An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the state or jurisdiction is a:
Chapter 2 – Definitions
For existing buildings in flood hazard areas, the code official must determine if proposed work for reconstruction or repair constitutes:
104.3.1
Which classification of clothes dryer is used in business with direct intercourse of the function with the public, and is not designed for use in individual family living environment?
Chapter 2 – Definitions
What is the minimum net airflow required for a Double Island Canopy Hood (per side) used for extra-heavy-duty cooking appliances?
507.2.10.1
Soldered joints are limited to refrigeration systems using Group A1 refrigerant and having a pressure of less than or equal to what maximum pressure?
1108.3.3
Listed self-contained systems using Group A3 refrigerant are exempt from restrictions if they contain a maximum of how many pounds?
1104.3.2 Exception 2
The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be not less than how many inches?
306.5
Where a fire alarm system is required, the actuation of a duct smoke detector must activate what type of signal at a constantly attended location?
606.4.1
Which ASSE standard is listed as applicable for Copper and copper alloy fittings in Table 1202.5?
Table 1202.5
For enclosed structures involving organic coating processes using Class I liquids, what is the minimum ventilation rate required per square foot of solid floor area?
502.12
In commercial tenant spaces, the use of corridors for conveying return air is permitted if the tenant space area is not more than what size?
601.2 Exception
Under what static vent pressure state does a Natural Draft System remove flue or vent gases?
Chapter 2 – Definitions
A listed and labeled chimney composed of factory-made components, assembled in the field in accordance with manufacturer’s instructions and the conditions of the listing, is a:
Chapter 2 – Definitions
The makeup air supplied to a commercial kitchen must be conditioned such that the temperature difference between the makeup air and the design setpoint temperature in the kitchen space is not greater than what amount?
508.1.1
Threads used for threaded joints in hydronic piping systems must conform to which ASME standard?
1203.3.5
Exhaust system discharge for dust, stock, and refuse conveying systems is permitted to be recirculated, provided the solid particulate has been removed at a minimum efficiency of 99.9 percent at what particle size?
510.1.3
The cutting, notching, and boring of holes in structural steel framing members shall be as prescribed by the:
302.5
Exhaust outlets for grease ducts that terminate above the roof must have the discharge opening located not less than how many inches above the roof surface?
506.3.13.1
An airflow differential pressure control on a pollution-control unit must activate a visual alarm located where when the airflow is reduced below the design velocity?
506.5.2
When connecting an appliance to an existing chimney or vent, the flue gas passageway must be free from obstructions, combustible deposits, and must be cleaned if previously used for venting what type of appliance?
801.18.2, 12
What is required for a Type I Hood, which collects and removes grease vapors and smoke?
Chapter 2 – Definitions
For electrical equipment and appliances, the required label information must include the electrical rating in volts, amperes, and motor phase, and what other essential rating?
301.9
What is strictly prohibited from penetrating the grease duct walls?
506.3.3
Where must circulating air for fuel-burning, forced-air-type, warm-air furnaces be conducted into the blower housing from outside the furnace enclosure?
918.4
What is the minimum clearance required to combustibles for hazardous exhaust ducts conveying flammable vapors?
Table 509.8.2
If motor vehicles are capable of passing under an appliance in a public garage, the appliance must be installed at least 1 foot (305 mm) higher than what other measurement?
304.6
The height requirement for solar thermal equipment exposed to vehicular traffic does NOT apply if what condition is met?
1402.6 Exception, 10
Official records required by the code official shall be retained for not less than 5 years or for how long?
104.7
What is the minimum dimension allowed for combustion air openings used to connect indoor spaces?
304.5.3.1
The LFL for refrigerants is determined in accordance with specific test conditions established by which standard?
Chapter 2 – Definitions
If the proposed work conforms to code requirements and all fees have been paid, who shall issue the permit to the applicant?
105.5
For a chimney venting system serving a single appliance with a draft hood, the effective area of the chimney flue shall be not less than the area of the draft hood outlet nor greater than what multiple of the draft hood outlet area?
503.5.5
Where is Return Air removed from?
Chapter 2 – Definitions
Semirigid metallic tubing used to connect an appliance to the piping system must be located entirely in the same room as the appliance and shall not exceed what maximum length?
411.1
If work authorized by a permit is suspended or abandoned for a period of 180 days, the permit shall:
105.5.3
In indoor locations intended for hydrogen-generating or refueling operations using natural ventilation, what is the maximum floor area permitted?
304.5.1
Who is authorized to require design submittals for reports not complying with Section 104.2.3.6.1 to be prepared by, and bear the stamp of, a registered design professional?
104.2.3.6.2
Rodentproofing construction must be in accordance with the International Building Code for spaces where persons live, sleep, or work, or where what is stored, prepared, processed, served, or sold?
301.17
An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, is defined as what?
Chapter 2 – Definitions
Piping and components subject to manual gravity draining in drain-back systems must maintain a horizontal slope in the direction of flow of not less than what minimum value?
1402.4.1, 7
A Bathroom is defined as a room containing a water closet and which other fixture?
Chapter 2 – Definitions
A Protective Assembly (Reduced Clearance) that is attached directly to a combustible assembly shall not be considered as part of what?
Chapter 2 – Definitions
A device placed in a gas line between the service pressure regulator and the appliance for controlling, maintaining or reducing the pressure in that portion of the piping system downstream of the device is a:
Chapter 2 – Definitions
The content of the technical opinion and report shall analyze the properties of the design, operation or use of the building to identify and propose:
104.2.2.3
Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through what two building elements?
509.5.7
What is the minimum level working space required in front of the control side to service an appliance?
306.1
For the reduction of required clearances to combustible materials, the allowable reduction must be based on one of the methods specified in Table 308.2 or shall utilize a reduced clearance protective assembly listed and labeled in accordance with which standard?
308.2
Certification obtained by the manufacturer indicating that the function and performance characteristics of a product have been determined by testing and ongoing surveillance by an approved third-party certification agency is defined as:
Chapter 2 – Definitions
Flue lining systems for use with residential-type and low-heat appliances shall be limited to clay flue lining complying with ASTM C315 or equivalent, listed and labeled chimney lining systems complying with UL 1777, and what other approved materials?
801.16.1, 10
Where work does not pass an initial test or inspection, after necessary corrections are made, the work shall be resubmitted to the code official for:
111.3.3
A Ceiling Radiation Damper is a listed device installed in a ceiling membrane of a fire-resistance-rated assembly to automatically limit what?
Chapter 2 – Definitions
Which standard applies to Copper or copper-alloy tubing (Type K, L or M) used for fuel oil piping?
1302.3
Any combination of outdoor and transfer air intended to replace exhaust air and exfiltration is defined as:
Chapter 2 – Definitions
What is the maximum design temperature permitted for systems utilizing underground plastic duct and fittings?
603.8.3
For a Type B double-wall vent serving two or more Category I appliances with Type B double-wall connectors (Table 504.3(1)), if the vent height (H) is 15 feet and the connector rise (R) is 6 feet (the max rise for R=6 ft row), what is the maximum combined input rating (NAT+NAT) for a 9-inch common vent diameter?
504.3; Table 504.3(1)
What is the minimum clearance required above an appliance where the original required clearance was 9 inches, and the protection is 1/2-inch insulation board with ventilated airspace?
308.2; Table 308.2
For smoke control systems, belt-driven fans must have what multiple of the number of belts required for the design duty, with a minimum of two belts?
512.10.5
Using the Standard Method (304.5.1), what is the minimum required volume of indoor air per 1,000 Btu/h of the appliance input rating?
304.5.1
An appliance shall not be connected to a flue serving a factory-built fireplace unless the appliance is specifically listed for such installation.
501.7.2
A valve of the plug and barrel type designed for use with gas, and equipped with a lever handle for manual operation and a dial to indicate the percentage of opening is a:
Chapter 2 – Definitions
Where must the discharge line of a fuel oil system relief valve connect?
1307.5
What is the minimum duration required for the hydrostatic test on hydronic piping systems?
1208.1
A listed smoke damper designed to resist the passage of smoke must be provided at each point a duct or air transfer opening penetrates which two types of building assemblies?
607.5.4
Where Class I liquids are pumped, used, or transferred in bulk plants or terminals, where shall adequate openings for natural ventilation in outside walls be provided?
502.9.5.5.1
Preparation of pipe ends requires that pipe be cut square and free from burrs and obstructions, and what two other actions?
1203.2
What is the minimum diameter required for the overflow installed at the top of an open-type expansion tank?
1009.3
Chimneys for residential-type or low-heat appliances must extend not less than 3 feet above the highest point where they pass through a roof and not less than what minimum height higher than any portion of a building within a horizontal distance of 10 feet?
503.5.4
The code official is authorized to establish a:
108.6
What type of fluid must be used as the heat transfer fluid in single-wall heat exchangers?
1402.8.4.2, 17
For service access, what is the minimum required depth and width of the level working space provided in front of the control side of an appliance?
306.1
The amount of return air taken from any room or space shall not be greater than what value?
601.5
What is the purpose of providing Excess Air for the combustion of a fuel?
Chapter 2 – Definitions
The cutting and notching of holes in cold-formed steel structural framing members shall be in accordance with which standard?
302.5
Where plastic vents are specified by the appliance manufacturer for Category IV appliances, are they required to be listed and labeled?
502.1
If horizontal grease ducts exceed 75 feet (22 860 mm) in length, what is the minimum required slope?
506.3.7
If factory inspections have been performed on an installation, the system shall have an identifying label permanently affixed indicating:
111.2.5.2
What is the minimum thickness required for a galvanized steel chimney connector larger than 16 inches in diameter serving a low-heat appliance, according to Table 803.9(1)?
Table 803.9(1), 23
For exhaust openings that terminate outdoors, the openings in screens, louvers, and grilles must be sized not less than what minimum dimension?
501.3.2
What type of metallic pipe is strictly prohibited from use in piping systems?
403.3.1
What is the LFL (Lower Flammability Limit) for R-1234yf in parts per million (ppm)?
Table 1103.1
If a commercial electric dishwasher incorporates a self-contained condensing system listed and labeled in accordance with UL 921, is a hood required?
507.1 Exception 2
What must Type L vents terminate with?
802.4, 16
The function of the code compliance agency is the implementation, administration, and enforcement of the provisions of this code, and the official in charge shall be known as the:
103.1
Concealed piping is prohibited from being located in solid partitions and solid walls unless installed in:
404.4
Where must the permit or a copy be kept until the completion of the project?
105.4.7
For an appliance connected to a chimney flue serving a fireplace, what must be provided for access to the flue?
801.10.1, 5
Which of the following framing cavities or spaces is NOT permitted to be utilized as an air plenum?
602.2.1
Where terms are not defined in this code, they shall have meanings ascribed to them as defined in which other referenced code?
201.3
The pressure of the weight of air and water vapor on the surface of the earth, approximately 14.7 psi (101 kPa absolute) at sea level, is defined as:
Chapter 2 – Definitions
High-density polyethylene (HDPE) pipe used for ground-source heat pump ground-loop systems must conform to which specific ASTM standard?
Table 1210.4
An approved agency that tests mechanical equipment and appliances must maintain a record of all tests performed to verify compliance with what?
301.8.1
Where appliances requiring service are installed on a sloped roof (3 units vertical in 12 units horizontal or greater) and the roof edge is more than 30 inches above grade, how large must the level platform be on the service side?
