent terminal serves an appliance rated at 10,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
In machinery rooms using Group A2L and B2L refrigerants, open flame-producing devices or continuously operating hot surfaces shall not exceed what maximum temperature?
1106.4.1
The code official shall designate the evaluation service of an approved agency as the evaluation agency and review the agency’s evaluation report for adequacy and:
111.2.5.1
In an Induced Draft system, the fan, blower, or ejector is located where?
Chapter 2 – Definitions
Shield plates used to protect clothes dryer exhaust ducts from penetration damage must be of steel material having a minimum thickness of what gauge?
504.8.1
In an Indirect Evaporative Cooling system, how is heat removed from a primary air stream?
Chapter 2 – Definitions
Factory-built chimneys for appliances that operate at a positive vent pressure must be listed for such application in accordance with which UL standard?
503.5.1
In Group I-2, Condition 2 occupancies, gas fireplace appliances and decorative gas appliances are prohibited except where they are direct-vent appliances installed in:
303.3.1
What is the maximum water volume allowed for a compressed gas container or cylinder that is exempt from the requirement to be used in an upright position?
704.2
What is the minimum thickness required for the concrete encasement of an underground grease duct system?
506.3.10
What is the minimum required pipe size for a condensate waste and drain line?
307.2.2
Safety and safety relief valves must be set at not greater than what value of the boiler or pressure vessel?
1006.4
Posts 3 feet (914 mm) or less in height supporting illuminating appliances shall not be smaller than what minimum size Schedule 40 steel pipe?
628.3
If a clothes dryer is installed in a residential bathroom, what is the minimum required area for the permanent opening communicating with a space outside of a sleeping room, bathroom, toilet room or storage closet?
303.3
The inside lower edge of canopy-type Type I and II commercial hoods must overhang or extend a horizontal distance of not less than how many inches beyond the edge of the top horizontal surface of the appliance on all open sides?
507.1.6.1
A nontoxic, gaseous hydrogen system mixture must contain at least what minimum percentage of hydrogen gas by volume?
702.1
Duct cleanouts must be located at the base of each vertical duct riser and at intervals not exceeding how many feet in horizontal sections of duct conveying combustible dust?
509.7.1
Dampers equipped with fusible links, internal operators, or both must be provided with an access door that is not less than how many inches square?
607.4.1
Where is Return Air removed from?
Chapter 2 – Definitions
What is the maximum temperature of the products of combustion at the point of entrance to the flue for a Low-heat appliance (residential appliance) under normal operating conditions?
Chapter 2 – Definitions
Members of the board of appeals must be qualified by experience and training on matters pertaining to the provisions of this code and must not be:
112.3
Oil-fired vented wall furnaces must be tested in accordance with which UL standard?
909.1
The pressure difference that causes a continuous flow of air and products of combustion through the gas passages of the appliance to the atmosphere is defined as what?
Chapter 2 – Definitions
Copper tubing joints that are embedded in a portion of the building (like concrete or plaster) must be joined by which method?
1209.3.2
Threaded and flanged connections in hydrogen service piping are prohibited except in which two locations?
704.1.2.4
In industrial refrigerating systems, if the quantity of any Group A2, B2, A3, or B3 refrigerant in a single independent circuit would exceed 25 percent of the LFL upon release, electrical equipment must conform to what hazardous location classification requirements of NFPA 70?
1104.2.2
What is the maximum capacity in cfh for 3/8-inch ACR semirigid copper tubing at 100 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(8)
Refrigerants with different refrigerant designations may only be mixed if the resulting mixture does not change what characteristic?
1102.2.1
When combining indoor spaces on the same story for combustion air, one permanent opening shall commence within 12 inches of the top of the enclosure, and where must the other permanent opening commence?
304.5.3.1
A Peer Review must be conducted by whom?
Chapter 2 – Definitions
For an Animal exam room (veterinary office), what is the estimated maximum occupant load rate per 1,000 square feet?
Table 403.3.1.1
Air filters must be installed such that all return air, outdoor air, and makeup air is filtered upstream from what two components?
605.1
The treatment of air so as to control simultaneously the temperature, humidity, cleanness and distribution of the air to meet the requirements of a conditioned space is defined as:
Chapter 2 – Definitions
Air conveyed within energy recovery systems shall not be considered as recirculated air if the system is constructed to limit cross-leakage between air streams to less than what percentage of the total airflow design capacity?
513.4
What is the capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 500 feet in length, operating at 3.0 psi inlet pressure with a 2.0 psi pressure drop?
402.4; Table 402.4(6)
Which valve standard is approved for general valve applications up to 125 psig pressure?
409.1.1; Table 409.1.1
What is the minimum clearance required above an appliance where the original required clearance was 12 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
Ventilation in dry cleaning plants must be adequate to protect employees and the public in accordance with this section and which other referenced standard, where applicable?
502.6
For an appliance installed in a dwelling unit closet, the level service space required at the service side must be not less than 30 inches (762 mm) deep and what minimum height?
306.2 Exception
For existing buildings located in flood hazard areas undergoing reconstruction or repair, the code official shall determine if the proposed work constitutes substantial improvement or what?
104.3.1
Which of the following is considered a Heavy-Duty Cooking Appliance?
Chapter 2 – Definitions
For existing buildings identified as historic, the provisions of this code are not mandatory provided the buildings are judged to be safe and in the public interest by the:
102.6
What is the maximum operating pressure allowed by these regulations for natural gas piping systems?
101.2.3
Type L vents must terminate not less than how many feet higher than any portion of a building within 10 feet (3048 mm)?
802.5, 17
Condensate from cooling coils shall be conveyed to an approved place of disposal and shall not discharge into a street, alley, or other areas so as to cause what?
307.2.1
When conveying particulate matter, hazardous exhaust systems must be designed employing which method?
509.5
For a structure with a previously issued lawful permit, construction must have been pursued in good faith within how many days after the effective date of this code to avoid requiring changes?
105.4.6
For a Nail salon, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than how many CFM per station?
Table 403.3.1.1 Note h
Brazing alloys used in hydrogen service piping must have a melting point greater than what minimum temperature?
704.1.2.4.1
What is the maximum water temperature allowed for a hot water supply boiler at or near the boiler outlet?
Chapter 2 – Definitions
Where two or more appliances are connected to a vertical vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material.
503.10.4
Devices or safeguards required by this code shall be maintained in compliance with which edition of the code?
102.3
Machinery rooms must be mechanically ventilated to what location?
1105.6
For gas engine-powered equipment and turbines, what connection method is prohibited to the gas supply piping to protect against the effects of normal vibration?
616.2
Vent connectors for medium-heat appliances are prohibited from passing through walls or partitions constructed of what type of material?
503.10.15
Materials, equipment, and devices approved by the code official must be constructed and installed in accordance with:
104.9
Where work does not pass an initial test or inspection, after necessary corrections are made, the work shall be resubmitted to the code official for:
111.3.3
In addition to keeping concentrations below 25 percent of the LFL, what is the minimum required average air velocity through all openings for an open face or open front spray booth?
502.7.3.3.1
Flue lining systems for use with residential-type and low-heat appliances must resist flue gases and condensate at temperatures up to what maximum temperature?
501.12
Where combustion air openings are provided with volume, smoke, or fire dampers, the dampers must be interlocked with what component of the appliance?
701.2
What is the exact amount of air required to supply oxygen for complete combustion of a given quantity of a specific fuel?
Chapter 2 – Definitions
What is the minimum density required for mineral wool batts (blanket or board) when used as part of a clearance reduction system?
308.2
What is the maximum pressure for a low-pressure boiler supplying hot water?
Chapter 2 – Definitions
Factory-built chimneys for medium-heat appliances producing flue gases having a temperature above 1,000°F must be listed and labeled in accordance with which UL standard?
506.3
Where different portions of this code specify different materials or methods of construction for a specific case, which requirement shall govern?
102.1
Ducts discharging combustible material directly into any combustion chamber shall conform to the requirements of which standard?
601.1 Exception
Under what concentration of the lower flammable limit (LFL) is air exhausted from spraying operations permitted to be recirculated as makeup air for unmanned spray operations?
502.7.3.2 Exception 1
In a multistory common exhaust system, the finished cleanout opening located at the base of the shaft must be not less than what minimum size?
614.11
When soldering on the metal portion of a PEX plastic tubing system, the solder joints shall be performed not less than what minimum distance from a plastic-to-metal adapter in the same water line?
1203.9.2
What air component, required by Section 403.3, shall not be recirculated?
403.2.1
What must failure of the exhaust ventilation system cause in a repair garage for lighter-than-air fuels?
502.16.2.1
Pressure relief devices shall be arranged to discharge to the outdoors, except for DOTn-specified containers with an internal volume not exceeding what maximum amount?
703.3.8 (Exception)
What must oil-fired appliances be equipped with to stop burner operation if the venting system is obstructed?
801.21, 15
A venting system designed to remove flue or vent gases under nonpositive static vent pressure entirely by natural draft is a:
Chapter 2 – Definitions
Compartments housing equipment used in aircraft fueling and defueling operations shall be adequately ventilated at floor level or within what other location?
502.2
Appliance connections to a chimney or vent equipped with a power exhauster must be made on which side of the exhauster?
801.14, 8
To consider the volumes of spaces in different stories as communicating spaces for combustion air, what is the total minimum free area required for connecting openings in doors or floors, based on total appliance input rating?
304.5.3.2
Upon issuance of a stop work order, how shall the cited work proceed?
115.2
The code official shall take action without delay in accordance with the decision of the:
112.4
For natural gas calculations using the equation factors listed, what is the value designated as Y?
402.4; Table 402.4
Equipment used in residential occupancies is excepted from the human comfort refrigerant restriction if it contains a maximum of how many pounds of refrigerant?
1104.3.1 Exception 1
Mechanical exhaust systems, where required in other than Group R-3 occupancies and dwelling units in Group R-2, must maintain the space with what pressure characteristic?
