2023 Commercial Electrical Inspector (Untimed)

80 Questions

3.5 Hours

1 / 80

1. If a feeder supplies 55 dwelling units in a multifamily dwelling, what demand factor percentage applies using the optional method (Table 220.84(B))?

2 / 80

2. A location adjacent to a Zone 20 location may be classified as Zone 21, unless communication from the Zone 20 location is minimized by adequate positive pressure ventilation from a source of clean air and what else?

3 / 80

3. What must activate the damper operation of an HVAC system serving other occupancies that also serves the information technology equipment room?

4 / 80

4. Cables with entirely nonmetallic sheaths entering the top of a surface-mounted enclosure through nonflexible raceways (Exception No. 1) must ensure the raceway length is not more than what maximum distance?

5 / 80

5. What is the minimum required rating for the service disconnecting means supplying a one-family dwelling?

6 / 80

6. Equipment having an open-circuit voltage exceeding 300 Volts shall not be installed in dwelling occupancies unless designed so that there will be no exposed live parts during which three actions?

7 / 80

7. Which of the following is NOT a permitted wiring method in ducts specifically fabricated to transport environmental air?

8 / 80

8. Where buildings exceed three stories or 15 m (50 ft) in height, overhead lines shall be arranged, where practicable, to leave a clear space (or zone) of at least what minimum width?

9 / 80

9. Free nonheating leads of cables must be installed from the junction box to a location within the ceiling using which wiring methods?

10 / 80

10. The size of the DC system bonding jumper shall not be smaller than what conductor?

11 / 80

11. ENT shall not be used in theaters and similar locations, except as provided in which two specific sections?

12 / 80

12. Horizontal runs of LFMC supported by openings through framing members shall be permitted if the support intervals do not exceed what maximum distance?

13 / 80

13. For PVC conduit installed in wet locations, what is required for all supports, bolts, straps, screws, and so forth?

14 / 80

14. Where service heads or goosenecks cannot be located above the point of attachment of the service conductors, the service head or gooseneck location shall be permitted not farther than what maximum distance from the point of attachment?

15 / 80

15. What is the ampacity for 4/0 AWG copper single-insulated conductor in free air, Type RHH, installed in a 30°C ambient temperature?

16 / 80

16. What is the minimum wire-bending space and minimum gutter space required in switchboards, switchgear, and panelboards?

17 / 80

17. If trade size designators are used, when is it required to use dimensions instead of the trade size?

18 / 80

18. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors unless what is installed?

19 / 80

19. Which piece of information is explicitly required to be marked on the surface of Type SHD-GC portable power feeder cables?

20 / 80

20. PVC conduit is generally prohibited in theaters and similar locations, except as provided in which two specific sections?

21 / 80

21. The first 60 amperes of the load for a farm building (other than the dwelling unit) shall be calculated at what percentage, if it is the largest of the simultaneous loads or 125 percent of the largest motor?

22 / 80

22. What is the minimum conductor size permitted within a listed component or as part of the wiring of a listed assembly?

23 / 80

23. Service raceways exposed to the weather must be arranged to drain and must be listed or approved for use in which type of location?

24 / 80

24. Thermal protection is not required for a recessed incandescent luminaire if it is identified for use and installed in what specific material?

25 / 80

25. What is the minimum required clearance for overhead spans of open conductors above the track rails of railroads?

26 / 80

26. For indoor electrical equipment, which enclosure type provides protection against falling dirt and incidental contact but does NOT provide protection against falling liquids?

27 / 80

27. Other outlets not specifically covered in 220.14(A) through (J) shall be calculated based on how many volt-amperes per outlet?

28 / 80

28. Retrofit trip units must be listed for use with what specific component?

29 / 80

29. Each length of IMC shall be clearly and durably marked at least every what maximum distance with the letters IMC?

30 / 80

30. Insulated conductors or cables exposed to direct rays of the sun must be listed as being what?

31 / 80

31. What is the maximum interval permitted for securing LFNC when installed in lengths exceeding 1.8 m (6 ft)?

32 / 80

32. What restriction applies to supporting, terminating, or connecting metal raceways by welding?

33 / 80

33. For a new restaurant that is NOT all-electric and has a total connected load of 900 kVA, what is the required calculated load (kVA)?

34 / 80

34. For connections within an accessible ceiling to luminaire(s) or other equipment, what is the maximum length of unsecured ENT permitted from the last point where the raceway is securely fastened?

35 / 80

35. What must corrosion protection maintain for the ferromagnetic envelope in skin-effect heating systems?

36 / 80

36. In urban water-pipe areas, if the grounded conductor has at least four water-pipe connections, the metal interconnection shall be permitted to be made to the secondary neutral conductor with omission of what direct connection?

37 / 80

37. What is the maximum weight a ceiling-suspended (paddle) fan shall be permitted to weigh when supported solely by an outlet box or outlet box system?

38 / 80

38. What demand factor percentage applies when calculating the load for 10 shore power receptacles in a marina (Table 220.120)?

39 / 80

39. Flexible cords are permitted in show windows and showcases as supply cords for portable luminaires and other displayed merchandise, or for which other wiring use?

40 / 80

40. Securing or supporting of LFNC is NOT required when installed in lengths not exceeding what distance at terminals where flexibility is required?

41 / 80

41. For tap conductors not over 3 m (10 ft) long, the ampacity of the tap conductors shall be not less than the rating of the equipment containing an overcurrent device(s) supplied by the tap conductors OR not less than the rating of what device?