306.5.1
A medium-heat appliance has products of combustion temperatures at the point of entrance to the flue that are more than 1,000°F (538°C) but not greater than:
Chapter 2 – Definitions
When does a permit become valid?
108.1
What is the capacity in thousands of Btu per hour for CSST Flow Designation 31 at 25 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(33)
Upon activation, smoke detectors in air distribution systems shall shut down all operational capabilities of the system in accordance with what criteria?
606.4
A separate grease duct system is NOT required for each Type I hood if all interconnected hoods are located in the same story, the same or adjoining rooms, do not penetrate fire-resistance-rated assemblies, and do not serve what type of appliances?
506.3.5
If granted, an extension of time to commence work under an unexpired permit shall not exceed how many days?
105.5.4
How is an Unvented Alcohol Fuel-Burning Decorative Appliance intended to be secured?
Chapter 2 – Definitions
Condensate piping shall maintain a minimum slope in the direction of discharge of not less than what unit vertical in 12 units horizontal?
307.2
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 9 inches, and the protection is 3 1/2-inch-thick masonry wall with ventilated airspace?
308.2; Table 308.2
Unvented alcohol fuel-burning decorative appliances must be listed and labeled in accordance with which UL standard?
929.1
Hearth extensions of approved factory-built fireplaces must be installed in accordance with the listing and must comply with which UL standard?
903.2
Joints and piping on the positive pressure side of a power exhauster must be listed for positive pressure applications as specified by what documentation?
801.14, 8
Noncanopy-type hoods shall be located not greater than how many feet above the cooking surface?
507.1.6.2
Underground fuel oil piping systems must be listed and labeled in accordance with which UL standard?
1302.9
Clothes dryer exhaust ducts must terminate not less than how many feet in any direction from openings into buildings, where the manufacturer’s instructions do not specify a location?
504.4.1
Factory-built chimneys for medium-heat appliances producing flue gases having a temperature above 1,000°F must be listed and labeled in accordance with which UL standard?
506.3
Machinery rooms larger than what minimum area must have not less than two exits or exit access doorways?
1105.9
What is the exact amount of air required to supply oxygen for complete combustion of a given quantity of a specific fuel?
Chapter 2 – Definitions
Combustion air ducts that are not provided with dampers and that pass through rated construction must be enclosed in a shaft in accordance with which code?
701.2
Where all combustion air is provided by a mechanical air supply system, what is the minimum required supply rate per 1,000 Btu/h of total appliance input rating?
304.9
A Toilet Room is a room containing a water closet and sometimes a lavatory, but not what other fixture?
Chapter 2 – Definitions
For detached one- and two-family dwellings not more than three stories above grade plane, compliance shall be with the code or which other regulatory document?
101.2 Exception
Media-type air filters used in non-dwelling units must comply with which UL standard?
605.2
In Group I-1 and I-2 occupancies, range hoods over domestic cooking equipment must have a minimum airflow rate of how many CFM?
505.7, 505.8
What is the minimum required thickness (in inches) for a steel vent connector serving a medium-heat appliance with a diameter of up to 14 inches?
503.10.2.5; Table 503.10.2.5
Foam plastic used as interior wall or ceiling finish or interior trim in plenums is permitted to exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less if it is separated from the airflow by corrosion-resistant steel having a base metal thickness of not less than what dimension?
602.3.7 Exception 2
A Portable Fuel Cell Appliance utilizes what connection type to a grid-isolated load?
Chapter 2 – Definitions
A machinery room is not required for listed equipment containing not more than what maximum weight of refrigerant, regardless of the safety classification?
1104.2 Exception 1
What is the maximum control voltage permitted for the electrical control system of a boiler?
1006.8
Cleanouts in horizontal grease ducts must have opening dimensions of not less than what minimum size?
506.3.9
If a new permit is obtained after a permit has expired due to suspension or abandonment, and the work recommences, the fee shall be one-half the amount required for a new permit provided the suspension or abandonment has not exceeded how long?
105.5.3
What type of concentration is the Occupational Exposure Limit (OEL) based on?
Chapter 2 – Definitions
Requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas are regulated by the:
101.2.6
Where gas piping systems for other than dry gas conditions have condensate, a drip shall be provided with ready access to permit:
408.3
Corridors and other common areas within the conditioned space of Group R-2, R-3, and R-4 occupancies shall be provided with outdoor air at what minimum rate per square foot of floor area?
403.3.2.2
What is the maximum water temperature allowed for a hot water supply boiler at or near the boiler outlet?
Chapter 2 – Definitions
Rigid metallic pipe and fittings, semirigid metallic tubing and fittings or a listed and labeled device that connects an appliance to the gas piping system is a(an):
Chapter 2 – Definitions
What is a characteristic of a Direct Solar System?
Chapter 2 – Definitions
Steam piping must be installed to drain to the boiler or what other system component?
1206.8
Pollution-control units must be listed and labeled in accordance with which standard?
506.5.2
In addition to meeting minimum CFM requirements, the exhaust rate for xenon motion picture projectors must be such that the exterior temperature of the lamp housing does not exceed what temperature?
502.11.2
What is the minimum exhaust distance required for air discharged from mechanical ventilation systems from a property line or openings into buildings?
1105.6.1
Solar thermal system components containing pressurized fluids must be protected against pressures and temperatures exceeding design limitations using what devices?
1402.3, 5
What primary contaminants does a Type II Hood collect and remove?
Chapter 2 – Definitions
Where rooms are ventilated through an adjoining room, the minimum openable area to the outdoors shall be based on what total area?
402.3
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 18 inches, and the protection is 3 1/2-inch-thick masonry wall with ventilated airspace?
308.2; Table 308.2
What additional device must be installed in the room with a manually fired appliance or fireplace when utilizing a mechanical draft system?
804.3.8, 36
Who is authorized to establish a refund policy for fees?
108.6
Supply and exhaust ducts to the machinery room must be covered with corrosion-resistant screen of not less than what mesh size?
1105.6.2
Apparatus, material, and labor required for testing a mechanical system shall be furnished by whom?
111.3.2
A masonry chimney flue cleanout opening must have a minimum height of 6 inches and its upper edge must be located not less than what vertical distance below the lowest chimney inlet opening?
501.15.3
Who must obtain the required permit before beginning work regulated by this code?
105.1
External duct insulation, except spray polyurethane foam, must be legibly printed or identified at intervals not greater than what maximum distance?
604.7
Air intake openings that terminate outdoors must be protected with corrosion-resistant screens, louvers, or what other devices?
401.5
The code official shall perform all of the following duties EXCEPT:
104.3
Where any cooking appliance under a single hood requires a Type I hood, what type of hood must be installed?
507.1
What is the minimum required clearance from the top of a high-pressure steam boiler with steam generating capacity not exceeding 5,000 pounds per hour to the ceiling?
Table 1004.3.1
Appliances and supports exposed to wind must be designed and installed to resist wind pressures in accordance with which code?
301.1
What is the minimum internal area (in square inches) required for a clay-tile-lined exterior masonry chimney flue for a 5-inch diameter Type B double-wall connector when used for single appliance venting?
504.2; Table 504.2(3)
An Induced-draft venting system uses a fan or other mechanical means to cause the removal of flue or vent gases under what static vent pressure condition?
Chapter 2 – Definitions
A Push-Fit Joint is a type of mechanical joint consisting of elastomeric seals and what other component?
Chapter 2 – Definitions
If the air infiltration rate of a structure is known to be less than 0.40 ACH, which method must be used to determine the required volume of indoor air for combustion?
304.5
The termination of concealed condensate piping must be marked to indicate connection to which two types of drains?
307.2
CSST gas piping systems (without an arc-resistant jacket) must be electrically continuous and bonded to the electrical service grounding electrode system or, where provided, which other system?
310.2
The maximum amount of gas input required per unit of time, usually expressed in cubic feet per hour, or Btu/h, is defined as:
Chapter 2 – Definitions
Domestic booster fans are prohibited from being installed in dryer exhaust systems.
614.6
What identification must each length of pipe and tubing and each pipe fitting utilized in a mechanical system bear?
301.3
Flexible air connectors are prohibited from passing through which building elements?
603.6.2.2
Type L vents and pellet vents shall be tested in accordance with which UL standard?
802.1, 15
What is the capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 500 feet in length, operating at 3.0 psi inlet pressure with a 2.0 psi pressure drop?
402.4; Table 402.4(6)
If a replacement refrigerant is classified into a different safety group, what additional requirement must the system comply with, besides meeting new installation requirements?
1101.7
Pipe-joint compound or tape must be applied only on which threads of a threaded fuel oil pipe joint?
1303.3.3
A through-the-wall direct-vent terminal serves an appliance rated at 100,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
Who is authorized to approve an alternative material, design, or method of construction?
104.2.3.1
When calculating reduced clearances using Table 308.4.2, reduced clearances shall not be derived by what process below the range of the table?
308.4.2
A natural gas, manufactured gas, liquefied petroleum gas or mixtures of these gases is defined as:
Chapter 2 – Definitions
In a dwelling unit, if an appliance is installed in a closet, the unobstructed passageway must measure not less than how many inches wide?
306.2 Exception
What is the Refrigerant Safety Group Classification for R-290 (propane)?
Table 1103.1
Air necessary for complete combustion of a fuel, including theoretical air and excess air, is defined as:
Chapter 2 – Definitions
Where vents penetrate outside walls, the annular spaces around such penetrations must be permanently sealed using approved materials to prevent entry of combustion products into the building.
503.16
The pipe that connects an appliance to a chimney or vent is the:
Chapter 2 – Definitions
If a timer is provided to control the main burner operation of a sauna heater, what is the maximum operating time allowed?
914.4.1
Controls and safety devices for boilers with fuel input ratings of less than 12,500,000 Btu/hr must meet the requirements of which standard?
1004.1
Screws, rivets and other fasteners are prohibited from penetrating the inner wall of double-wall gas vents, except at the transition from an appliance draft hood outlet, flue collar or what other component?
503.6.14
A Water Heater is any heating appliance or equipment that heats potable water and supplies such water to what system?
Chapter 2 – Definitions
The fuel input rate for an appliance shall not be increased or decreased beyond the limit rating for what specific environmental factor?
301.12
When is cross-connection protection NOT required for potable water supplies to solar systems?
1401.2 Exception, 2
Which of the following conditions permits the use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum?
601.2.1
The portion of an appliance within which combustion occurs is the:
Chapter 2 – Definitions
What is the maximum water volume allowed for a compressed gas container or cylinder that is exempt from the requirement to be used in an upright position?
704.2
Who must sign the application for a permit?
105.3
Air that is conveyed to or from occupied areas through ducts that are NOT part of the heating or air-conditioning system is defined as what?
Chapter 2 – Definitions
An appliance shall not be connected to a flue serving a factory-built fireplace unless what condition is met?
801.10.2, 5
If outdoor air intake openings front on a street or public way, the 10-foot horizontal distance shall be measured from where?
401.4
In a repair garage for liquid or odorized gas fueled vehicles, mechanical exhaust systems that are electrically interlocked with the lighting circuit are allowed as an exception to what general requirement?