501.4
The equipment in Section 1106.5.1 must be automatically shut off whenever the refrigerant vapor concentration in the machinery room exceeds the vapor detector’s upper detection limit or what maximum percentage of the LEL, whichever is lower?
1106.5.1
Where leakage or other defects are located during testing, what must be done to the affected portion of the piping system?
406.5.2
The ventilation system for gas rooms, exhausted enclosures, and gas cabinets must be designed to operate at what pressure relative to the surrounding area?
502.8.2
When equipment and ductwork for exit enclosure ventilation are located within the exit enclosure, where must the intake air be taken from?
601.3
Where vents penetrate outside walls, the annular spaces around such penetrations must be permanently sealed using approved materials to prevent entry of combustion products into the building.
503.16
Soldered joints are limited to refrigeration systems using Group A1 refrigerant and having a pressure of less than or equal to what maximum pressure?
1108.3.3
What is the minimum thickness required for a galvanized steel chimney connector larger than 16 inches in diameter serving a low-heat appliance, according to Table 803.9(1)?
Table 803.9(1), 23
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a residential boiler with a listed gas conversion burner and a draft hood?
503.10.5; Table 503.10.5
For all environmental air exhaust, what is the minimum termination distance from mechanical air intakes?
501.3.1
High-density polyethylene (HDPE) pipe fittings for ground-source loops must conform to which standards, including ASTM D2683 and ASTM D3261?
Table 1210.5
Multiple spray booths are allowed to have a common exhaust system if their combined frontal area is what maximum size, provided identical spray-finishing material is used?
502.7.3.5 Exception 1
For pneumatic leak tests of gaseous hydrogen systems where the maximum working pressure is less than 125 psig (862 kPa gauge), what is the minimum required test pressure?
705.3.2
Outdoor air intake openings located within 10 feet (3048 mm) of a contaminant source must be located not less than how many feet below the contaminant source?
401.4
Exhaust hood systems for domestic cooking capable of exhausting in excess of how many CFM must be provided with makeup air?
505.4
Which type of refrigeration system is defined as having a high probability that leaked refrigerant could enter an occupied area?
1103.3.2
In System A for combustible wall pass-through, what is the required clearance to combustibles?
Table 803.10.4, 27
The board of appeals shall render all decisions and findings in writing to the appellant with a duplicate copy provided to the:
112.1
Except for engineered systems, what is the minimum area required for a chimney or vent serving a single appliance?
801.6
Mechanical ventilation systems must be provided with manual or automatic controls that will operate such systems whenever the spaces are in what state?
405.1
What causes the formation of Condensate?
Chapter 2 – Definitions
If appliances are served by a mechanical air supply system, what must be provided to prevent main burner operation when the mechanical air supply system is not operating?
304.9.2
The board of appeals shall not have the authority to perform what action regarding the requirements of this code?
112.2
Oil-fired appliances shall be vented in accordance with this code and which specific standard?
801.2.1
Where factory-built chimneys pass through attic space, how high above the insulation materials must the insulation shield terminate?
805.8, 40
Appliances shall not be converted to utilize a different fuel gas unless complete instructions for such conversion are provided by which source?
301.7.1
What is the primary integral feature of Compensating Hoods?
Chapter 2 – Definitions
Exit and exit access doorways in machinery rooms must swing in the direction of egress travel and be equipped with what, regardless of the occupant load served?
1105.9
The concentration of airborne contaminants that poses a threat of death or immediate/delayed permanent adverse health effects is known as what?
Chapter 2 – Definitions
Hydrogen Generating Appliances utilize which of the following processes to generate gaseous hydrogen?
Chapter 2 – Definitions
Any person who begins work on a mechanical system before obtaining necessary permits shall be subject to what fee, in addition to the required permit fees?
108.4
Appliances regulated by this code must be listed and labeled for their application unless approved in accordance with which section?
301.7
What type of system converts solar radiation to thermal energy for use in heating or cooling?
Chapter 2 – Definitions
Standard air is defined as air at a temperature of 70°F (21°C) and what pressure?
Chapter 2 – Definitions
A vent cap must be installed on vertical terminations of mechanical draft systems for what purpose?
804.3.5, 34
When testing at a pressure greater than 10 psig (68.98 kPa gauge) but less than or equal to 100 psig (689.5 kPa gauge), the testing gauge must have increments of what maximum amount?
705.3.6
Which process is typically used at a field job site or local service shop to reduce contaminants for Recycled Refrigerants?
Chapter 2 – Definitions
If one or more temperature or radiant energy sensors are used to activate a Type I hood exhaust fan, the fan must activate not more than how many minutes after the first appliance served by that hood has been turned on?
507.1.1
For multiple-appliance common venting systems, where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced, and the horizontal length of the offset shall not exceed 1 1/2 feet for each inch of which component diameter?
504.3.5
For natural gas systems, where is a system shutoff valve considered to be if it is provided after the outlet of the service meter assembly?
Chapter 2 – Definitions
In the Zone Outdoor Airflow rate calculation (Equation 4-2), the Breathing Zone Outdoor Airflow is divided by what value?
403.3.1.1.1.3
The allowable clearance reduction for protective assemblies can be based on a labeled protective assembly that is listed and labeled in accordance with which standard?
308.4.1
Appliances located in private garages and carports shall be installed with a minimum clearance of how many feet above the floor?
304.7
If work authorized by a permit is suspended or abandoned for a period of 180 days, the permit shall:
105.5.3
Any combination of outdoor and transfer air intended to replace exhaust air and exfiltration is defined as:
Chapter 2 – Definitions
One set of approved construction documents shall be retained by the code official for a period of not less than how many days from the date of completion of the permitted work?
106.2
Clearance is measured as the minimum distance through air between the heat-producing surface of a mechanical appliance and what other surface?
Chapter 2 – Definitions
If the depth of an appliance pit exceeds 12 inches (305 mm) below adjoining grade, the walls of the pit or excavation must be lined with what material?
303.7
Where vents pass through attic space, how high above the insulation materials must the insulation shield terminate?
802.8, 18
The standby power source and its transfer switches for a smoke control system must be enclosed with fire barriers or horizontal assemblies having what minimum fire-resistance rating?
512.11.1
Joints between different piping materials shall be made with what type of fitting?
1203.1.1
Dry Cleaning Systems classified as Type III use Class III combustible liquid solvents having a flash point at or above 140°F (60°C) and below what maximum temperature?
Chapter 2 – Definitions
A tee fitting used for pressure measurement or as a sediment trap must be installed not less than 10 pipe diameters downstream of the MP regulator, unless which alternative condition is met?
410.2
What minimum unobstructed width is required for passageways around all sides of boilers, unless otherwise approved?
1004.3
Ventilation Air is that portion of supply air that comes from the outside (outdoors), plus any recirculated air that has been treated to maintain what?
Chapter 2 – Definitions
Factory-built solar thermal collectors must bear a label showing the manufacturer’s name and what two other pieces of information?
1404.1, 21
The code official shall designate the evaluation service of an approved agency to review the evaluation report for adequacy and conformance to this code. What is this designated agency known as?
111.2.5.1
What is the purpose of providing Excess Air for the combustion of a fuel?
Chapter 2 – Definitions
Appliances installed in pits or excavations shall be installed not less than how many inches above the pit floor?
303.7
What must be provided for the control circuit of a boiler that is capable of being locked in the off position?
1006.8
Plenums shall be limited to uninhabited crawl spaces, above a ceiling or below the floor, attic spaces, mechanical equipment rooms, and what other construction features?
602.1.1
An operation performed on a gas piping system to verify that the system does not leak is a:
Chapter 2 – Definitions
Equipment and appliances used to exhaust explosive or flammable vapors, fumes, or dusts must bear an identification plate stating what information?
503.3
A metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare is a:
Chapter 2 – Definitions
For strength testing of refrigeration piping systems, the piping shall be pressurized for a minimum of how many minutes?
1110.6
What is the minimum melting point required for solder used in sweat fittings if they were permitted in fuel oil lines (though such joints are prohibited)?
1303.1
In indoor locations intended for hydrogen-generating or refueling operations using natural ventilation, what is the maximum floor area permitted?
304.5.1
Outlets for exhaust that exceed 600°F (315°C) shall be designed as what feature in accordance with Table 510.2?
510.2
Screens used for combustion air openings shall have a mesh size not smaller than what dimension?
304.1
Single-wall metal pipe must extend not less than 2 feet above the highest point where it passes through a roof and not less than what minimum height higher than any portion of a building within a horizontal distance of 10 feet?
503.7.3
Fire dampers are not required at penetrations of shafts where steel exhaust subducts extend vertically not less than how many inches in exhaust shafts?
607.5.5 Exception 1
Which vented appliance category operates with a nonpositive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent?
Chapter 2 – Definitions
For liquid single-phase solar energy systems, the expansion tanks must be sized in accordance with Section 1009, with an additional expansion tank acceptance volume equal to the total volume of liquid contained in what two components?
1402.8.7, 19
What is the minimum distance required between an air intake opening and a lot line or building on the same lot?
401.4
The imposition of violation penalties shall not preclude the legal officer of the jurisdiction from instituting appropriate action to prevent what?
114.5
Metallic ducts installed underground and not having an approved protective coating must be completely encased in not less than how many inches of concrete?
603.8
For a single appliance vented by a masonry chimney using a Type B double-wall connector (Table 504.2(3)), if the height (H) is 15 feet and the lateral (L) is 15 feet, what is the minimum input rating (FAN Min) for a 9-inch diameter connector?
504.2; Table 504.2(3)
Elements of the smoke management system relying on volatile memories must be supplied with uninterruptible power sources of sufficient duration to span how long of a primary power interruption?
512.11.2
Direct-fired industrial air heaters shall incorporate a means to supply outside ventilation air to the space at a rate of not less than 4 cubic feet per minute per what unit of rated input of the heater?