42 / 80

42. Which parts of Article 706 must flow battery Energy Storage Systems (ESS) also meet, in addition to Part V requirements?

43 / 80

43. An SPD shall not be installed on ungrounded systems unless listed specifically for use on which systems?

44 / 80

44. What function must an SPD provide to show that it is operational?

45 / 80

45. A box or conduit body is NOT required for splices and taps in direct-buried conductors and cables, as permitted by which section?

46 / 80

46. If a Power Source output connection is made to a feeder at a location other than the opposite end from the primary source overcurrent device, what is one method to protect the portion of the feeder on the load side of the connection?

47 / 80

47. In tunnel installations over 1000 volts, how must electrical controls for the ventilation system be arranged?

48 / 80

48. Cell line conductors must be joined by which of the following connection methods?

49 / 80

49. Splicing of a wire-type grounding electrode conductor is permitted only by irreversible compression-type connectors listed as grounding and bonding equipment or by what other method?

50 / 80

50. Where the generator disconnecting means is located within the generator behind a hinged cover, door, or enclosure panel, what must be provided?

51 / 80

51. A system or circuit conductor that is intentionally grounded is defined as the:

52 / 80

52. In prewiring for air-conditioning installation in a recreational vehicle, the prewire circuit shall terminate in a junction box with a blank cover or other listed enclosure, and the ampere rating marked on the safety label shall not exceed what percentage of the circuit rating?

53 / 80

53. The disconnecting means for the normal power source of a fire pump shall not be located within the same enclosure, panelboard, or switchboard that supplies what type of loads?

54 / 80

54. Solar PV systems with PV system DC circuits operating at 80 volts DC or greater between any two conductors shall be protected by what listed device?

55 / 80

55. Underground cables and conductors installed under a building must be installed in what wiring method?

56 / 80

56. Dispensing devices for LP-Gas must be located at least what minimum distance from any dispensing device for Class I liquids, unless certain conditions regarding low release volume are met?

57 / 80

57. Flexible cords and cables used to connect moving parts of Power Production Equipment must be listed and identified as DG cable or what other specific requirement?

58 / 80

58. How often must exposed cable or raceway systems be permanently marked to identify them as a component of an Emergency System circuit?

59 / 80

59. When unused metallic plugs or plates are used to close unused openings in nonmetallic enclosures, what minimum distance must they be recessed from the outer surface of the enclosure?

60 / 80

60. For over 1000Volts installations, parts that must be removed for lamp replacement shall be hinged or what other condition applies?

61 / 80

61. EMT shall not be used for the support of luminaires or other equipment, except for what?

62 / 80

62. Where resistance-type boilers are rated 50(kW) or more, the conductors supplying the supplementary overcurrent protective devices can be sized at 100 percent of the nameplate rating if what type of device controls the cyclic operation?

63 / 80

63. Portable power feeder cables rated from 2000Volts to 5000Volts shall not be bent to a radius less than how many times the overall cable outer diameter?

64 / 80

64. A separate leakage test device shall not be required where the shore power equipment includes which features?

65 / 80

65. Equipment intended to interrupt current at fault levels must have an interrupting rating at nominal circuit voltage at least equal to what?

66 / 80

66. Horizontal runs of LFNC supported by openings through framing members shall be permitted if the support intervals do not exceed what maximum distance?

67 / 80

67. If equipment and conductors are connected to more than one electrical source in a fuel cell system installation, what protection is required?

68 / 80

68. When installing Class 2 and Class 3 Circuit conductors in enclosures with electric light or power circuits, what minimum separation distance must be maintained if voltage is not 150 volts or less to ground?

69 / 80

69. When using a common grounding electrode conductor for multiple separately derived systems, how must tap connections be made to the common GEC?

70 / 80

70. Open service conductors must be attached to fittings identified for use with service conductors or to noncombustible, nonabsorbent insulators that are securely attached to what?

71 / 80

71. Barber shops and beauty parlors are considered similar to what occupancy type for lighting load calculations in Table 220.42(A)?

72 / 80

72. For fixed multioutlet assemblies in commercial occupancies where appliances are unlikely to be used simultaneously, each 1.5 m (5 ft) or fraction thereof shall be considered as one outlet of not less than how many volt-amperes?

73 / 80

73. What is the minimum wire-bending space required in an enclosure for a single 1/0 AWG wire per terminal, measured in a straight line from the end of the lug?

74 / 80

74. What is the required color identification for Isolated Conductor No. 2 in an isolated power circuit?

75 / 80

75. When applying demand factors from Table 220.45, they shall apply to the total branch-circuit load calculated for general illumination but shall NOT be applied when determining what?

76 / 80

76. Which of the following occupancies requires a surge-protective device (SPD) to be provided for all services supplying it?

77 / 80

77. For a dc feeder system operating at 120 volts, how must a positive ungrounded conductor of 4 AWG be identified at all termination, connection, and splice points?

78 / 80

78. If multiple grounding connections result in objectionable current, and the effective ground-fault current path requirements are met, which remedial action is permitted?

79 / 80

79. The equipment grounding conductor of the supply circuit shall be permitted to serve as the bonding means if the metal frames or parts are likely to become energized in the event of what?

80 / 80

80. For indoor electrical equipment, which enclosure type is suitable for protection against hosedown and splashing water, temporary submersion, and falling dirt, but NOT against corrosive agents?