502.16.2.2 Exception 2
The approved agency must periodically perform an in-plant inspection of the appliances to be labeled to verify that the labeled appliances are representative of the appliances that were:
301.4.2
Drain and fill valves must be labeled with a description and warning that identifies the fluid in that loop as “Potable Water,” “Food-Grade Fluid,” “Nonfood-Grade Fluid” or what fourth category?
1404.3, 22
What is the maximum diameter allowed for a chimney connector for a domestic-type appliance that passes through a wall constructed of combustible material using one of the methods in Table 803.10.4?
803.10.4, 26
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 9 inches, and the protection is 1-inch glass fiber or mineral wool batts sandwiched between two sheets of 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
For an exterior masonry chimney serving a single space-heating appliance in a climate zone with a Local 99% Winter Design Temperature of 27 to 36°F, with a vent height of 10 feet and an internal area of 38 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.2; Table 504.2(6)
Oil-fired floor furnaces must be tested in accordance with which UL standard?
910.1
Factory-built cooling towers must be listed in accordance with UL 1995 or which other standard?
908.1
Where different portions of this code specify different materials or methods of construction for a specific case, which requirement shall govern?
102.1
Flexible air ducts shall not be limited in length, but flexible air connectors shall be limited in length to what maximum dimension?
603.6.1.1, 603.6.2.1
What is an assembly consisting of a hearth and fire chamber of noncombustible material, provided with a chimney, for use with solid fuels?
Chapter 2 – Definitions
Which piece of information is required to appear on a permanent factory-applied nameplate affixed to an appliance?
301.5
An enclosed portion of the building structure that is designed to allow air movement and serve as part of an air distribution system is defined as a Plenum, provided it is not what?
Chapter 2 – Definitions
When a violation continues each day after due notice has been served, how is that classified?
113.4
Louvers that protect exhaust openings in structures located in hurricane-prone regions must comply with which standard?
501.3.2
In an Indirect Refrigeration System classified as a Closed System, the secondary fluid is circulated how?
Chapter 2 – Definitions
If the depth of an underfloor passageway or service space exceeds 12 inches (305 mm) below adjoining grade, the walls of the passageway must be lined with what material?
306.4
Ducts shall not be attached to wall furnaces unless what condition is met?
608.5
What is the equivalent length reduction for a 4-inch radius mitered 90-degree elbow in a domestic dryer exhaust duct?
Table 504.9.4.1
The code official is authorized to appoint a deputy code official, technical officers, and inspectors with the concurrence of whom?
103.3
If appliances are served by a mechanical air supply system, what must be provided to prevent main burner operation when the mechanical air supply system is not operating?
304.9.2
According to Table 308.4.2, what is the reduced clearance for a horizontal combustible assembly located above the heat source if the required clearance without protection is 36 inches and the protection is galvanized sheet steel (No. 24 gage) spaced 1 inch off the combustible assembly?
Table 308.4.2
What must be provided for water heaters and hot water storage tanks to ensure easy removal?
1002.1
What is the capacity in cubic feet per hour (cfh) for Flow Designation 23 CSST at a length of 100 feet, for natural gas with a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(17)
Which warning statement is required on the fluid safety labeling for drain and fill valves?
1404.3, 22
For exhaust openings that terminate outdoors, the openings in screens, louvers, and grilles must be sized not larger than what maximum dimension?
501.3.2
The code regulates the design, installation, maintenance, and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. What is the fourth regulatory action specified?
101.2
Exhaust hood systems for domestic cooking capable of exhausting in excess of how many CFM must be provided with makeup air?
505.4
Where vents pass through insulated assemblies, an insulation shield must be installed, constructed of steel having a minimum thickness of what gauge (0.0187 inch)?
502.4
Factory-built chimneys for building heating appliances producing flue gases having a temperature not greater than 1,000°F must be listed and labeled in accordance with which UL standard?
506.1
Joints between dissimilar metallic piping materials must be made with a dielectric fitting or what other component conforming to dielectric tests of ASSE 1079?
1108.1.1
What are the two primary components that a Venting System is usually composed of?
Chapter 2 – Definitions
For a nondirect-vent terminal, what is the minimum clearance required below or to the side of an openable window or door opening (Clearance B)?
503.8; Table 503.8
What is the minimum required clearance from the top of a high-pressure steam boiler having heating surface in excess of 1,000 square feet to the ceiling?
Table 1004.3.1
The maximum flame spread index and smoke-developed index requirements for pipe insulation do not apply to which specific building type?
1204.1 Exception
Which of the following is defined as an Ignition Source?
Chapter 2 – Definitions
Grease ducts shall be considered concealed where installed in shafts or covered by coatings or wraps that prevent visual inspection on how many sides?
506.3.2.5
The point of discharge of condensate drains must be located within the same occupancy, tenant space, or dwelling unit as the source of the condensate, except where discharging to what location?
307.2.1.1
The officer or other designated authority charged with the administration and enforcement of this code, or a duly authorized representative, is the:
Chapter 2 – Definitions
A thermostat in which the thermostatic valve travels instantly from the closed to the open position, and vice versa, is a:
Chapter 2 – Definitions
Fire dampers are classified for use in either static systems or dynamic systems, where a dynamic system is one that continues to operate during what event?
Chapter 2 – Definitions
A Type B-W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected.
503.6.3
The code official is authorized to suspend or revoke a notice of approval where it is determined that the building, structure, or premises is in violation of:
107.2
Compressed gas containers and tanks, except for small volume units, shall be used in an upright position where the container axis is inclined as much as what maximum angle from the vertical?
704.2
Stop valves are required on refrigeration systems containing more than how many pounds of refrigerant?
1109.6.1
An alternative material, design, or method of construction must comply with the what of the provisions of this code?
104.2.3.3
If a portion of this code is held to be unconstitutional, what effect does this decision have on the validity of the remaining portions?
101.4
A Smoke Damper is installed to operate automatically, controlled by what system?
Chapter 2 – Definitions
Smoke detectors are generally required for return air systems with a design capacity greater than how many CFM?
606.2.1
Where an additional appliance is to be served by an existing piping system, what must be done if the existing system is determined to be inadequate?
401.4
The code official is authorized to issue a stop work order where work is being performed in a manner contrary to the provisions of this code or in a(an):
114.1
Smoke detectors required in air distribution systems must be listed and labeled for installation in air distribution systems, and duct smoke detectors must comply with which UL standard?
606.1
Where a listing standard for equipment is not specified by this code, the listing shall be based on:
104.2.1
Devices or safeguards required by this code shall be maintained in compliance with which edition of the code?
102.3
What type of joint connection must NOT be used for clothes dryer exhaust ducts?
504.4
A pressure regulator in series with one or more other pressure regulators is a:
Chapter 2 – Definitions
A Dwelling contains not more than how many dwelling units?
Chapter 2 – Definitions
Where appliances are located on more than one floor and served by a common vent, the total available height (H) for each segment shall be measured from the highest draft hood outlet or flue collar entering that segment to which location?
504.3.13
Which of the following is prohibited when taking return air from a crawl space?
601.5
What is the minimum required thickness for protective steel shield plates?
305.5.1
A valve that automatically opens and closes a vent for relieving a vacuum within the hot water supply system, depending on whether the vacuum is above or below a predetermined value, is a:
Chapter 2 – Definitions
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter of 15 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
Cleanout openings in grease ducts are required to be spaced not more than how many feet from changes in direction greater than 45 degrees (0.79 rad)?
506.3.8
Log lighters shall be listed in accordance with which standard?
603.1
Floor-mounted-type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not less than what minimum distance?
620.4
Where leakage or other defects are located during testing, what must be done to the affected portion of the piping system?
406.5.2
For naturally ventilated hydrogen-generating operations, what is the minimum free area required for the two permanent openings per 1,000 cubic feet of garage volume?
304.5.1.1
A boiler not listed by a nationally recognized testing agency is a(an):
Chapter 2 – Definitions
Roof and wall penetrations for solar thermal systems must be flashed and sealed to prevent the entry of water, rodents, and what other pests, in accordance with Section 302?
1402.7.2, 11
Exhaust ducts for domestic clothes dryers shall be supported at intervals not exceeding what maximum distance?
614.9.2
Who shall defend any suit or criminal complaint instituted against an officer or employee acting in the lawful discharge of duties under this code?
104.8.1
A valve installed after the point of delivery to shut off the entire piping system is a:
Chapter 2 – Definitions
To determine compliance with maintenance provisions, who has the authority to require an installation to be reinspected?
102.3
Exposed refrigerant piping installed in open spaces that afford passage shall be not less than what minimum height above the finished floor?
1109.2.1
Exhaust ducts for commercial clothes dryers must have a minimum clearance of what distance to combustible materials?
614.1
A horizontal vent system termination shall terminate not less than how many feet below, horizontally from, or 1 foot above any door, window, or gravity air inlet into the building?
804.3.4, 33
Where a structure or premises is occupied and the code official needs to perform an inspection, what must the code official do?
104.4
Catwalks installed to provide required access on elevated structures shall be not less than how many inches wide?
306.5
Internal combustion engines used as gas engine-powered air conditioners shall not be connected to the gas supply piping in what manner?
411.1.5
What type of system converts solar radiation to thermal energy for use in heating or cooling?
Chapter 2 – Definitions
Who is authorized to terminate a permit for temporary uses, equipment or systems and order the same to be discontinued?
110.4
Constituents resulting from the combustion of a fuel with the oxygen of the air, including inert gases, but excluding excess air, are defined as:
Chapter 2 – Definitions
Metallic ducts for air distribution systems (other than those within single dwelling units) must be constructed as specified in which standard?
603.4
For intake openings in residential occupancies, the maximum opening size in louvers, grilles, and screens must be less than or equal to what dimension?
Table 401.5
What must be provided prior to placing a gaseous hydrogen system into operation to displace the air in the piping system?
705.5.2
Who shall perform fire tests conducted to demonstrate equivalent fire safety for an alternative material?
104.2.3.5.1
The board of appeals shall hold office at the pleasure of which entity?
112.1
Which type of space is explicitly excluded from the definition of an Occupiable Space?
Chapter 2 – Definitions
Power exhausters serving automatically fired appliances must be electrically connected to each appliance to prevent appliance operation when the power exhauster is not operating. This is referred to as what type of connection?
804.3.2, 32
In institutional occupancies, the total of all Group A2, B2, A3, and B3 refrigerants shall not exceed what maximum weight in occupied areas or machinery rooms?
1104.2.1
Which of the following is an example of work for which a permit is not required?
105.2
For an unlisted appliance having a draft hood, the ventilated metal thimble used where the single-wall metal pipe passes through a combustible exterior wall must be not less than how much larger in diameter than the metal pipe?
503.7.7
What is required to be provided in each vertical riser of a clothes dryer exhaust duct?
504.3
Alterations resulting in the addition of loads to any truss member, such as HVAC equipment or water heaters, are prohibited without verification that the truss is capable of supporting such additional loading by a:
302.4
Fuel-burning appliances and fireplaces in Group I-2, Condition 2 occupancies must be in accordance with which section?
303.9
The person issued an annual permit must keep a detailed record of alterations made under the permit, and the code official shall have what level of access to such records?
105.1.2
Upblast fans serving Type I hoods and installed in a vertical or horizontal position must be hinged and equipped with a means of restraint to limit what?
506.5.4
Which type of chimney is composed of factory-made components, assembled in the field in accordance with the manufacturer’s instructions?