612.5
An appliance regulated by this code that was legally installed prior to the effective date of the code is classified as what?
Chapter 2 – Definitions
In which residential occupancy is the use of corridors for conveying return air permitted?
601.2 Exception
What is an assembly consisting of a hearth and fire chamber of noncombustible material, provided with a chimney, for use with solid fuels?
Chapter 2 – Definitions
The installation of conversion burners must conform to which standard?
919.1
Where appliances are located on more than one floor and served by a common vent, the total available height (H) for each segment shall be measured from the highest draft hood outlet or flue collar entering that segment to which location?
504.3.13
If the code official finds the proposed work conforms to requirements and fees have been paid, what action shall be taken?
105.4
The fee for a permit, where required, shall be paid in accordance with the schedule established by whom?
108.2
Which duty is authorized and directed for the code official regarding permits?
104.3
Where a closet is designed for a clothes dryer installation, the required makeup air opening in the closet enclosure must have an area of not less than what minimum size?
614.7.1
In a Wall Canopy Hood, what component acts as a back panel, forcing the makeup air across the front of the cooking equipment?
Chapter 2 – Definitions
Evaluation reports used to support alternative material approvals shall be issued by which entity?
104.2.3.6.1
What is the minimum size required for the bonding jumper used for CSST piping systems?
310.2.2
Louvers that protect air intake openings in structures located in hurricane-prone regions, as defined in the International Building Code, shall comply with which standard?
401.5
Air necessary for complete combustion of a fuel, including theoretical air and excess air, is defined as:
Chapter 2 – Definitions
A yellow insulated copper tracer wire or other approved conductor must be installed adjacent to underground nonmetallic piping. The minimum tracer wire size shall be not less than:
404.17.3
What is the maximum capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 750 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(2)
Air transferred from occupiable spaces is permitted to serve as makeup air for required exhaust systems in spaces such as kitchens, baths, toilet rooms, elevators, and which other space?
403.2.2
Which entity determines if something is “Approved” for the purposes of this code?
Chapter 2 – Definitions
If the code official determines that the valuation provided by the applicant is underestimated, what action may be taken?
108.3
A required technical opinion and report shall be prepared by a party acceptable to the code official, such as a qualified engineer, specialist, laboratory, or what other type of organization?
104.2.2.2
The term that refers to a blower or fan used for the purpose of distributing supply air to a room, space, or area is what?
Chapter 2 – Definitions
What is the capacity in cfh for 3-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(7)
The Uncorrected Outdoor Air Intake flow rate for a multiple zone recirculating system is determined using Equation 4-6, which includes the Occupant diversity, defined by what ratio?
403.3.1.1.2.3.3
Who is authorized to approve an alternative material, design, or method of construction?
104.2.3.1
When using Type B double-wall gas vent connected directly to a single Category I appliance, if the vent height (H) is 10 feet and the vent diameter (D) is 6 inches, what is the maximum input rating (FAN Max) for a Fan-Assisted Combustion System?
504.2; Table 504.2(1)
What machine is defined as a specific machine, with or without accessories, for compressing a gas?
Chapter 2 – Definitions
Thermal Resistance (R) is defined as the reciprocal of what measure?
Chapter 2 – Definitions
Certification obtained by the manufacturer indicating that the function and performance characteristics of a product have been determined by testing and ongoing surveillance by an approved third-party certification agency is defined as:
Chapter 2 – Definitions
Where the fuel supply line is taken from the top of a tank that is above the level of the burner inlet connection, what must be installed in lieu of the shutoff valve?
1301.4
The register of a floor furnace with a horizontal warm-air outlet shall not be placed closer than what minimum distance to the nearest wall?
609.2
If a grease duct is large enough for personnel entry, what are the minimum dimensions required for the approved opening in horizontal sections?
506.3.8.1
Individual radiant tubing circuit lengths shall be installed with a variance of not more than what percentage from the design length?
1209.6
Using the Standard Method (304.5.1), what is the minimum required volume of indoor air per 1,000 Btu/h of the appliance input rating?
304.5.1
Which systems are not required to comply with Chapter 11?
1101.1.2
A listed shutoff valve shall be installed immediately ahead of which device?
409.4
Pipe insulation installed in buildings must have a maximum smoke-developed index not exceeding what value?
1204.1
Where used in this code, the term ” piping ” refers to:
Chapter 2 – Definitions
When interpreting this code, words used in the masculine gender shall be construed to include which other gender(s)?
201.2
Where hazardous materials capable of emitting hazardous vapors are stored, contaminated exhaust air shall not be recirculated to occupied areas unless what condition is met?
502.8.1.1
When shall the rough-in inspection be made?
111.2
For exhaust openings that terminate outdoors, the openings in screens, louvers, and grilles must be sized not larger than what maximum dimension?
501.3.2
The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used for what purpose?
801.17, 10
Which material is explicitly prohibited from being reused in ground-source heat pump loop systems?
1210.2
If non-stainless steel or non-black steel piping is installed through wood studs less than 1 1/2 inches (38 mm) from the nearest edge, what minimum thickness must the required steel shield plates have?
704.1.2.3.5
What is the minimum open area required for the passageway of dryer exhaust duct terminals?
504.4.2
Cleanout openings in grease ducts are required to be spaced not more than how many feet apart for sections that are inaccessible from the hood or discharge openings?
506.3.8
What is the minimum openable area to the outdoors required for natural ventilation of an occupied space?
402.2
Listed self-contained systems using Group A3 refrigerant are exempt from restrictions if they contain a maximum of how many pounds?
1104.3.2 Exception 2
What type of clearance must chimneys and vents have to combustibles, according to the International Building Code and manufacturer’s instructions?
801.18.4, 13
Approved construction documents shall not be changed, modified, or altered without authorization from whom?
105.4.1
Any heating appliance or equipment that heats potable water and supplies such water to the potable hot water distribution system is a:
Chapter 2 – Definitions
What is the minimum separation distance required for the atmospheric venting of CNG from CNG dispensers?
413.10.2.3; Table 413.10.2.3
In an absorption system, what process is used to pressurize the refrigerant?
Chapter 2 – Definitions
In mechanically ventilated hydrogen-generating locations, equipment and appliances having an ignition source shall be located such that the source of ignition is where relative to the mechanical ventilation outlet(s)?
304.5.2
Hazardous exhaust systems that penetrate a floor/ceiling assembly must be enclosed in what structure?
509.6.2
When an automatically operated fuel-burning appliance is in operation, an Automatic Vent Damper Device is designed to perform what action?
Chapter 2 – Definitions
The liquid that condenses from a gas (including flue gas) caused by a reduction in temperature or increase in pressure is defined as:
Chapter 2 – Definitions
Joints, seams, and penetrations of grease ducts must be made with a continuous liquid-tight weld or braze made on which surface of the grease duct system?
506.3.2
The cutting and notching of holes in cold-formed steel structural framing members shall be in accordance with which standard?
302.5
A Volume Damper is a device that restricts, retards, or directs the flow of air in a duct or what other products?
Chapter 2 – Definitions
Where a smoke damper is installed within a duct, the smoke detector or sampling tubes must be located within what maximum distance of the damper?
607.3.3.2
Duct furnaces shall be listed in accordance with which ANSI/CSA or UL standard?
610.1
The issuance of a permit based on construction documents shall not prevent the code official from thereafter requiring the correction of what?
105.4.2
If ready access is not provided to mechanical systems in prefabricated assemblies, who shall conduct in-plant inspections as frequently as necessary?
111.2.5.2
Exposed refrigerant piping installed in open spaces that afford passage shall be not less than what minimum height above the finished floor?
1109.2.1
Where a vent connector for a Category I appliance with a draft hood passes through an unconditioned space (like an attic) in an area with a 99-percent winter design temperature of 5°F or higher, which type of pipe is permitted to be used within the exterior walls?
503.10.2.2 (Exception)
Who is responsible for the maintenance of mechanical systems?
102.3
Materials, equipment, and devices approved by the code official shall be constructed and installed in accordance with what?
104.9
An approved agency that tests mechanical equipment and appliances must maintain a record of all tests performed to verify compliance with what?
301.8.1
When a multistory common vent system includes an offset that does not exceed 45 degrees, the common vent capacity listed in the tables must be reduced by what percentage for the segment containing the offset?
504.3.16
Appliances must be supported and connected to the piping so as not to exert undue strain on which components?
305.12
Suspended-type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches at the sides, 12 inches at the bottom, and what minimum distance above the top if the unit heater has an internal draft hood?
620.4
If the air infiltration rate of a structure is known to be less than 0.40 ACH, which method must be used to determine the required volume of indoor air for combustion?
304.5
Open-type expansion tanks shall be located not less than how many feet above the highest heating element?
1009.3
If the code official determines an installation has become hazardous to life, health, or property, he or she shall order in writing that such installation either be removed or:
113.6.1
Air-conditioning systems that supply required ventilation air must be provided with controls designed to automatically maintain the required outdoor air supply rate during which time period?
405.1
A permit shall not be extended more than:
105.5.4
Venting systems must be designed and constructed to develop a positive flow adequate to convey all combustion products to where?
801.4
When is the use of the space between the corridor ceiling and the floor or roof structure above permitted as a return air plenum, specifically related to the fire suppression system?
601.2.1
What is the capacity in thousands of Btu/h for 1 1/2-inch nominal Schedule 40 metallic pipe at a length of 100 feet, for undiluted propane with an inlet pressure of 10.0 psi and a 1.0 psi pressure drop?
402.4; Table 402.4(25)
Domestic electric water heaters must comply with which UL standard(s)?
1002.1
Where return air risers serve two or more stories and are part of a return air system having a design capacity greater than 15,000 cfm (7.1 m3/s), where must smoke detectors be installed?
606.2.3
Ducts and air transfer openings penetrating fire barriers must be protected with listed fire dampers, unless the duct system has a required fire-resistance rating of 1 hour or less, is in areas other than Group H, is in a fully sprinklered building, AND is constructed of sheet steel not less than what minimum thickness?
607.5.2 Exception 3
Fuel-fired appliances must be designed for use with the type of fuel to which they will be connected and for what other installation factor?
301.12
When combining indoor spaces on the same story for combustion air, what is the minimum free area required for each opening?
304.5.3.1
The clearance reduction methods in Table 308.4.2 shall not reduce the required clearance to less than how many inches for solid fuel-burning appliances labeled for installation with clearances greater than 12 inches?
308.4.2.1
Louvers that protect exhaust openings in structures located in hurricane-prone regions must comply with which standard?
501.3.2
Sauna heaters must be listed and labeled in accordance with which UL standard?
914.2
For fire dampers, the operating temperature of the primary heat-responsive device must be approximately 50{F} above the normal duct temperature, but not less than what minimum temperature?
607.3.3.1
What is the maximum allowable exhaust duct length for a domestic clothes dryer when using the specified length method, excluding transition duct length?
504.9.4.1
Where a factory-built chimney passes through insulated assemblies, the insulation shield shall be constructed of steel having a minimum thickness of 0.0187 inch, which is equivalent to what gauge?
503.5.11
For a Kitchen (cooking) in a food and beverage service occupancy, what is the required Exhaust Airflow Rate in CFM/ft squared?
Table 403.3.1.1
If the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length must be identified on a permanent label located within what maximum distance of the exhaust duct connection?
614.9.5
What creates the pressure difference in a Natural Draft system?
Chapter 2 – Definitions
The code official is authorized to issue an annual permit for alterations to an already approved system to any person, firm, or corporation regularly employing how many qualified tradespersons?
105.1.1
Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts, unless an exception applies. Which term defines this prohibition?
601.2
Which type of boilers are required to be protected with a low-water cutoff control?
1007.1
Which vented appliance category operates with a nonpositive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent?
Chapter 2 – Definitions
A Grease Duct serves which type of hood?
Chapter 2 – Definitions
Where in an occupied area should the inlet to an exhaust system be located?
502.1.1
According to Table 308.4.2, what is the reduced clearance for a horizontal combustible assembly located above the heat source if the required clearance without protection is 36 inches and the protection is galvanized sheet steel (No. 24 gage) spaced 1 inch off the combustible assembly?
Table 308.4.2
A metal-joining process wherein coalescence is produced by the use of a nonferrous filler metal having a melting point above 1,000°F (538°C), but lower than that of the base metal being joined, is:
Chapter 2 – Definitions
A fireplace composed of listed factory-built components assembled in accordance with the terms of listing is a:
Chapter 2 – Definitions
When calculating the minimum required volume using the Known Air-Infiltration-Rate Method (304.5.2), what is the maximum air infiltration rate (ACH) that shall be used in the equations?
304.5.2
What is the primary function of a Stop Valve?
Chapter 2 – Definitions
Which of the following framing cavities or spaces is NOT permitted to be utilized as an air plenum?
602.2.1
A room or space in which people sleep, which can also include permanent provisions for living, eating and either sanitation or kitchen facilities, but not both, is a:
Chapter 2 – Definitions
Inlet ducting, where used with nonrecirculating direct-fired industrial air heaters, shall be purged by not less than how many air changes prior to an ignition attempt?
611.9
Portable residential spas and portable residential exercise spas must comply with UL 1563 or which other CSA standard?
916.1 Exception
Piping located in a flood hazard area must be capable of resisting what three types of loads and stresses during the occurrence of flooding to the design flood elevation?
1206.9.1
How shall the depth of an opening below grade be measured for natural ventilation requirements?
402.4
Where recirculation of air from a space is prohibited (Note b, Table 403.3.1.1), all air supplied to such spaces, including air in excess of that required, shall be what?
403.2.1
The pressure difference created by a vent or chimney because of its height, and the temperature difference between the flue gases and the atmosphere, is defined as:
Chapter 2 – Definitions
When is the code official authorized to make a disconnection of a defective installation immediately without written notice?
113.6.1
Where connecting an appliance to a masonry fireplace flue, the connector must be designed to allow access or be removable for inspection and cleaning of both the connector and the flue.
501.7.3
Preparation of pipe ends requires that pipe be cut square and free from burrs and obstructions, and what two other actions?
1203.2
Carbon monoxide and nitrogen dioxide detectors used for automatic operation of enclosed parking garage ventilation systems must be listed in accordance with which UL standard?
404.1
When calculating clearances for indoor air-conditioning appliances, if the furnace plenum is adjacent to plaster on metal lath, where is the clearance measured if the specified clearance is 2 inches or less?
308.3.3
Equipment and ductwork for exit enclosure ventilation located exterior to the building must be directly connected to the exit enclosure by ductwork enclosed in construction as required by the International Building Code for what purpose?
601.3
For ducts conveying explosive or flammable vapors, fumes or dusts, what is the minimum termination distance from a property line?
501.3.1
An alternative material, design, or method of construction must comply with:
104.2.3.3
What is strictly prohibited from penetrating the grease duct walls?
506.3.3
Which exhaust systems are allowed to be located in ceiling return air plenums over spaces permitted to have 10 percent recirculation (Section 403.2.1, Item 4), provided the duct joints comply with Section 603.9?
601.4 Exception 1
Which standard applies to Copper or copper-alloy tubing (Type K, L or M) used for fuel oil piping?
1302.3
The code official shall perform all of the following duties EXCEPT:
104.3
To determine compliance with maintenance provisions, who has the authority to require an installation to be reinspected?
102.3
What is the maximum water pressure allowed for a hot water heating boiler at or near the boiler outlet?
Chapter 2 – Definitions
When rooftop-mounted solar thermal collectors are mounted on or above the roof covering, the collector array and mounting systems must be constructed of noncombustible materials or what other material conforming to the International Building Code?
1402.8.1.2, 12
Applications for alternative materials, design, and methods of construction and the final decision of the code official shall be:
104.7.3
Who is authorized to terminate a permit for temporary uses, equipment or systems and order the same to be discontinued?
110.4
Heat exchangers used in domestic water-heating systems must be approved for the intended use and must ensure the proper safeguarding of what?
1401.3, 16
Which vented appliance category operates with a positive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent?
Chapter 2 – Definitions
A plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature is:
Chapter 2 – Definitions
Uninhabited spaces, such as crawl spaces and attics, must be provided with natural ventilation openings as required by the International Building Code or a mechanical exhaust and supply air system with a mechanical exhaust rate of not less than how many CFM per square foot of horizontal area?
406.1
What specific type of fluid is strictly prohibited from being utilized as a heat transfer fluid in a solar system?
1403.5, 21
What is the maximum vapor pressure that Flammable Liquids are permitted to have at 100°F (38°C)?
Chapter 2 – Definitions
In flood hazard areas, exhaust outlets serving structures shall be installed at or above the elevation required for utilities and attendant equipment by which code section?
501.3.1
For absorption units, the label information must include the hourly rating in Btu/h (W), the type of fuel, the type of refrigerant, the cooling capacity in Btu/h (W), and what other key information?
301.9
The payment of a permit fee for construction, alteration, removal, or demolition does not relieve the applicant from payment of:
108.5
Equipment and appliances having an ignition source and located in private garages must be elevated such that the source of ignition is not less than how many inches above the floor surface?
304.3
Why does a Single Island Canopy Hood require a greater exhaust airflow than an equivalent sized wall-mounted canopy?
Chapter 2 – Definitions
Gas vents must terminate not less than what minimum vertical distance above any forced air inlet located within 10 feet horizontally?
503.6.8
Construction or work for which a permit is required shall remain visible and able to be accessed for inspection purposes until:
111.1
When a mechanical draft system is used with manually fired appliances and fireplaces, what specific device must be installed that produces visible and audible warning upon failure of the draft device or loss of electrical power?
804.3.8, 36
When inspecting structures or premises, the code official shall carry:
104.5
Large-diameter ceiling fans must be tested and labeled in accordance with AMCA 230, listed and labeled in accordance with UL 507, and installed according to what documentation?
930.1
The makeup air supplied to a commercial kitchen must be conditioned such that the temperature difference between the makeup air and the design setpoint temperature in the kitchen space is not greater than what amount?
508.1.1
Air being removed from any space or piece of equipment or appliance and conveyed directly to the atmosphere by means of openings or ducts is defined as:
Chapter 2 – Definitions
For piping materials other than steel pipe and CSST, exposed piping must be identified by a yellow label marked “Gas” in black letters at intervals not exceeding what distance?
401.5
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 4-inch radius mitered 45-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
What is the function of a Flame Safeguard?
Chapter 2 – Definitions
Which type of thermostat is an automatic device, actuated by temperature changes, in which the thermal actuating element is an integral part of the device?
Chapter 2 – Definitions
Oil-fired appliances shall be provided with combustion air in accordance with which specific standard?
701.1
For Group R-2, R-3, and R-4 occupancies, the minimum continuous outdoor airflow rate is calculated using Equation 4-9 based on conditioned floor area and what other variable?
403.3.2.1
The use of what medium is prohibited when removing debris from the interior of a piping system?
404.18
Prior to approval of a prefabricated construction assembly having concealed mechanical work, what shall the code official require the submittal of?
111.2.5
For which purpose may the code official authorize the temporary connection of a system to a utility?
109.2
Factory-built cooling towers must be listed in accordance with UL 1995 or which other standard?
908.1
If a code provision is less restrictive than the conditions of the equipment listing, which requirement shall apply?
305.1
Return air for heating or air-conditioning systems shall not be taken from which two types of locations?
601.5
Air dispersion systems must be listed and labeled in compliance with which UL standard?
603.17
What is the capacity in thousands of Btu per hour for 4-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 1,000 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(36)
Where a structure or premises is occupied and the code official needs to perform an inspection, what must the code official do?