Chapter 2 – Definitions
Diffusers, registers, and grilles are prohibited in the floor or its upward extension within toilet and bathing rooms, except in which type of space?
603.18.2 Exception
What must failure of the exhaust ventilation system cause in a repair garage for lighter-than-air fuels?
502.16.2.1
What is the maximum percentage of the specified minimum yield strength of the pipe that the hoop stress can reach during a pressure test exceeding 125 psig (862 kPa gauge)?
705.3.3
The purpose of a Transition Fitting, Plastic to Steel, is to provide what type of connection between the two materials?
Chapter 2 – Definitions
For undiluted liquefied petroleum gas systems, the point of delivery shall be considered to be the outlet of which device?
Chapter 2 – Definitions
Equipment and appliances used to exhaust explosive or flammable vapors, fumes, or dusts must bear an identification plate stating what information?
503.3
For a Kitchen (cooking) in a food and beverage service occupancy, what is the required Exhaust Airflow Rate in CFM/ft squared?
Table 403.3.1.1
What type of hood must be installed over extra-heavy-duty cooking appliances?
507.2.2
Stationary engine generator assemblies must meet the requirements of which UL standard?
915.1
Ductless mini-split equipment that produces condensate must be provided with an inline check valve located in the drain line or what other device?
307.2.4.1
Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system must be designed for what type of pressure application?
501.6
In private garages, equipment and appliances having an ignition source must be elevated such that the source of ignition is not less than what distance above the floor?
305.3
For HPM exhaust ducts, what is prohibited from being installed in the exhaust ducts?
502.10.2
In Group I-2, Condition 2 occupancies, gas fireplace appliances and decorative gas appliances are prohibited except where they are direct-vent appliances installed in:
303.3.1
What is the estimated maximum occupant load rate per 1,000 square feet for a Smoking lounge?
Table 403.3.1.1
A metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare is defined as what?
Chapter 2 – Definitions
A hazardous exhaust system is required if a flammable vapor, gas, fume, mist, or dust is present in concentrations exceeding what percentage of the lower flammability limit (LFL)?
509.2
Rough-in inspection shall be made after the roof, framing, fireblocking, and bracing are in place and all ducting and other components to be concealed are complete, and prior to the installation of what?
111.2
What is the capacity in cubic feet per hour (cfh) for CSST Flow Designation 37 at a length of 50 feet, for natural gas with a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(16)
A room or space in which people sleep, which can include permanent provisions for living, eating, and either sanitation or kitchen facilities but not both, is defined as what?
Chapter 2 – Definitions
Except for engineered systems, what is the minimum area required for a chimney or vent serving a single appliance?
801.6
When conveying particulate matter, hazardous exhaust systems must be designed employing which method?
509.5
Where ducts used for cooling are externally insulated, the insulation must be covered with a vapor retarder having a maximum permeance of what value, unless the insulation itself meets this standard?
604.11
If an outdoor opening is rectangular, the size requirements for openings in louvers, grilles, and screens apply to which side?
Table 401.5
What is the minimum thickness required for the concrete encasement of an underground grease duct system?
506.3.10
Under what condition can the minimum required rate of outdoor air be reduced from the rate determined in Section 403.3?
403.2 Exception
In all clearance reduction systems using a ventilated airspace, what is the minimum air gap required between the clearance reduction system and combustible walls and ceilings?
308.2
Which type of vent is listed and labeled for use with wall furnaces?
Chapter 2 – Definitions
When equipment and ductwork for exit enclosure ventilation are located within the exit enclosure, where must the intake air be taken from?
601.3
Where a solar thermal system directly heats potable water for a potable water distribution system, the pipe, fittings, valves and other components must comply with the requirements of which code?
1402.5.2, 9
It shall be unlawful for a person to erect, construct, alter, repair, remove, demolish or utilize an installation in conflict with or in violation of:
113.1
If a roof-mounted pollution-control unit is installed, what is the minimum distance it must be mounted above the roof?
506.5.2
Where natural draft venting systems for Category I appliances include offsets, the offsets shall not exceed what maximum angle from the vertical?
503.6.10.2
In flood hazard areas, exhaust outlets serving structures shall be installed at or above the elevation required for utilities and attendant equipment by which code section?
501.3.1
A burner in which gas, air or both are supplied at pressures exceeding, for gas, the line pressure, and for air, atmospheric pressure, with this added pressure being applied at the burner is a(an):
Chapter 2 – Definitions
When installing a floor furnace, a distance of not less than 18 inches (457 mm) must be provided from two adjoining sides of the floor furnace register to walls for which reason?
609.2
Mechanical draft systems must be listed and labeled in accordance with which UL standard?
804.3, 32
What is the minimum net airflow required for a Wall-mounted Canopy Hood used for medium-duty cooking appliances?
507.2.10.3
What is the function of a Flame Safeguard?
Chapter 2 – Definitions
Within dwelling units, unobstructed stud and joist spaces are permitted to convey combustion air, provided that not more than how many required fireblocks are removed?
304.11
A device that will automatically shut off the fuel supply to a main burner or group of burners when the means of ignition becomes inoperative or flame failure occurs is a:
Chapter 2 – Definitions
To obtain a building permit, construction documents are required to be drawn to what characteristic?
Chapter 2 – Definitions
Repair garages for lighter-than-air fuels (other than hydrogen) shall have air supply inlets and exhaust outlets arranged to provide uniformly distributed air movement, with outlets located where?
502.16.2.1
Where chemicals that generate corrosive or flammable products are routinely used, fired appliances where these chemicals can enter combustion air shall be located in a mechanical room that is partitioned off and provided with combustion air from:
304.12
If subject matter in a referenced standard is within the scope of this code, which provisions shall take precedence?
102.8.2
For liquid single-phase solar energy systems, the expansion tanks must be sized in accordance with Section 1009, with an additional expansion tank acceptance volume equal to the total volume of liquid contained in what two components?
1402.8.7, 19
Exhaust outlets for grease ducts must be located not less than how many feet above adjoining grade level?
506.3.13.3
A through-the-wall direct-vent terminal serves an appliance rated at 10,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
Piping installed downstream of the point of delivery is prohibited from extending through any townhouse unit other than:
404.3
Where an emergency exists, the code official is not required to provide a written notice prior to:
114.3
Brazing alloys used in hydrogen service piping must have a melting point greater than what minimum temperature?
704.1.2.4.1
The entire length of a vent connector must be provided with what type of access for inspection, cleaning and replacement?
503.10.12
A single booster-type automatic instantaneous water heater used solely for sanitizing rinse in a commercial kitchen must have its draft hood outlet located not less than 36 inches vertically and what minimum distance horizontally from any surface other than the heater?
501.8
Listed and labeled fireplace accessories must comply with which UL standard?
902.2
Refrigerant piping systems erected in the field shall be pressure tested for strength and leak tested for tightness after installation and before being placed in operation, in accordance with which section?
1110.1
Vents for Category II and III appliances shall be tested in accordance with which UL standard?
502.1
Air-conditioning systems that supply required ventilation air must be provided with controls designed to automatically maintain the required outdoor air supply rate during which time period?
405.1
For which purpose may the code official authorize the temporary connection of a system to a utility?
109.2
A time limit for compliance with an order to remove or restore an unsafe installation to a safe condition shall be specified in the:
113.6.1
A draft hood supplied with or forming a part of a listed vented appliance must be installed without alteration, exactly as furnished and specified by the appliance manufacturer.
503.12.2
Masonry chimneys exposed to the outdoors on one or more sides below the roof line are defined as:
Chapter 2 – Definitions
Vent outlets for purging gaseous hydrogen systems shall be located at least what minimum distance from building openings and lot lines of properties that can be built on?
705.5.3.1
A fireplace composed of listed factory-built components assembled in accordance with the terms of listing is a:
Chapter 2 – Definitions
Vent pipe outlets for purging gaseous hydrogen systems shall be located not less than what minimum height above the adjacent ground level?
705.5.3.1
Mechanical joints used on steel or stainless steel fuel oil pipe and employing an approved elastomeric seal must generally be installed in which location?
1303.7.1
In multiple-tenant buildings, shutoff valves for each tenant must be provided with access and must be located where?
409.3.1
A permanent mechanical joint incorporating an elastomeric seal and made with a pressing tool and jaw or ring approved by the fitting manufacturer is a:
Chapter 2 – Definitions
Appliances located in private garages and carports shall be installed with a minimum clearance of how many feet above the floor?
304.7
In residential garages, appliances installed in a separate, enclosed space having access only from outside the garage are permitted to be installed at floor level, provided the required combustion air is taken from where?
305.3.1
A technical opinion and report required by the code official shall be provided without charge to whom?
104.2.2.1
The use of plastic solar collector covers serving as roof covering is limited to those approved light-transmitting plastics meeting the requirements for plastic roof panels in which specific section of the International Building Code?
1402.8.1.3 Exception, 13
For fire dampers, the operating temperature of the primary heat-responsive device must be approximately 50{F} above the normal duct temperature, but not less than what minimum temperature?
607.3.3.1
The required minimum indoor temperature must be maintained at what specific point above the floor on the design heating day?
309.1
What is the testing standard a material must pass to be classified as a Noncombustible Material?
Chapter 2 – Definitions
What is the minimum horizontal distance required between vertical discharge fans and parapet-type building structures?
506.5.6 Exception
Where is nonmetallic fuel oil pipe permitted to be installed?
1302.4
Protective steel shield plates must extend not less than how many inches above sole plates and below top plates?
305.5
The length of the bonding jumper between the connection to a gas piping system and the connection to a grounding electrode system shall not exceed what maximum length?
310.2.3
The installing contractor or registered design professional must issue a certificate of test to the code official for all refrigeration systems containing what minimum amount of refrigerant?
1110.7
The use of toxic fluids in solar thermal systems must comply with Chapter 60 of the International Fire Code and which federal act?
1403.4, 21
A room primarily utilized for the installation of a boiler is defined as what?
Chapter 2 – Definitions
Plastic plumbing piping and tubing within plenums must have a flame spread index not greater than 25 and a smoke-developed index not greater than 50 when tested in accordance with which standard?
602.3.8
What is the minimum length (in feet) of nominal 4-inch piping that, when removed from service, must have its residual fuel gas displaced with an inert gas?
406.7.1.1; Table 406.7.1.1
Steel pipe joints embedded in concrete must be welded by electrical arc method or what other method?
1209.3.1
Which components are generally exempt from field testing requirements for refrigeration piping systems?
1110.1 Exception
What are the parts of a refrigerating system subject to evaporator pressure?
Chapter 2 – Definitions
Where used in this code, the term ” piping ” refers to:
Chapter 2 – Definitions
Where factory-built chimneys pass through attic space, how high above the insulation materials must the insulation shield terminate?
805.8, 40
For chimney connector wall pass-through systems, insulation material that is part of the system shall be noncombustible and have a thermal conductivity of what maximum value?
Table 803.10.4 Note, 28
Appliances, equipment, and systems regulated by this code are prohibited from being located in which area?
301.15
Which of the following is not one of the criteria against which an alternative material, design, or method of construction must be found equivalent?
104.2.3.4
When using Type B double-wall gas vent connected by a single-wall metal connector to a single Category I appliance, if the vent height (H) is 20 feet, the lateral (L) is 20 feet, and the vent diameter (D) is 12 inches, what is the maximum input rating (NAT Max) for a Natural Draft appliance?