104.4
Where must the discharge line of a fuel oil system relief valve connect?
1307.5
What type of damper must comply with the requirements of UL 555C or be tested as part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly in accordance with ASTM E119 or UL 263?
607.3.1
It shall be the duty of the permit holder to provide access to and means for inspection of such work that is required by this code and to notify the code official when the work is:
111.2.2
What is required for a Type I Hood, which collects and removes grease vapors and smoke?
Chapter 2 – Definitions
Refrigerant circuit access ports located outdoors must be fitted with what type of cap?
1101.9
A Portable Fuel Cell Appliance utilizes what connection type to a grid-isolated load?
Chapter 2 – Definitions
The code official has authority to suspend or revoke a permit if the permit was issued in error or on the basis of:
105.5.5
Tests conducted to demonstrate equivalent fire safety must be sufficient scale to predict fire safety performance of the:
104.2.3.5.1
Which type of appliance is explicitly stated to not be governed by the methods of providing combustion air detailed in Chapter 7?
701.1
Each buffing machine in a tire rebuilding or recapping room must be connected to a dust-collecting system that prevents what?
502.17.1
What is the minimum required clearance from the top of a hot water-heating boiler with manholes on top to the ceiling?
Table 1004.3.1
Motors for fans used to convey flammable vapors or dusts must be located outside the duct or protected with what?
503.1
The issuance of a permit or construction documents approval shall not be construed to be a permit for or an approval of any:
105.5.2
If a timer is provided to control the main burner operation of a sauna heater, what is the maximum operating time allowed?
914.4.1
A flux conforming to which ASTM standard must be applied to a soldered joint?
1203.3.3
Heat-fusion joints for polypropylene (PP) pipe and tubing joints must be installed in accordance with which ASTM standard?
1203.15.1
Grease filters must be installed at a minimum angle of how many degrees from the horizontal?
507.2.8.2
A Pellet Fuel-Burning Appliance is equipped with what type of mechanism for burning processed pellets of solid fuel?
Chapter 2 – Definitions
Who is authorized to establish a refund policy for fees?
108.6
For residential-type appliances, if not installed in unconditioned areas, a vent connector made of galvanized sheet steel must be not less than what minimum thickness?
503.10.2.3
Before a permit is issued, the code official is authorized to perform what action?
105.3.1
Which location is required to have a stop valve on refrigeration systems containing more than 6.6 pounds (3.0 kg) of refrigerant?
1109.6.1
When sizing piping using the Longest Length Method, the pipe size is determined using the longest length of piping from the point of delivery to which point?
402.4.1
Which classification of clothes dryer is primarily used in a family living environment and is usually the smallest unit physically and in function output?
Chapter 2 – Definitions
Joints between different metallic fuel oil piping materials must be made with approved dielectric fittings or what other type of fitting?
1303.1.1
Class IC Flammable Liquids have a flash point at or above 73°F (23°C) and below what maximum temperature?
Chapter 2 – Definitions
What is the minimum clearance required above an appliance where the original required clearance was 9 inches, and the protection is 1/2-inch insulation board with ventilated airspace?
308.2; Table 308.2
For a single draft-hood-equipped appliance connected directly to a single-wall metal pipe (Table 504.2(5)), if the vent height (H) is 20 feet and the lateral (L) is 15 feet, what is the maximum input rating in thousands of Btu/h for a 7-inch diameter vent?
504.2; Table 504.2(5)
Catwalks installed to provide required access on elevated structures shall be not less than how many inches wide?
306.5
If equipment replacements or repairs must be performed in an emergency situation, the permit application shall be submitted within what timeframe?
105.1 Exception
What electrical component is required at or near equipment located on a roof or elevated structure?
306.5.2
The amount of return air taken from any room or space shall not be greater than what value?
601.5
Which component is part of a Duct System?
Chapter 2 – Definitions
A BTU is the quantity of heat required to raise the temperature of 1 pound (454 g) of water by how many degrees Fahrenheit?
Chapter 2 – Definitions
A field-constructed chimney of metal is a:
Chapter 2 – Definitions
What is the estimated maximum occupant load rate per 1,000 square feet for a Smoking lounge?
Table 403.3.1.1
An independent and objective technical review conducted by an approved third party is defined as a:
Chapter 2 – Definitions
A low-heat appliance (residential appliance) is defined as any appliance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of:
Chapter 2 – Definitions
Where a draft hood is required but not supplied by the manufacturer, and no instructions are available, the installed draft hood shall be of the same size as which other appliance component?
503.12.2.1
Additions, alterations, renovations, or repairs related to structural issues shall be regulated by which other code?
102.2.1
For a sloped roof (3 units vertical in 12 units horizontal or greater) where an appliance is installed and the roof edge is more than 30 inches above grade, a level platform must be provided on which side(s) of the appliance?
306.5.1
A self-contained package of integrated systems for generating electrical energy and recoverable thermal energy that is permanently connected and fixed in place is defined as what?
Chapter 2 – Definitions
Storage tanks and heating equipment installed in outdoor locations must be designed for what specific condition?
1402.8.5.2, 18
Temporary uses, equipment, and systems shall conform to the requirements of this code as necessary to ensure what?
110.2
Exhaust outlets serving Type II hoods that terminate above a roof must terminate not less than how many inches above the roof surface?
506.4.2
Fire dampers must have a minimum rating of 1.5 hours for which type of fire-resistance-rated assemblies?
Table 607.3.2.1
In case of emergency, the code official has the authority to authorize disconnection of utility service where necessary to eliminate what?
109.3
Outdoor air inlets serving a nonresidential portion of a building must be covered with a screen having openings larger than 1/4 inch (6.4 mm) and not larger than what maximum size?
618.4
For a light test on a grease duct system, the lamp used must have a rating of not less than how many lumens?
506.3.2.5.1
The highest stress level that the component will tolerate without rupture is defined as what?
Chapter 2 – Definitions
Hydronic piping materials must be rated for the operating temperature and pressure of the system and must be suitable for what other specific factor?
1202.3
The requirements for combustion and dilution air for gas-fired appliances must be in accordance with which code?
701.1
For an attic passageway to an appliance, what is the maximum length allowed if the passageway is at least 30 inches high and 22 inches wide?
306.3
The Breathing Zone is the region within an occupied space located between planes 3 inches (76 mm) and what maximum height above the floor?
Chapter 2 – Definitions
What inert gas must be used to purge air from piping being brazed to remove oxygen?
1108.3.1
A heater in which all the products of combustion generated by the burners are released into the air stream being heated, with the purpose of offsetting building heat loss by heating outdoor air, and, if applicable, indoor air, is a:
Chapter 2 – Definitions
Chimneys for medium-heat appliances shall extend not less than what horizontal distance higher than any portion of any building within 25 feet?
503.5.4
Which types of copper or copper-alloy tube (Type K, L or M) are listed as acceptable piping materials in Table 1202.4?
Table 1202.4
Construction documents, engineering calculations, diagrams, and other data shall be submitted with each application for a permit in what minimum number of sets (unless digital submission is allowed)?
106.1
A system or material used to form the inside surface of a flue in a chimney or vent, for the purpose of protecting the surrounding structure and conveying combustion products without leakage, is a:
Chapter 2 – Definitions
A device used in piping to control the gas supply to any section of a system of piping or to an appliance is a:
Chapter 2 – Definitions
A joint made by bolting together a pair of flanged ends is a:
Chapter 2 – Definitions
Which two CGA standards, along with CGA S-1.3, govern the sizing and selection of pressure relief devices for gaseous hydrogen systems?
703.3
Official records required by the code official shall be retained for not less than 5 years or for how long?
104.7
For HPM exhaust ducts, what is prohibited from being installed in the exhaust ducts?
502.10.2
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter of 8 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
Where are shutoff valves required on a heat exchanger?
1205.1.1
A Self-Contained Refrigeration System is factory-assembled and tested, and does not have refrigerant-containing parts joined in the field by other than what?
Chapter 2 – Definitions
When using the Combination Indoor and Outdoor Combustion Air method, how is the outdoor opening size reduction factor determined?
304.7.3
What is the maximum capacity in cfh for 2 1/2-inch nominal Schedule 40 metallic pipe at 400 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
In private garages, equipment and appliances having an ignition source must be elevated such that the source of ignition is not less than what distance above the floor?
305.3
The pressure difference existing between the appliance or any component part and the atmosphere, that causes a continuous flow of air and products of combustion, is defined as:
Chapter 2 – Definitions
A safety valve designed to forestall the development of a dangerous condition by relieving either pressure, temperature or vacuum in the hot water supply system is a:
Chapter 2 – Definitions
If a notice of violation is not complied with promptly, the code official shall request the legal counsel of the jurisdiction to institute the appropriate proceeding to restrain, correct, or:
113.3
What is the capacity in cubic feet per hour (cfh) for Flow Designation 23 CSST at a length of 100 feet, for natural gas with a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(17)
Naturally ventilated refrigerant pipe shafts (Group A2L or B2L) must have a pipe, duct, or conduit connecting the lowest point of the shaft to the outdoors, with a minimum diameter of what size?
1109.3.2
A device that will automatically shut off the fuel supply to a main burner or group of burners when the means of ignition becomes inoperative or flame failure occurs is a:
Chapter 2 – Definitions
A mechanical system that is unsafe, constitutes a fire or health hazard, or is otherwise dangerous to human life is declared to be what?
114.6
On down-flow units that do not have provisions to install a secondary drain pan, where must a water-level monitoring device be installed?
307.2.3.1
Where a listing standard for equipment is not specified by this code, the listing shall be based on:
104.2.1
The approved agency must periodically perform an in-plant inspection of the appliances to be labeled to verify that the labeled appliances are representative of the appliances that were:
301.4.2
What is the minimum inside diameter required for a fuel oil supply line pipe?
1305.1
The details of the written request for and action granting modifications must be recorded and entered into the files of the:
104.2.4
Before replacing an existing appliance, the chimney passageway must be examined to ascertain that it is clear and free of obstructions and must be cleaned if previously used for venting which types of appliances?
503.5.6
Reused pipe, fittings, valves, or other materials must be clean and free from foreign materials and must be approved by whom for reuse?
1202.2
What is the minimum clearance required above the top of the sloping side of a vertical draft hood on a suspended unit heater?
620.4
An employee charged with the enforcement of this code is relieved from personal liability provided they are acting for the jurisdiction in good faith and without what?
104.8
Supply air plenums formed by gypsum boards shall not be incorporated in air-handling systems utilizing which specific cooling system type?
602.2
Who must be notified prior to making a change of refrigerant in an existing system to a refrigerant with a different refrigerant designation?
1101.7
Condensate waste and drain line size shall be not less than what minimum pipe size?
307.3
Rooms containing appliances must be provided with an unobstructed passageway measuring not less than what minimum width and height?
306.2
A rigid conduit of iron, steel, copper, copper-alloy or plastic is defined as:
Chapter 2 – Definitions
What is the capacity in cfh for 3-inch nominal Schedule 40 metallic pipe at 250 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(3)
For an exterior masonry chimney serving a single space-heating appliance in a climate zone with a Local 99% Winter Design Temperature of 27 to 36°F, with a vent height of 10 feet and an internal area of 38 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.2; Table 504.2(6)
Who is authorized to require design submittals for reports not complying with Section 104.2.3.6.1 to be prepared by, and bear the stamp of, a registered design professional?
104.2.3.6.2
In a multistory common exhaust system, the exhaust fan must run continuously and be connected to what type of backup system?
614.11
Where an exterior masonry chimney serves two or more draft-hood equipped space-heating appliances (NAT+NAT) in a climate zone with a Local 99% Winter Design Temperature of 5 to 16°F, with a vent height of 10 feet and an internal area of 50 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.3; Table 504.3(6b)
What is the required operating temperature for the actuation device of a ceiling radiation damper?
607.3.3.4
Controls and safety devices for boilers with fuel input ratings of less than 12,500,000 Btu/hr must meet the requirements of which standard?
1004.1
Where single-wall metal pipe passes through a combustible exterior wall serving a listed appliance with a draft hood, the ventilated metal thimble must be not less than 4 inches larger in diameter than the metal pipe, unless a minimum horizontal pipe run of 6 feet is provided in the open, in which case the thimble can be not less than how much larger in diameter than the metal pipe?
503.7.7
What is the maximum percentage of the specified minimum yield strength of the pipe that the hoop stress can reach during a pressure test exceeding 125 psig (862 kPa gauge)?
705.3.3
Materials, equipment, and devices shall not be reused unless they are in good working condition and meet what other requirement?
104.9.1
The application for a permit shall be signed by whom?
105.3
Cutting, notching, and boring of wood framing members shall comply with which section of the International Building Code?
302.3
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 12 inches, and the protection is 3 1/2-inch-thick masonry wall without ventilated airspace?
308.2; Table 308.2
A manual shutoff control for hazardous exhaust systems in storage rooms must be provided outside the room adjacent to the access door, and what must the switch be labeled?
502.8.1.1
Appliances equipped with an automatic burner ignition and safety shutoff device and other automatic devices that accomplish complete turn-on and shutoff of the gas to the main burner(s) and graduate the gas supply, but do not affect complete shutoff of the gas, are defined as:
Chapter 2 – Definitions
Provisions of this code are not mandatory for existing historic buildings where the code official judges the building to be safe and in the public interest of what?
102.6
Subslab soil exhaust system ducts must terminate not less than how many feet from any operable openings or air intake?
511.4
If a separate overflow drain line is connected to the equipment drain pan, at what level must it connect relative to the primary drain connection?
307.2.3
What does this document establish to provide a reasonable level of safety, health, property protection and general welfare?
101.3
What is the maximum capacity in thousands of Btu per hour for 1 1/2-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 500 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(35)
What is the minimum net airflow required for Type II hoods used for dishwashing appliances, per linear foot of hood length?
507.3.4.2
What is the minimum net airflow required for a Double Island Canopy Hood (per side) used for extra-heavy-duty cooking appliances?
507.2.10.1
What specific piping must be removed when fuel oil tanks are abandoned or removed?
1301.5
For natural gas systems, which device is installed by the serving gas supplier to reduce and limit the service line pressure to delivery pressure?
Chapter 2 – Definitions
A continuous open passageway from the flue collar or draft hood of an appliance to the outdoor atmosphere for the purpose of removing flue or vent gases is a:
Chapter 2 – Definitions
How shall defective material or parts be replaced or repaired?
301.14
A unit consisting of a burner and its controls for installation in an appliance originally utilizing another fuel is a:
Chapter 2 – Definitions
Exhaust ducts for domestic clothes dryers shall be supported at intervals not exceeding what maximum distance?
614.9.2
Parts of fans in contact with explosive or flammable vapors, fumes or dusts shall be constructed of what type of materials?
503.2
Where connected to rigid piping, a union fitting must be installed within what maximum distance of either side of an MP regulator?
410.2
What is the minimum required thickness (in inches) for a steel vent connector serving a medium-heat appliance with an area between 201 and 254 square inches?
503.10.2.5; Table 503.10.2.5
Where terms are not defined through authorized methods, such terms shall have what kind of meanings, as the context implies?
201.4
Supports for cooling towers, evaporative condensers, and fluid coolers must be designed in accordance with which code?
908.4
For refrigerant blends not listed in Table 1103.1, a machinery room is required if the combined amount of blend components exceeds a limit of what maximum concentration by volume?
1104.2
Piping that is located in a concealed location is defined as:
Chapter 2 – Definitions
Masonry chimneys exposed to the outdoors on one or more sides below the roof line are defined as:
Chapter 2 – Definitions
What components must be installed to allow the solar loop to be isolated from the remainder of the system?
1402.8.6.1, 18
Which of the following is NOT one of the rooms or spaces from which fuel-fired appliances shall not obtain combustion air?
303.3
In multiple-tenant buildings, shutoff valves for each tenant must be provided with access and must be located where?
409.3.1
Oil-fired water heaters must comply with which UL standard?
1002.1
Mechanical joints used on steel or stainless steel fuel oil pipe and employing an approved elastomeric seal must generally be installed in which location?
1303.7.1
Which components are prohibited from being attached to vented wall furnaces unless listed as part of the appliance?
909.4
A Ductless Mini-Split System is comprised of one or multiple indoor evaporator/air-handling units and an outdoor condensing unit that is connected by refrigerant piping and what other feature?
Chapter 2 – Definitions
Fans in systems handling materials that are capable of clogging the blades, such as buffing or woodworking exhaust systems, must be of which fan type?
503.2
Drain and fill valves must be labeled with a description and warning that identifies the fluid in that loop as “Potable Water,” “Food-Grade Fluid,” “Nonfood-Grade Fluid” or what fourth category?
1404.3, 22
Recirculating direct-fired industrial air heaters shall be listed to which standard?
612.1
The LFL for refrigerants is determined in accordance with specific test conditions established by which standard?
Chapter 2 – Definitions
What is the approximate number of threads required to be cut for a 2 1/2-inch iron pipe size?
403.8.2; Table 403.8.2
A through-the-wall direct-vent terminal serves an appliance rated at 100,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
What is the minimum exhaust rate required per square foot of floor area for spaces containing cooking appliances that do not require Type II hoods, such as those that produce only heat or moisture?
507.1 Exception 2
Exhaust fan motors serving a Type I hood must be located where relative to the exhaust airstream?
506.5.1.1
Water heaters utilized for both potable hot water and space-heating applications must be listed and labeled for such applications and installed in accordance with the manufacturer’s instructions and which other code?
1002.2
If granted, an extension of time to commence work under an unexpired permit shall not exceed how many days?
105.5.4
What is the maximum input rating allowed for a single wall-mounted unvented room heater installed in a bedroom?
303.3
What is the maximum on-center spacing allowed for permanent ladder rungs?
306.5
Use of a corridor as a source of makeup air for exhaust systems in adjacent rooms is permitted, provided the corridor is directly supplied with outdoor air at what rate?
601.2 Exception
Mechanical systems that are part of structures moved into or within the jurisdiction shall comply with provisions for which type of installations?
102.7
If the code official believes the estimated valuation of work provided by the applicant is underestimated, what action may be taken?
108.3
What is the maximum circuit length allowed for 5/8-inch nominal tube size radiant heating tubing from a supply-and-return manifold arrangement?
Table 1209.6.1
Piping to be embedded in concrete must be pressure tested prior to pouring concrete, and during pouring, the pipe must be maintained at what pressure?
1209.2
What is the minimum clearance required from the sides and rear of a single-wall metal pipe where the original required clearance was 6 inches, and the protection is 0.024-inch sheet metal with ventilated airspace over 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
A valve of the plug and barrel type provided with means for maintaining a lubricant between the bearing surfaces is a:
Chapter 2 – Definitions
Flammable gas cylinders in occupancies regulated by the International Residential Code shall not exceed what maximum volume at normal temperature and pressure (NTP)?
703.2.1
What is the minimum pressure difference required across a smoke barrier in buildings equipped throughout with automatic sprinkler systems when utilizing the pressurization method?
512.6.1
Steam boilers must be protected with which type of safety device?
1006.1
Unvented alcohol fuel-burning decorative appliances must be listed and labeled in accordance with which UL standard?
929.1
Where do Direct-Vent Appliances derive all air for combustion?
Chapter 2 – Definitions
An attic passageway that is not less than 6 feet high for its entire length shall be not greater than what maximum length?
306.3 (Exception 2)
If means for isolation of vibration of an appliance is installed, what else must be provided?
301.8
Which material fittings are strictly prohibited from being used in fuel oil piping systems?