504.2; Table 504.2(2)
Commercial electric water heaters must comply with which UL standard?
1002.1
Vented appliances are generally required to be installed with draft hoods, except for which type of appliance?
503.12.1
Which exhaust systems are allowed to be located in ceiling return air plenums over spaces permitted to have 10 percent recirculation (Section 403.2.1, Item 4), provided the duct joints comply with Section 603.9?
601.4 Exception 1
Metallic ducts installed underground and not having an approved protective coating must be completely encased in not less than how many inches of concrete?
603.8
Open-type expansion tanks shall be located not less than how many feet above the highest heating element?
1009.3
Air intake openings and living space exhaust air openings of an individual dwelling unit can use a factory-built intake/exhaust combination termination fitting if the separation distance is less than what distance?
501.3.1
The strength and rigidity of posts greater than 3 feet (914 mm) in height supporting illuminating appliances must be at least equivalent to a 2 1/2-inch-diameter (64 mm) post constructed of what minimum thickness of steel?
628.3
In a Retail store, sales floor, or showroom, what is the required Exhaust Airflow Rate in CFM/ft squared for Dressing rooms?
Table 403.3.1.1
Prior to the approval of a prefabricated construction assembly having concealed work and the issuance of a permit, the code official shall require the submittal of a(an):
111.2.5
A water heater pan constructed of plastic must have a minimum thickness of not less than what dimension?
1002.4
Ignition of gas at the burner(s) when the gas controlling device is turned on, including reignition if the flames have been extinguished by means other than by the closing of the gas controlling device, is defined as:
Chapter 2 – Definitions
An oxygen-depletion safety system on an unvented room heater shall shut off the gas supply when the oxygen in the surrounding atmosphere is depleted to the percent concentration specified by the manufacturer, but not lower than what minimum percentage?
621.6
A room or space in which nonfuel-fired mechanical equipment and appliances are located is defined as what?
Chapter 2 – Definitions
The pressure difference created by a vent or chimney because of its height, and the temperature difference between the flue gases and the atmosphere, is defined as:
Chapter 2 – Definitions
What is the minimum clearance required above the top of the sloping side of a vertical draft hood on a suspended unit heater?
620.4
Which valve standard is approved for general valve applications up to 125 psig pressure?
409.1.1; Table 409.1.1
When calculating the installed thickness (R-value) for duct wrap, the installed thickness shall be assumed to be what percentage of the nominal thickness (representing 25 percent compression)?
604.7
When rooftop-mounted solar thermal collectors are mounted on or above the roof covering, the collector array and mounting systems must be constructed of noncombustible materials or what other material conforming to the International Building Code?
1402.8.1.2, 12
Recovered refrigerants may be reused only in the system from which they were recovered and in other systems of what party?
1102.2.2.2
Access to a dedicated enclosure containing an appliance (where combustion air is taken directly from the outdoors) shall be through a solid door equipped with what type of closing device?
303.3 Exception
New installations and parts of existing installations that have been altered, extended, renovated, or repaired shall be tested to disclose:
111.3.1
An application for a permit shall be deemed abandoned how many days after the date of filing, unless pursued in good faith or a permit has been issued?
105.3.2
Type L vents shall terminate not less than how many feet above the highest point of the roof penetration?
802.5, 17
If the code official has obtained a proper inspection warrant, what must the person having charge or control of the structure permit?
104.4.1
A thermostat in which the motion of the valve is approximately in direct proportion to the effective motion of the thermal element induced by the temperature change is a:
Chapter 2 – Definitions
Dampers equipped with fusible links, internal operators, or both must be provided with an access door that is not less than how many inches square?
607.4.1
The payment of the fee for work authorized by a permit shall not relieve the applicant or holder of the permit from paying what?
108.5
What is the minimum clearance required above an appliance where the original required clearance was 12 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
Hydronic piping materials must be rated for the operating temperature and pressure of the system and must be suitable for what other specific factor?
1202.3
Outdoor air inlets serving the residential portion of a building must be covered with a screen having what maximum size openings?
618.4
What is the minimum required dimension of the ventilation opening into the sauna room located near the top of the door?
914.5
Air transported to occupied spaces through dust-producing materials by means other than natural convection shall be treated in what manner before entering the occupied space, in accordance with Section 605?
1402.8.2.1, 14
Periodic testing is required for which of the following emergency devices and systems?
1111.1
Mechanical ventilation systems must be provided with manual or automatic controls that will operate such systems whenever the spaces are in what state?
405.1
For gas engine-powered equipment and turbines, what connection method is prohibited to the gas supply piping to protect against the effects of normal vibration?
616.2
Ground-source heat pump loop system piping must be marked where it enters a building, indicating “GROUND-SOURCE HEAT PUMP LOOP SYSTEM” and what two other pieces of information?
1210.8.9
What must be done to the parts in a Plastic Heat Fusion Joint to permit fusion of the materials when the parts are pressed together?
Chapter 2 – Definitions
The code official shall be appointed by which authority?
103.2
What is the required People Outdoor Airflow Rate in the Breathing Zone in CFM/person for a Bedroom/living room in hotels, motels, resorts, and dormitories?
Table 403.3.1.1
For 3/4-inch Nominal OD Polyethylene plastic tubing (SDR 11) at a length of 500 feet, what is the capacity in cubic feet per hour (cfh) for natural gas with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(24)
For smoke barriers in non-sprinklered buildings using the pressurization method, the pressure difference across the smoke barrier must be not less than what value relative to the maximum calculated pressure difference produced by the design fire?
512.6.1
What is the minimum thickness required for steel construction of a Type II hood?
507.3.1
For Refrigerant Pressure Vessels, evaporators are excluded if each separate section does not exceed what maximum refrigerant-containing volume?
Chapter 2 – Definitions
Which method allows a venting system (chimney or vent) to pass through a plenum, provided it is installed such that fittings and joints between sections are not installed in the above ceiling space?
601.4 Exception 2
Where must the midpoint of the water-gauge glass be installed on a steam boiler?
1010.2.1
When utilizing a combustible gas detector to monitor purging, when shall purging be stopped?
406.7.2.1
Storage tanks and heating equipment installed in outdoor locations must be designed for what specific condition?
1402.8.5.2, 18
Insulation R-values for slab-on-grade and suspended floor installation for radiant heating systems must be in accordance with which code?
1209.5
What is an assembly of connected ducts, plenums, fittings, registers, grilles and hoods through which air is conducted from the space and exhausted to the outdoor atmosphere?
Chapter 2 – Definitions
Where in an occupied area should the inlet to an exhaust system be located?
502.1.1
Liquid adhesive coatings used on air filters must have a flash point not lower than what minimum temperature?
605.1
Plume discharges from cooling towers, evaporative condensers, and fluid coolers must be located not less than how many feet above or away from any ventilation inlet to a building?
908.3
A vent cap must be installed on vertical terminations of mechanical draft systems for what purpose?
804.3.5, 34
Pressure relief devices shall be arranged to discharge to the outdoors, except for DOTn-specified containers with an internal volume not exceeding what maximum amount?
703.3.8 (Exception)
A timer provided to control main burner operation of a sauna heater shall have a maximum operating time of what duration?
615.6.1
What type of appliance is strictly prohibited from being installed within a plenum?
602.1
A plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature is:
Chapter 2 – Definitions
An appliance vented by natural draft shall not be connected into a vent, chimney, or vent connector on which side of a mechanical flue exhauster?
804.3.6, 35
An automatic or semiautomatic device consisting essentially of a valve and operator that control the gas supply to the burner(s) during operation of an appliance is a(an):
Chapter 2 – Definitions
What is the minimum weight of steel pipe required for Group A2, A3, B2, and B3 refrigerants for sizes 1 1/2 inches or less in diameter?
1107.4.1
A change in a mechanical system that involves an extension, addition, or change to the arrangement, type, or purpose of the original installation is defined as what?
Chapter 2 – Definitions
Appliances regulated by this code must be listed and labeled for their application unless approved in accordance with which section?
301.7
Which type of vent is listed and labeled for use with appliances that are listed for use with Type L or Type B vents?
Chapter 2 – Definitions
A self-contained, automatically controlled, vented, fuel-gas-burning, space-heating appliance, intended for installation in the space to be heated without the use of ducts, and having integral means for circulation of air, is a:
Chapter 2 – Definitions
When split-style piping insulation is used in a solar loop, what must be sealed?
1402.8.3.1, 15
What is the capacity in cfh for 1 1/4-inch nominal Schedule 40 metallic pipe at 100 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(3)
What are the accepted standards used to determine the Flash Point of a liquid?
Chapter 2 – Definitions
What is the minimum pressure difference required across a smoke barrier in buildings equipped throughout with automatic sprinkler systems when utilizing the pressurization method?
512.6.1
What must boiler rooms be equipped with for disposing of liquid waste?
1004.6
Screens used for combustion air openings shall have a mesh size not smaller than what dimension?
304.1
Where are fuel oil test wells strictly prohibited from being installed?
1306.2
Exhaust outlets that terminate through exterior walls shall not be located within what minimum horizontal distance of any opening in the exterior wall?
506.3.13.2
What is the capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, operating at 3.0 psi inlet pressure with a 2.0 psi pressure drop?
402.4; Table 402.4(6)
According to Table 1009.2, what is the required nonpressurized expansion tank capacity in gallons for a system volume of 500 gallons?
Table 1009.2
A Limit Control is a device responsive to changes in pressure, temperature, or what other factor, for turning on, shutting off, or throttling the gas supply to an appliance?
Chapter 2 – Definitions
A metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare is a:
Chapter 2 – Definitions
Solar thermal systems are intended to utilize solar energy for which purposes?
1401.1
Pressure relief devices, fusible plugs, and purge systems located within the machinery room shall terminate outside the structure not less than how many feet above the adjoining grade level?
1105.7
Unless otherwise approved, pressure vessels must be constructed and certified in accordance with which standard?
1003.1
A fuel oil fill pipe must terminate outside a building at a point not less than what minimum distance from any building opening at the same or lower level?
1305.6
A valve located in the piping system, used to isolate individual appliances for purposes such as service or replacement, is a(an):
Chapter 2 – Definitions
A manually or automatically controlled device to regulate draft or the rate of flow of air or combustion gases is a:
Chapter 2 – Definitions
What is the maximum capacity in cubic feet per hour (cfh) for 1 1/4-inch nominal Schedule 40 metallic pipe at a length of 50 feet, for natural gas at less than 2 psi inlet pressure and 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
When granting a modification due to practical difficulties, the code official must ensure the modification does not lessen which requirement?
104.2.4
The code official shall keep a record of tests conducted to comply with the requirements for tests used as evidence of compliance and tests required for:
104.7.4
Compartments housing equipment used in aircraft fueling and defueling operations shall be adequately ventilated at floor level or within what other location?
502.2
In machinery rooms using Group A2L and B2L refrigerants, open flame-producing devices or continuously operating hot surfaces shall not exceed what maximum temperature?
1106.4.1
Controls and safety devices for boilers with inputs greater than or equal to 12,500,000 must meet the requirements of which standard?
1004.1
Galvanized sheet steel auxiliary drain pans must have a minimum thickness of not less than what gauge?
307.2.3
Where equipment is located on a roof such that personnel must climb higher than 16 feet (4877 mm) above grade to access it, what type of access must be provided?
306.5
Under what concentration of the lower flammable limit (LFL) is air exhausted from spraying operations permitted to be recirculated as makeup air for unmanned spray operations?
502.7.3.2 Exception 1
What is the minimum closed cup flash point for Class IIIB Combustible Liquids?
Chapter 2 – Definitions
As an alternative to the provisions of Sections 1202 and 1203, hydronic piping shall be designed, installed, inspected, and tested in accordance with which standard?
1201.3
What is the Refrigerant Safety Group Classification for R-1234yf?
Table 1103.1
In a Limited Charge System, with the compressor idle, the design pressure will not be exceeded when what condition occurs?
Chapter 2 – Definitions
Catwalks installed to provide required access shall be not less than what minimum width?
306.5
For domestic kitchen cooking appliances with downdraft exhaust systems, PVC pipe and fittings are permitted under a concrete slab poured on grade, provided the underfloor trench is completely backfilled with what?
505.3 Exception 2
What are the specified materials for Tubing, as defined in Piping?
Chapter 2 – Definitions
Appliances equipped with an automatic burner ignition and safety shutoff device and other automatic devices that accomplish complete turn-on and shutoff of the gas to the main burner(s) and graduate the gas supply, but do not affect complete shutoff of the gas, are defined as:
Chapter 2 – Definitions
The test pressure measuring device must have an accuracy of what maximum percentage of the test pressure?
1110.5
What is the approximate number of threads required to be cut for a 2 1/2-inch iron pipe size?
403.8.2; Table 403.8.2
Structures occupied for purposes involving explosion hazards must be provided with explosion control where required by which code?
310.1
Who appoints the code official?
103.2
For piping materials other than steel pipe and CSST, exposed piping must be identified by a yellow label marked “Gas” in black letters at intervals not exceeding what distance?
401.5
One ton of Refrigeration Capacity Rating is equivalent to how many Btu/h?
Chapter 2 – Definitions
Supply air ducts connecting to listed central heating furnaces must maintain the same minimum clearance to combustibles as required for the furnace plenum for a distance of not less than how far from the supply plenum?
308.4.5
For undiluted propane calculations using the equation factors listed, what is the value designated as Cr?
402.4; Table 402.4
What is the maximum temperature of the products of combustion at the point of entrance to the flue for a Low-heat appliance (residential appliance) under normal operating conditions?
Chapter 2 – Definitions
For Group R-2, R-3, and R-4 occupancies, the minimum continuous outdoor airflow rate is calculated using Equation 4-9 based on conditioned floor area and what other variable?
403.3.2.1
A thermostat controlling a sauna heater must limit the room temperature to what maximum temperature?
914.4
A manually operated damper shall not be placed in the vent connector for any appliance, but fixed baffles and balancing baffles are not classified as manually operated dampers.
503.13
Commercial cooking appliances installed on casters must be connected to the piping system with an appliance connector listed as complying with which standard?
411.1.1
A combination flashback arrestor and backflow check valve shall be installed at an approved location on both the fuel gas and oxygen supply lines where fuel gas is used with oxygen in which operation?
410.5
If a greater quantity of air is supplied by a mechanical ventilating supply system than is removed by a mechanical exhaust for a room, adequate means shall be provided for what?
501.4
Plastic pipe, fittings, and components must be third-party certified as conforming to which standard?
301.4
Grease ducts must be constructed of steel having a minimum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) or stainless steel not less than what minimum thickness?
506.3.1
What must a clearly identified switch of the break-glass type or with an approved tamper-resistant cover provide for the machinery room ventilation fans?
1106.5.2
What is the maximum horizontal length allowed for a single-wall connector?
803.10.2, 25
To prevent the entry of room air into a chimney flue below the point of connection to an appliance serving a fireplace, what type of seal must be provided?
501.7.1
What is the exception for the minimum average air velocity into an open face or open front spray booth using fixed or automated electrostatic spray application equipment?
502.7.3.3.1 Exception
Who is authorized to make or require other inspections of construction work to ascertain compliance with the provisions of this code?
111.2.1
Appliance connections to a chimney or vent equipped with a power exhauster must be made on which side of the exhauster?
501.1
In a Wall Canopy Hood, what component acts as a back panel, forcing the makeup air across the front of the cooking equipment?
Chapter 2 – Definitions
Cutting, notching, and boring of wood framing members shall comply with which section of the International Building Code?
302.3
Evaluation reports issued to support approval of materials or assemblies not specifically provided for in the code must be issued by whom?
104.2.3.6.1
Where must mechanical fasteners penetrate when installing radiant heating panels on wood or steel framing?
927.3
Masonry chimneys without the required airspace clearances are permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with which UL standard?
801.18.4 Exception, 13
What type of damper must comply with the requirements of UL 555C or be tested as part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly in accordance with ASTM E119 or UL 263?
607.3.1
The application for a permit shall be signed by whom?
105.3
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 6 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
Appliances located in private garages shall be installed with a minimum clearance of what distance above the floor?
305.5
Supports for cooling towers, evaporative condensers, and fluid coolers must be designed in accordance with which code?
908.4
Arc-resistant-jacketed CSST shall be listed as arc resistant in accordance with which standard?
310.3
When two or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical vent or chimney shall not exceed what multiple of the flow area of the smallest listed appliance categorized vent area?
504.3.17
Tests conducted to demonstrate equivalent fire safety must be sufficient scale to predict fire safety performance of the:
104.2.3.5.1
Venting systems are prohibited from extending into or passing through any fabricated air duct or what other air-handling component?
503.3.5
Exhaust fan motors serving a Type I hood must be located where relative to the exhaust airstream?
506.5.1.1
Where an oil-fired appliance is connected to an existing masonry chimney, the chimney flue shall be repaired or relined in accordance with which standard?
801.18.2, 12
Which type of thermostat senses temperature changes and controls the flow of gas to the burner(s) electrically, by means of separate components?
Chapter 2 – Definitions
That which enables a device, appliance or equipment to be reached by ready access or by a means that first requires the removal or movement of a panel, door, or similar obstruction is defined as:
Chapter 2 – Definitions
If non-stainless steel or non-black steel piping is installed through wood studs less than 1 1/2 inches (38 mm) from the nearest edge, what minimum thickness must the required steel shield plates have?
704.1.2.3.5
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe must conform to which ASTM standard?
Table 1202.4
The opening in a cap, spud or other device whereby the flow of gas is limited and through which the gas is discharged to the burner is the:
Chapter 2 – Definitions
Air dispersion systems must be utilized in systems operating under what pressure characteristic?
603.17
A refrigerating system where the evaporator or condenser is in direct contact with the air or other substances to be cooled or heated is defined as what?
Chapter 2 – Definitions
Construction or work for which a permit is required shall remain visible and able to be accessed for inspection purposes until:
111.1
In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to which specific location?
403.3.1.1
What is a device actuated by another device, to govern succeeding operations of the same or allied devices?
Chapter 2 – Definitions
What is the pipe that connects an approved fuel-fired appliance to a vent?
Chapter 2 – Definitions
In industrial occupancies and refrigerated rooms, where a machinery room would otherwise be required, refrigerant detectors are not required in unoccupied areas that contain only what type of piping?
1104.2.2 Exception
A Vented Room Heater burns which types of fuel?
Chapter 2 – Definitions
Additions, alterations, renovations, or repairs related to structural issues shall be regulated by which other code?
102.2.1
Smoke damper leakage ratings must be Class I or II, and the elevated temperature ratings shall be not less than what minimum temperature?
607.3.2.2
Shutoff valves used in fuel oil systems must comply with which UL standard?
1307.1
The required thickness for hydronic piping insulation shall conform to the requirements of which code?
1204.2
Which term is NOT an alternate name for a backshelf hood?
Chapter 2 – Definitions
The point at which a gas-fired appliance connects to the gas piping system is the:
Chapter 2 – Definitions
Basements or pits in bulk plants or terminals where Class I liquids are stored or used must be provided with ventilation designed to prevent what?
502.9.5.5.2
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 9 inches, and the protection is 0.024-inch sheet metal over 1-inch glass fiber or mineral wool batts with ventilated airspace?
308.2; Table 308.2
What is the minimum distance required between the lowest edge of a grease filter and an exposed flame or burner cooking surface?
Table 507.2.8
What is the maximum spacing of supports required for vertical 1-inch O.D. smooth-wall tubing?
415.1; Table 415.1
What is the minimum clearance required from the grade level to the lowest portion of a floor furnace?
609.4
What is a factory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant?
Chapter 2 – Definitions
Vent connectors are generally prohibited from being covered with insulation, except when the connectors are:
503.10.2.3 (Exception)
Recirculating direct-fired air heaters shall not be installed in buildings that contain flammable solids, liquids or gases, explosive materials, or substances that can become toxic when exposed to flame or heat.
612.2
Where a venting system passes through an above-ceiling air-handling space and joints are installed within that space, the joints must be sealed in accordance with the appliance or vent manufacturer’s instructions, or the venting system must be installed in a sealed conduit or enclosure.
503.3.6
A nontoxic, gaseous hydrogen system mixture must contain at least what minimum percentage of hydrogen gas by volume?
702.1
Vented wall furnaces shall be located so that a door cannot swing within what minimum distance of an air inlet or air outlet of such furnace, measured at right angles to the opening?
608.4
A valve used in conjunction with an automatic gas shutoff device to shut off the gas supply to a water-heating system is a(an):
Chapter 2 – Definitions
When using Type B double-wall gas vent connected by a single-wall metal connector to a single Category I appliance, if the vent height (H) is 8 feet, the lateral (L) is 5 feet, and the vent diameter (D) is 9 inches, what is the minimum input rating (FAN Min)?
504.2; Table 504.2(2)
Pellet fuel-burning appliances must be listed and labeled in accordance with which standard?
904.1
The cross-sectional area of a flue serving a solid-fuel-burning appliance shall be no greater than what multiple of the cross-sectional area of the appliance flue collar?
801.7
Reused pipe, fittings, valves, or other materials must be clean and free from foreign materials and must be approved by whom for reuse?
1202.2
What is the minimum thickness required for the steel insulation shield installed where factory-built chimneys pass through insulated assemblies?
805.8, 40
Outdoor Air is defined as air taken from the outdoors and is characterized as not having been previously circulated through what?
Chapter 2 – Definitions
Liquid combustion byproducts of condensing appliances must be discharged to an approved plumbing fixture or disposal area in accordance with whose instructions?
307.2
For an exterior masonry chimney serving a single space-heating appliance in a climate zone with a Local 99% Winter Design Temperature of 5 to 16°F, with a vent height of 15 feet and an internal area of 113 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.2; Table 504.2(6)
Inlet ducting, where used with nonrecirculating direct-fired industrial air heaters, shall be purged by not less than how many air changes prior to an ignition attempt?
611.9
Refrigerant piping protection is not required outside the building if the piping is installed underground not less than how many inches below finished grade and protected against corrosion?
1109.2.2
To confirm its objectivity, an approved agency must disclose all possible:
301.4.2.1
What is the minimum wall thickness required for copper tubing used as a fuel oil line?
1305.1
In the exception for adjoining spaces, if an exterior opening opens into a thermally isolated sunroom addition, what is the minimum openable area required between the sunroom and the interior room?