1303.1
In commercial tenant spaces, the use of corridors for conveying return air is permitted if the tenant space area is not more than what size?
601.2 Exception
According to Table 1009.2, what is the required nonpressurized expansion tank capacity in gallons for a system volume of 500 gallons?
Table 1009.2
Which decorative appliance is exempt from the requirement to use a flame safeguard device?
602.2
For each elbow up to and including 45 degrees in the common vent of a multiple appliance system, the maximum common vent capacity must be reduced by what percentage?
504.3.6
Which valve controls the gas supply to the main burner manifold?
Chapter 2 – Definitions
Arc-resistant-jacketed CSST shall be listed as arc resistant in accordance with which standard?
310.3
Where damage to any building components could occur from overflow of the primary condensate system, what is one auxiliary protection method that must be provided?
307.2.3
What is the maximum control voltage permitted for the electrical control system of a boiler?
1006.8
Which chimney flues are exempt from the cleanout requirement if access is provided through the fireplace opening?
801.13 Exception, 7
What is the capacity in thousands of Btu per hour for CSST Flow Designation 60 at 10 feet in length, for undiluted propane operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(34)
Shutoff valves are not required at heat exchangers that are integral with a boiler, or capable of being isolated by supply and return valves required by which section?
1205.1.1 Exception
What are the two primary components that a Venting System is usually composed of?
Chapter 2 – Definitions
A Combustible Assembly is constructed of one or more component materials that are not defined as what?
Chapter 2 – Definitions
What material is specified as a required thermal break where a heated slab meets a foundation wall or other conductive slab?
1209.5.1
In Group I-1 and I-2 occupancies, range hoods over domestic cooking equipment must have a minimum airflow rate of how many CFM?
505.7, 505.8
Panel Heating usually consists of warm water piping, warm air ducts, or what other element embedded in or located behind ceiling, wall or floor surfaces?
Chapter 2 – Definitions
Recovered refrigerants may be reused only in the system from which they were recovered and in other systems of what party?
1102.2.2.2
When utilizing the airflow design method for smoke control, the airflow toward the fire shall not exceed what maximum velocity?
512.7.1
New wood-burning residential hydronic heaters must have what certification?
905.1
For naturally ventilated hydrogen-generating operations, what is the minimum free area required for the two permanent openings per 1,000 cubic feet of garage volume?
304.5.1.1
Joints between dissimilar metallic piping materials must be made with a dielectric fitting or what other component conforming to dielectric tests of ASSE 1079?
1108.1.1
A transition assembly in which plastic piping is installed and terminated above ground outside of a building is known as a(an):
Chapter 2 – Definitions
What is the minimum fire-resistance rating required for a grease duct enclosure?
506.3.11
Household electric ranges must be listed and labeled in accordance with which UL standard?
917.1
The code official has the authority to waive the submission of construction documents if the nature of the work is such that reviewing the documents is not necessary to determine what?
106.1 Exception
A small flame that is utilized to ignite the gas at the main burner or burners is a:
Chapter 2 – Definitions
Spaces above, below, or behind what feature shall NOT be considered a concealed location?
Chapter 2 – Definitions
Air distribution, ventilation, and exhaust systems must be provided with means to adjust the system to achieve the design airflow rates and shall be balanced by what method?
608.1
What is the capacity in cfh for 1/2-inch nominal Schedule 40 metallic pipe at 700 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(4)
The code official is authorized to appoint a deputy code official, technical officers, and inspectors with the concurrence of whom?
103.3
What is the minimum length (in feet) of nominal 4-inch piping that, when removed from service, must have its residual fuel gas displaced with an inert gas?
406.7.1.1; Table 406.7.1.1
Flexible ducts and air connectors are prohibited from passing through what type of building assembly?
607.7
Members of the board of appeals shall not be what?
112.3
For piping installed in concealed locations, shield plates are required if the pipe is less than how far from the nearest edge of the wood framing member?
305.5
For exterior masonry chimneys serving two or more Category I appliances (NAT+NAT) with Type B double-wall connectors, if the vent height is 15 feet and the internal area is 78 square inches, what is the maximum combined input rating in thousands of Btu per hour?
504.3; Table 504.3(6a)
For listed and labeled appliances, clearances shall not be reduced where reduction is specifically prohibited by what?
308.2
A Combination Fire/Smoke Damper must be capable of being positioned from where?
Chapter 2 – Definitions
Electric kilns must comply with which UL standard?
923.1
Which characteristic is true of a Ground Source Heat Pump Loop System?
Chapter 2 – Definitions
To free a gas conduit of air or gas, or a mixture of gas and air, is to:
Chapter 2 – Definitions
Where plastic vents are specified by the appliance manufacturer for Category IV appliances, are they required to be listed and labeled?
502.1
A heater that directs a substantial amount of its energy output in the form of infrared radiant energy into the area to be heated is a(an):
Chapter 2 – Definitions
In residential garages, appliances installed in a separate, enclosed space having access only from outside the garage are permitted to be installed at floor level, provided the required combustion air is taken from where?
305.3.1
Which type of thermostat senses temperature changes and controls the flow of gas to the burner(s) electrically, by means of separate components?
Chapter 2 – Definitions
Which venting system is permitted for listed combination gas and oil-burning appliances?
503.4; Table 503.4
What is the required People Outdoor Airflow Rate in the Breathing Zone in CFM/person for a Bedroom/living room in hotels, motels, resorts, and dormitories?
Table 403.3.1.1
What is the capacity in thousands of Btu/h for 1 1/4-inch nominal Schedule 40 metallic pipe at a length of 100 feet, for undiluted propane with an inlet pressure of 11.0 in. w.c. and a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(28)
What is the minimum horizontal distance required between vertical discharge fans and parapet-type building structures?
506.5.6 Exception
Stationary engine generator assemblies must meet the requirements of which UL standard?
915.1
Type L vents and pellet vents shall be tested in accordance with which UL standard?
802.1, 15
For smoke control systems, belt-driven fans must have what multiple of the number of belts required for the design duty, with a minimum of two belts?
512.10.5
What is the minimum level working space required in front of the control side to service an appliance?
306.1
When the free area of a louver or grille is not known, what percentage free area shall be assumed for metal louvers and grilles?
304.5.1.2
The approval of unlisted appliances must be based on:
301.3
The strength and rigidity of posts greater than 3 feet (914 mm) in height supporting illuminating appliances must be at least equivalent to a 2 1/2-inch-diameter (64 mm) post constructed of what minimum thickness of steel?
628.3
The code official has authority to grant extensions for time limitations on a permit application for additional periods, not exceeding how many days each?
105.3.1
What is the minimum horizontal distance required between exhaust outlets for grease ducts and adjacent property lines?
506.3.13.3
A Positive Displacement Compressor achieves an increase in pressure by changing what component?
Chapter 2 – Definitions
Where plastic piping is used to vent a listed appliance, the appliance manufacturer’s instructions must identify what characteristic of the plastic piping?
503.4.1
A valve designed to activate when the fuel gas passing through it exceeds a prescribed flow rate is a(an):
Chapter 2 – Definitions
A notice of violation served by the code official shall direct the discontinuance of the illegal action or condition and the:
113.2
Regarding modifications in flood hazard areas, the code official shall not grant a modification unless a determination has been made that failure to grant the variance would result in exceptional hardship by rendering the lot what?
104.2.4.1
The installing contractor or registered design professional must issue a certificate of test to the code official for all refrigeration systems containing what minimum amount of refrigerant?
1110.7
A time limit for compliance with an order to remove or restore an unsafe installation to a safe condition shall be specified in the:
113.6.1
For a roof slope between Over 10/12 to 11/12, what is the minimum required vertical height (H) above the roof to the lowest discharge opening?
503.6.5; Figure 503.6.5 (Table)
What is the minimum exhaust ventilation rate required for a repair garage used for compressed natural gas, liquefied natural gas, or other lighter-than-air motor fuel (other than hydrogen)?
502.16.2.1
Control-air tubing for smoke control systems must be tested at what multiple of the operating pressure for not less than 30 minutes?
512.13.3
The maximum horizontal length of a Type B double-wall connector shall be what percentage of the height of the chimney or vent?
503.10.9
The minimum internal dimension allowed for any shaped single-wall metal pipe used for venting must be not less than what dimension?
503.7.10
Where the area beneath a veranda, porch, deck, or balcony is open on not less than two sides, what is the minimum clearance (Clearance K) required to the underside of that structure for a vent terminal?
503.8; Table 503.8
For CPVC pipe joint connections, a primer is not required if the solvent cement is used only for joining CPVC pipe and fittings within what diameter range?
1203.3.4 Exception
Who appoints the code official?
103.2
What is the minimum clearance required above a paved sidewalk or paved driveway located on public property (Clearance J) for a vent terminal?
503.8; Table 503.8
What components shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance?
803.1, 19
If excavated soil contains rubble that would damage the piping, clean backfill shall be required where?
111.2
What is the maximum spacing of supports (in feet) required for horizontal smooth-wall copper tubing with a 5/8-inch outside diameter (O.D.)?
415.1; Table 415.1
For equipment with a capacity over 20 tons up to 40 tons of refrigeration, what is the minimum required condensate pipe diameter?
Table 307.2.2
Refrigerant piping protection is not required outside the building if the piping is installed underground not less than how many inches below finished grade and protected against corrosion?
1109.2.2
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 10-inch radius smooth 45-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
In the context of this code, which term refers to the rapid oxidation of fuel accompanied by the production of heat or heat and light?
Chapter 2 – Definitions
To prevent the entry of room air into a chimney flue below the point of connection to an appliance serving a fireplace, what type of seal must be provided?
501.7.1
For naturally ventilated hydrogen-generating operations, where must the upper of the two required permanent openings be located?
304.5.1.1
Where shall valves NOT be installed on a fuel oil piping system?
1305.4
Air removed by mechanical exhaust systems shall not be exhausted into an attic, a crawl space, or be directed onto what other location?