402.3 Exception
What is strictly prohibited from being installed in a machinery room if they use combustion air from the room?
1105.5
Gas piping systems constructed entirely of pipe or tubing not meeting the size and length criteria for displacement must have a design operating pressure of what maximum amount to be purged indoors or outdoors?
406.7.2
The amount of supply air in a mechanical ventilation system shall be approximately equal to the amount of what other air component?
403.1
Appliances shall not be installed in a location where subject to mechanical damage unless protected by what?
303.4
The Breathing Zone is the region within an occupied space located between planes 3 inches (76 mm) and what maximum height above the floor?
Chapter 2 – Definitions
What is the purpose of a Draftstop?
Chapter 2 – Definitions
When considering modifications in flood hazard areas, the code official must determine that the granting of a variance will not cause fraud on or victimization of the public or:
104.2.4.1
The Refrigerant Safety Group Classification indicates both the flammability and what other classification of refrigerants?
Chapter 2 – Definitions
Where an appliance is connected to an existing chimney or vent, the system must be resized to control flue gas condensation and provide the required:
501.15.1
The board of appeals shall render all decisions and findings in writing to the appellant with a duplicate copy provided to the:
112.1
Fireplace stoves must be tested in accordance with which UL standard?
905.1
In a Balanced Ventilation System, the mechanical supply airflow rate and mechanical exhaust airflow rate must each be within what percentage of the average of the two airflow rates?
Chapter 2 – Definitions
The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for which type of chimneys?
308.4.2.2
What is the minimum flash point for Fuel Oil?
Chapter 2 – Definitions
A device that will prevent the backflow of one gas into the supply system of another gas and prevent the passage of flame into the gas supply system is a:
Chapter 2 – Definitions
Exhaust inlets for manicure and pedicure stations must be located not more than how many inches horizontally and vertically from the point of chemical application, if a factory-installed inlet is not provided?
502.2
To ensure reliability, approved agencies must have adequate equipment to perform all required tests and must periodically perform what action to that equipment?
301.8.2.2
What is a Pressure-Limiting Device designed to stop automatically?
Chapter 2 – Definitions
These regulations, subsequent amendments thereto or any emergency rule or regulation that the administrative authority having jurisdiction has lawfully adopted, is the definition of which term?
Chapter 2 – Definitions
The cutting and notching of holes in cold-formed steel framing members designated as structural members shall be in accordance with which standard?
302.6
A Type B or L gas vent shall terminate not less than what minimum vertical height above the highest connected appliance draft hood or flue collar?
503.6.6
Brazed joints must be made with a filler metal conforming to which AWS standard?
1203.3.1
Which type of temperature relief valve automatically opens and closes a relief vent, depending on whether the temperature is above or below a predetermined value?
Chapter 2 – Definitions
Rooms containing appliances must be provided with a door and an unobstructed passageway measuring not less than what width and height?
306.2
Joints used underground in ground-source heat pump loop systems shall be of what type?
1210.6
Which of the following appliances is not required to be vented?
501.8
Which medium is strictly prohibited from being used to pressurize fuel oil tanks?
1305.5
What is the function of an Evaporator in a refrigeration system?
Chapter 2 – Definitions
Openings into fire-resistance-rated construction for exit enclosure ventilation systems shall be limited to those needed for maintenance and operation and protected by what?
601.3
An air compartment or chamber to which one or more ducts are connected and that forms part of an air distribution system is a:
Chapter 2 – Definitions
Spaces above, below, or behind what feature shall NOT be considered a concealed location?
Chapter 2 – Definitions
For absorption units, the label information must include the hourly rating in Btu/h (W), the type of fuel, the type of refrigerant, the cooling capacity in Btu/h (W), and what other key information?
301.9
An unvented heating appliance designed for stationary installation and utilized to provide comfort heating, providing radiant or convection heat directly from the heater without utilizing ducts, is a(an):
Chapter 2 – Definitions
Before a permit is issued, the code official is authorized to inspect and evaluate the systems, equipment, buildings, devices, premises and spaces or areas to be used in a procedure known as a:
105.4
The minimum mechanical ventilation rate determined by Equation 4-9 can be reduced by 30 percent if the system supplies ventilation air directly to each bedroom and to one or more of which specific rooms, AND the system is a balanced ventilation system?
403.3.2.1 Exception 2
A Type L vent is listed and labeled for use with oil-burning appliances and which type of gas-fired appliances?
Chapter 2 – Definitions
An established and recognized organization that is regularly engaged in conducting tests, furnishing inspection services or furnishing evaluation or certification, where such organization has been approved by the code official, is a(an):
Chapter 2 – Definitions
Why does a Single Island Canopy Hood require a greater exhaust airflow than an equivalent sized wall-mounted canopy?
Chapter 2 – Definitions
Carbon monoxide and nitrogen dioxide detectors used for automatic operation of enclosed parking garage ventilation systems must be listed in accordance with which UL standard?
404.1
Upon issuance of a stop work order, how shall the cited work proceed?
115.2
For Type II dry cleaning systems, the mechanical ventilation system must be designed to exhaust air at what minimum rate per square foot of floor area?
502.6.1
Liquid fuel vent pipes shall terminate outside buildings not less than what minimum distance from any building opening?
1305.7
A joint made by bolting together a pair of flanged ends is a:
Chapter 2 – Definitions
Ducts discharging combustible material directly into any combustion chamber shall conform to the requirements of which standard?
601.1 Exception
Fire dampers must have a minimum rating of 1.5 hours for which type of fire-resistance-rated assemblies?
Table 607.3.2.1
An automatic valve that opens and closes a relief vent, depending on whether the pressure is above or below a predetermined value, is a:
Chapter 2 – Definitions
Pipe hangers and supports in direct contact with piping shall be of approved materials that are compatible with the piping and will not promote what type of action?
305.2
A safety valve designed to forestall the development of a dangerous condition by relieving either pressure, temperature or vacuum in the hot water supply system is a:
Chapter 2 – Definitions
The upper edge of a masonry chimney cleanout opening must be located not less than how many inches below the lowest chimney inlet opening?
801.13, 7
Refrigeration systems using a refrigerant other than ammonia must comply with Chapter 11, the International Fire Code, and which specific ASHRAE standard?
1101.1.1
An adapter for joining plastic pipe to steel pipe, providing a permanent, pressure-tight connection between two materials that cannot be joined directly one to another, is defined as:
Chapter 2 – Definitions
Furnaces and boilers installed in closets and alcoves must be listed for what specific application?
303.5
A plastic water heater pan material must have a flame spread index of not more than 25 and a smoke-developed index of not more than what value when tested in accordance with ASTM E84 or UL 723?
1002.4
For CPVC pipe joint connections, a primer is not required if the solvent cement is used only for joining CPVC pipe and fittings within what diameter range?
1203.3.4 Exception
In the One-Permanent-Opening Method (304.6.2), what is the minimum free area required for the single opening per 3,000 Btu/h of total appliance input rating?
304.6.2
What is the distinguishing fuel characteristic of an Extra-Heavy-Duty Cooking Appliance?
Chapter 2 – Definitions
For horizontal terminations of mechanical draft systems adjacent to walkways, what is the minimum required height above the walkway level?
804.3.4, 33
Which occupancy includes hospitals, nursing homes, asylums, and spaces containing locked cells?
1103.2
The treatment of air so as to control simultaneously the temperature, humidity, cleanness, and distribution of the air is known as what?
Chapter 2 – Definitions
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a medium-heat appliance?
503.10.5; Table 503.10.5
When a multistory common vent system includes an offset that does not exceed 45 degrees, the common vent capacity listed in the tables must be reduced by what percentage for the segment containing the offset?
504.3.16
The fee for a permit, where required, shall be paid in accordance with the schedule established by whom?
108.2
If work authorized by a permit is suspended or abandoned for a period of 180 days, the permit shall expire. If a new permit is required, what fraction of the original fee shall be charged, provided the abandonment has not exceeded 1 year and changes have not been made?
105.4.3
What is the minimum slope required toward the hood or a grease reservoir for grease duct systems serving a Type I hood?
506.3.7
Potable water supplies to solar systems must be protected against contamination in accordance with which code?
1401.2
Requirements necessary for the strength, stability, or proper operation of a mechanical system not specifically covered by this code shall be determined by whom?
102.9
Refrigeration systems containing carbon dioxide (R-744) must also comply with which IIAR standard?
1101.1.1
A fire chamber and hearth constructed of noncombustible material for use with solid fuels and provided with a chimney is a:
Chapter 2 – Definitions
What NFPA standard dictates the exhaust ventilation requirements in public garages, private garages, repair garages, automotive motor fuel-dispensing facilities and parking garages that contain hydrogen-generating appliances or refueling systems?
703.1
A Peer Review must be conducted by whom?
Chapter 2 – Definitions
Supply air plenums formed by gypsum boards shall not be incorporated in air-handling systems utilizing which specific cooling system type?
602.2
Which components are exempt from the requirement for locking access port caps if installed in controlled areas such as roofs with locked access hatches or doors?
1101.9 Exception
Low-pressure boilers operate at pressures less than or equal to 15 pounds per square inch (psi) (103 kPa) for which medium?
Chapter 2 – Definitions
Materials, equipment, and devices approved by the code official must be constructed and installed in accordance with:
104.9
A draft hood must be located so its relief opening is not less than what minimum distance from any surface except that of the appliance it serves and the venting system?
503.12.7
Combustion air intake openings located on the exterior of a building shall have the lowest side of such openings located not less than what distance vertically from the adjoining finished ground level?
304.11
Each exhaust outlet located within a hood shall serve not more than what maximum linear length of hood?
507.1.5
An Offset (Vent) is a combination of approved bends that makes how many changes in direction?
Chapter 2 – Definitions
Additions, alterations, renovations, or repairs shall not cause an existing mechanical system to become what?
102.4
The interlock requirement for dampers in combustion air openings serves to prevent operation of any appliance that draws combustion air from the room or space when what condition is true?
701.2
A ventilating hood shall be provided above a domestic open-top broiler unit, and a minimum clearance of what distance shall be maintained between the cooking top and combustible material above the hood?
623.5.1
Piping run from a pressure-regulating or pressure-limiting device to the outdoors, designed to provide for the safe venting of gas in the event of excessive pressure in the gas piping system, is defined as:
Chapter 2 – Definitions
For acceptance tests conducted on boilers and pressure vessels, the pressure gauge scale shall be graduated over a range of not less than one and one-half times and not greater than what multiple of the maximum test pressure?
1011.2
What is the required continuous exhaust rate capacity for bathrooms and toilet rooms in Group R-2, R-3, and R-4 occupancies?
Table 403.3.2.3
Outdoor air intake openings located within 10 feet (3048 mm) of a contaminant source must be located not less than how many feet below the contaminant source?
401.4
A nontoxic, gaseous hydrogen system mixture must contain not more than what maximum percentage of oxygen by volume?
702.1
Fuel-fired appliances must be designed for use with the type of fuel to which they will be connected and for what other installation factor?
301.12
Where the duct is constructed of steel not less than 0.019 inch in thickness and there are no openings serving the corridor, smoke dampers are not required at which penetrations?
607.5.4 Exception 3
Steel, stainless steel, and wrought-iron pipe shall be not lighter than which schedule?