501.3
The purpose of an Energy Recovery Ventilation System is to preheat, precool, humidify, or dehumidify outdoor ventilation air prior to supplying such air to a space using what mechanism?
Chapter 2 – Definitions
What is the capacity in cfh for 1 1/4-inch nominal OD Polyethylene plastic pipe at a length of 200 feet, for natural gas with an inlet pressure less than 2 psi and a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(21)
For horizontal terminations of mechanical draft systems adjacent to walkways, what is the minimum required height above the walkway level?
804.3.4, 33
Electric Heating Appliances produce heat energy by the application of electric power to resistance elements, refrigerant compressors, or what other mechanism?
Chapter 2 – Definitions
Truss members and components shall not be cut, drilled, notched, spliced, or otherwise altered without whose written concurrence and approval?
302.4
Where the duct is constructed of steel not less than 0.019 inch in thickness and there are no openings serving the corridor, smoke dampers are not required at which penetrations?
607.5.4 Exception 3
A masonry chimney flue cleanout opening must have a minimum height of 6 inches and its upper edge must be located not less than what vertical distance below the lowest chimney inlet opening?
501.15.3
That which enables a device, appliance or equipment to be directly reached, without requiring the removal or movement of any panel, door or similar obstruction is defined as:
Chapter 2 – Definitions
Electric duct furnaces must comply with which UL standard?
911.1
An object placed in an appliance to change the direction of or retard the flow of air, air-gas mixtures or flue gases is a:
Chapter 2 – Definitions
Upblast fans serving Type I hoods and installed in a vertical or horizontal position must be hinged and equipped with a means of restraint to limit what?
506.5.4
What is the primary difference between Ready Access (To) and Access (To)?
Chapter 2 – Definitions
Where unvented infrared heaters are installed, outdoor ventilation air must be provided at a rate of not less than 4 cfm per what unit of the aggregate input rating of all such heaters installed in the space?
630.3
Who must test a representative sample of appliances being labeled to the relevant standard?
301.4.1
Heat-fusion joints for polyethylene pipe used in ground-source loops must be joined in accordance with which ASTM standard?
1210.6.6.1
A thermostat controlling a sauna heater must limit the room temperature to what maximum temperature?
914.4
Appliances located in public garages or repair garages shall be installed not less than how many feet above the floor?
304.6
Which occupancy includes hospitals, nursing homes, asylums, and spaces containing locked cells?
1103.2
Where an appliance is connected to an existing chimney or vent, the system must be resized to control flue gas condensation and provide the required:
501.15.1
A horizontal vent system termination shall terminate not less than how many feet below, horizontally from, or 1 foot above any door, window, or gravity air inlet into the building?
804.3.4, 33
What is the required Area Outdoor Airflow Rate in the Breathing Zone in CFM/ft squared for a Coin-operated laundry?
Table 403.3.1.1
Galvanized sheet steel auxiliary drain pans must have a minimum thickness of not less than what gauge?
307.2.3
In areas containing flammable vapors or dusts, motors driving exhaust fans shall be of a type approved for what?
503.1
A room or space in which people sleep, which can include permanent provisions for living, eating, and either sanitation or kitchen facilities but not both, is defined as what?
Chapter 2 – Definitions
When using the Two-Permanent-Openings Method (304.6.1) and communicating directly with the outdoors, what is the minimum free area required for each opening per 4,000 Btu/h of total appliance input rating?
304.6.1
Which warning statement is required on the fluid safety labeling for drain and fill valves?
1404.3, 22
Factory-built fireplaces must be listed and labeled and tested in accordance with which UL standard?
903.1
A fuel oil fill pipe must terminate outside a building at a point not less than what minimum distance from any building opening at the same or lower level?
1305.6
Any suit or criminal complaint instituted against an officer because of an act performed in the lawful discharge of duties shall be defended by:
104.8.1
What is the temperature range of the products of combustion at the point of entrance to the flue for a Medium-heat appliance?
Chapter 2 – Definitions
Where must the design outdoor air balance be included in design plans for a facility with a commercial kitchen ventilation system?
508.1.3
What is the minimum air velocity required within a grease duct system?
506.3.4
Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through what two building elements?
509.5.7
Provisions contained in the appendices shall apply only if they are:
101.2.1
For gas cabinets containing highly toxic or toxic compressed gases in any quantity, what is the minimum acceptable ventilation velocity at any point at the access port or window?
502.9.7.1
In addition to meeting minimum CFM requirements, the exhaust rate for xenon motion picture projectors must be such that the exterior temperature of the lamp housing does not exceed what temperature?
502.11.2
What is the maximum capacity in thousands of Btu/h for 4-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(25)
A low-water cutoff is not required for coil-type and water-tube-type boilers that require forced circulation, provided they are protected with what specific control?
1007.1 Exception
For fuel-burning units, the required label information includes the hourly rating in Btu/h (W), the required clearances, and what specific fuel detail?
301.9
Which medium is strictly prohibited from being used to pressurize fuel oil tanks?
1305.5
What is the portion of a building included between the upper surface of the topmost floor and the ceiling or roof above?
Chapter 2 – Definitions
What must be done to the parts in a Plastic Heat Fusion Joint to permit fusion of the materials when the parts are pressed together?
Chapter 2 – Definitions
A manually operated damper shall not be placed in the vent connector for any appliance, but fixed baffles and balancing baffles are not classified as manually operated dampers.
503.13
A vented self-contained, free-standing, nonrecessed appliance for furnishing warm air to the space in which it is installed, directly from the heater without duct connections, is a:
Chapter 2 – Definitions
For horizontal 1 1/2-inch steel pipe, what is the maximum spacing of supports permitted in feet?
415.1; Table 415.1
Who has the duty to notify the code official when work is ready for inspection?
111.2.2
A pipe in a ground-source heat pump piping system having an exterior surface temperature exceeding 250{F} must have a minimum clearance of what distance from combustible materials?
1210.8.3
What type of joint connection must NOT be used for clothes dryer exhaust ducts?
504.4
Protective shield plates for clothes dryer exhaust ducts must be constructed of steel and have a minimum thickness of 0.062 inch (1.6 mm).
614.8
A warm-air furnace normally installed in an air distribution duct to supply warm air for heating, depending for air circulation on a blower not furnished as part of the furnace, is a:
Chapter 2 – Definitions
Variable air volume air distribution systems, other than those supplying 100-percent outdoor air, must be provided with controls to regulate the flow of outdoor air to maintain the flow rate at not less than that required by what section?
403.3.1.4
The Refrigerant Safety Group Classification indicates both the flammability and what other classification of refrigerants?
Chapter 2 – Definitions
Masonry chimneys shall be constructed in accordance with which code?
801.3
Freeze-protection valves must discharge in a manner that does not create what two potential issues?
1402.4.2, 8
Exhaust system discharge for dust, stock, and refuse conveying systems is permitted to be recirculated, provided the solid particulate has been removed at a minimum efficiency of 99.9 percent at what particle size?
510.1.3
Round metallic ducts must be mechanically fastened by means of not less than how many sheet metal screws or rivets spaced equally around the joint?
603.4.1
What additional device must be installed in the room with a manually fired appliance or fireplace when utilizing a mechanical draft system?
804.3.8, 36
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 6 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
Permanently installed electric space heaters must be listed and labeled in accordance with which UL standard?
912.1
A fuel cell generator of electricity, which is not fixed in place, utilizes a cord and plug connection to a grid-isolated load and has an integral fuel supply is a:
Chapter 2 – Definitions
When two or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical vent or chimney shall not exceed what multiple of the flow area of the smallest listed appliance categorized vent area?
504.3.17
What is the minimum clearance required above an appliance where the original required clearance was 18 inches, and the protection is 1/2-inch insulation board with ventilated airspace?
308.2; Table 308.2
What is a characteristic of a Direct Solar System?
Chapter 2 – Definitions
Where equipment, other than piping, is located outside a building and within what minimum distance of any building opening, shall such equipment be governed by the occupancy classification of the building?
1103.2
For 1/2-inch nominal OD Polyethylene plastic tubing (SDR 7) at a length of 100 feet, what is the capacity in cubic feet per hour (cfh) for natural gas with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(23)
Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances is a:
Chapter 2 – Definitions
Hazardous exhaust systems are required if a vapor, gas, fume, mist, or dust with a health-hazard rating of 4 is present at what concentration?
509.2
What is the capacity in thousands of Btu/h for 1/2-inch nominal copper tubing (K & L) at 500 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(29)
The use of plastic solar collector covers serving as roof covering is limited to those approved light-transmitting plastics meeting the requirements for plastic roof panels in which specific section of the International Building Code?
1402.8.1.3 Exception, 13
For Refrigerant Pressure Vessels, evaporators are excluded if each separate section does not exceed what maximum refrigerant-containing volume?
Chapter 2 – Definitions
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter larger than 16 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
For pneumatic leak tests where the maximum working pressure is at or above 125 psig (862 kPa gauge), the test pressure shall be not less than what minimum percentage of the maximum working pressure?
705.3.2
In naturally ventilated hydrogen-generating locations, equipment and appliances having an ignition source shall be located such that the source of ignition is not within how many inches of the ceiling?
304.5.1
What is the capacity in cfh for 1 1/4-inch nominal Schedule 40 metallic pipe at 100 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(3)
For a sauna heater, the heat-sensing element of the room temperature thermostat must be located within what maximum distance of the ceiling?
615.6
What is required to be installed where space for a domestic clothes dryer is provided but the dryer is not installed at the time of occupancy?
504.9.6
Any material not defined as noncombustible is defined as:
Chapter 2 – Definitions
If the code official determines a mechanical system has become hazardous to life, health, or property, what must be specified in the written order to remove or restore the system?
114.6.1
A burner designed to supply gaseous fuel to an appliance originally designed to utilize another fuel is known as what?
Chapter 2 – Definitions