403.3.2
For underfloor spaces containing appliances, the unobstructed passageway from the access opening to the appliance shall be not more than what maximum length?
306.4
In an absorption system, what process is used to pressurize the refrigerant?
Chapter 2 – Definitions
What components are strictly prohibited in the rigid metal ductwork of a common multistory exhaust system for clothes dryers?
504.11
What is the maximum air temperature permitted within nonmetallic ducts?
603.5
If different provisions specify different methods of construction in a specific case, which requirement shall govern?
102.1
Where a listing standard is not specified by the code for equipment, materials, products, or services, the listing shall be based on what?
104.2.1
Threaded fittings in metallic piping systems shall not be used in sizes larger than what dimension?
403.9.5
A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under positive static vent pressure is a:
Chapter 2 – Definitions
When soldering on the metal portion of a PEX ground-source system, the solder joints shall be performed not less than what minimum distance from a plastic-to-metal adapter in the same water line?
1210.6.5.2
In a parking garage, connection to a room with a fuel-fired appliance must be by means of a vestibule providing a two-doorway separation, except that a single door is permitted if the sources of ignition in the appliance are what?
304.3.1
New wood-burning residential hydronic heaters must have what certification?
905.1
The air velocity limitations in grease ducts do not apply within transitions used to connect to differently sized or shaped openings, provided such transitions do not exceed what maximum length?
506.3.4 Exception
Decorative appliances for installation in approved solid fuel-burning fireplaces shall be listed in accordance with which ANSI/CSA standard?
602.1
Protective steel shield plates for tubing containing Groups A2, A3, B2, and B3 refrigerants and located in concealed framing spaces must have a minimum thickness of what gauge?
1109.3.1.1
The provisions of this code shall not be deemed to nullify what?
102.1
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 12 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
A connector entering a masonry chimney must be cemented to the masonry in an approved manner, and where thimbles are installed to facilitate removal, the thimble must be permanently cemented in place with what?
803.10.3, 25
Pipe and duct insulation contained within plenums must have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with which mounting procedures?
602.3.9
Overlapping duct joints in a grease duct system shall be installed to prevent ledges and obstructions from collecting grease or interfering with what process?
506.3.2.1
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a listed appliance with a draft hood?
503.10.5; Table 503.10.5
High-probability systems used for human comfort must use which refrigerant safety groups?
1104.3.1
Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at what percentage or less?
403.2.1
The Uncorrected Outdoor Air Intake flow rate for a multiple zone recirculating system is determined using Equation 4-6, which includes the Occupant diversity, defined by what ratio?
403.3.1.1.2.3.3
If appliances or equipment are subject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment, and insulation must be installed where?
307.2.3.2
A BTU is the quantity of heat required to raise the temperature of 1 pound (454 g) of water by how many degrees Fahrenheit?
Chapter 2 – Definitions
Where 150-pound pressure-rated steel flanges are bolted to Class 125 cast-iron flanges, which feature of the steel flange must be removed?
403.11.6
Heating and cooling system design loads must be determined in accordance with the procedures described in which standard?
312.1
The mechanical ventilation system must also exhaust a volume required to limit the room temperature rise to what maximum differential?
1105.6.3.1
What is the maximum capacity in cfh for 3/8-inch ACR semirigid copper tubing at 100 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(8)
In a Plastic Adhesive Joint, the adhesive substance forms a continuous bond between mating surfaces without doing what to either surface?
Chapter 2 – Definitions
Stop valves on copper tubing or aluminum tubing 1 inch (25.4 mm) outside diameter or larger shall not be supported by what?
1109.6.3
In accordance with a decision from the board of appeals, the code official shall take action without what?
112.4
Evaporative cooling equipment must be installed on level platforms in accordance with which section of this code?
928.1
Which vented appliance category operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent?
Chapter 2 – Definitions
The unique identifying alphanumeric value assigned to an individual refrigerant is published in which standard?
Chapter 2 – Definitions
For double-wall heat exchangers, an air gap open to the atmosphere must be provided between the two walls, and the discharge location from the heat exchanger must be what?
1402.8.4.1, 16
A transition assembly in which plastic piping is installed and terminated above ground outside of a building is known as a(an):
Chapter 2 – Definitions
The organization publishing a list of materials, products, or services must be acceptable to whom for the item to be considered Listed?
Chapter 2 – Definitions
What is the minimum height required for a cleanout opening in a masonry chimney flue?
801.13, 7
Fire dampers are not required at penetrations of shafts where steel exhaust subducts extend vertically not less than how many inches in exhaust shafts?
607.5.5 Exception 1
For refrigerant blends not listed in Table 1103.1, a machinery room is required if the combined amount of blend components exceeds a limit of what maximum concentration by volume?
1104.2
To free a gas conduit of air or gas, or a mixture of gas and air, is to:
Chapter 2 – Definitions
For kitchens in Group R-2, R-3, and R-4 occupancies, what is the required intermittent exhaust rate capacity?
Table 403.3.2.3
Parts of fans in contact with explosive or flammable vapors, fumes or dusts shall be constructed of what type of materials?
503.2
Kerosene and oil-fired stoves must comply with NFPA 31 and which UL standard?
922.1
Alterations resulting in the addition of loads to a truss, such as HVAC equipment, shall not be permitted without verification that the truss is capable of supporting what?
302.4
Heat transfer fluids must be rated to withstand the system’s maximum design temperature under operating conditions without what?
1403.2, 20
Nonrecirculating direct-fired industrial air heaters shall not be used to supply any area containing what type of room?
611.2
The underground inspection shall be made after trenches or ditches are excavated and bedded, and piping is installed, but prior to:
111.2
If a single hood serves a combination of light-, medium-, and heavy-duty cooking appliances, which duty classification must the required exhaust rate be based on?
507.2.10
Vent connectors for medium-heat appliances are prohibited from passing through walls or partitions constructed of what type of material?
503.10.15
Where must manufacturer’s installation instructions be available at the time of inspection?
304.1
What is the Zone Air Distribution Effectiveness for a configuration with Ceiling supply of warm air and ceiling return?
Table 403.3.1.1.1.2
If the code official believes the estimated valuation of work provided by the applicant is underestimated, what action may be taken?
108.3
If the lower 6-inch portion of a floor furnace is sealed by the manufacturer to prevent the entrance of water, what is the minimum clearance required from grade level?
609.4
Taking return air from a kitchen is permitted if the return air openings serve the kitchen and are located not less than how far from the cooking appliances?
601.5 Exception 1
Control-air tubing for smoke control systems must be tested at what multiple of the operating pressure for not less than 30 minutes?
512.13.3
Before a change in occupancy is made that subjects the structure to any special provision of this code, what must first be obtained?
102.5
In an attic, what are the minimum clear access opening dimensions required to allow removal of the largest appliance?
306.3
What is the required operating temperature for the actuation device of a ceiling radiation damper?
607.3.3.4
When calculating Net Occupiable Floor Area, how shall obstructions such as furnishings, display or storage racks, whether temporary or permanent, be treated?
Chapter 2 – Definitions
For buildings more than two stories in height, construction documents shall indicate where penetrations will be made for installations and shall indicate the materials and methods for maintaining required structural safety, fireblocking, and:
106.1
Any person who continues work after being served with a stop work order shall be subject to what?
115.4
Return air openings shall not be located less than what minimum distance from an open combustion chamber or draft hood of another appliance in the same room?
601.5
What is the maximum water pressure allowed for a hot water heating boiler at or near the boiler outlet?
Chapter 2 – Definitions
For the purposes of hazardous exhaust, what rating of materials, as specified in NFPA 704, is used to define volatile or airborne materials posing a health hazard?
509.1
Ambulatory care facilities provide care to persons for less than how long?
Chapter 2 – Definitions
When required, design submittals must be prepared by, and bear the stamp of, which professional?
104.2.2.2
Who regulates additions, alterations, renovations, or repairs related to building or structural issues in existing buildings?
102.2.1
What must an approved agency do periodically with its test equipment?
301.4.2.2
Refrigeration System Classification is based on the degree of probability that leaked refrigerant will enter an occupied area based on what primary factor?
Chapter 2 – Definitions
Connectors must rise vertically to the chimney or vent with a minimum pitch equal to what slope?
803.10.5, 29
A steam heating boiler generates steam that operates at a pressure not exceeding:
Chapter 2 – Definitions
What is required for the assertion of certification when a product is Third-Party Certified?
Chapter 2 – Definitions
A Fireplace Stove is designed to be operated with the fire chamber doors in which position(s)?
Chapter 2 – Definitions
What machine is defined as a specific machine, with or without accessories, for compressing a gas?
Chapter 2 – Definitions
If attics or structural spaces are part of a passive solar system, what is not required if other approved means of controlling condensation are provided?
1402.7.1, 11
If work fails an initial test or inspection, what must be done to the work or installation before resubmission to the code official?
111.3.3
For an uninhabited space, if a mechanical exhaust and supply air system is used, the system must be automatically controlled to operate when the relative humidity in the space served exceeds what percentage?
406.1
Prior to approval of a prefabricated construction assembly having concealed mechanical work, what shall the code official require the submittal of?
111.2.5
Which two piping materials shall not be used in contact with R-40 (methyl chloride)?
1107.3
Type I hoods must be constructed of steel having a minimum thickness of 0.0466 inch (1.181 mm) (No. 18 gage) or stainless steel not less than what minimum thickness?
507.2.3
A cleanout must be provided on both the inlet and outlet sides of an in-line fan and located within what distance of the fan duct connections?
506.3.8.2
A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment, is a:
Chapter 2 – Definitions
The flash point of the heat transfer fluid utilized in a solar system must be not less than what minimum temperature above the design maximum nonoperating (no-flow) temperature of the fluid attained in the collector?
1403.1, 19
In a common multistory exhaust system for clothes dryers, rigid metal ductwork must be constructed of sheet steel having what minimum thickness?
504.11
In a laboratory space provided with two or more gas outlets, the single dedicated shutoff valve must be located adjacent to which building feature?
409.6
Heat exchangers used in domestic water-heating systems must be approved for the intended use and must ensure the proper safeguarding of what?
1401.3, 16
Corridor dampers must have a minimum fire-resistance rating of what duration?
607.3.2.4
A burner that depends on draft induced by a fan that is an integral part of the appliance and is located downstream from the burner is a(an):
Chapter 2 – Definitions
A pipe in a ground-source heat pump piping system having an exterior surface temperature exceeding 250{F} must have a minimum clearance of what distance from combustible materials?
1210.8.3
Flue lining systems for Category I appliances shall include flue lining systems complying with Section 501.12 or chimney lining systems listed and labeled for use with Type B vents.
501.13
When shall the rough-in inspection be made?
111.2
A vertical pipe supplying fuel gas is defined as a:
Chapter 2 – Definitions
What is the required Area Outdoor Airflow Rate in the Breathing Zone in CFM/ft squared for a Coin-operated laundry?
Table 403.3.1.1
Who must test a representative sample of appliances being labeled to the relevant standard?
301.4.1
When two or more appliances are connected, the vent connector length for a 12-inch diameter connector shall not exceed what maximum horizontal length?
504.3.2; Table 504.3.2
When testing at a pressure greater than 100 psig (689.5 kPa gauge), the testing gauge must have increments of what maximum amount?
705.3.6
A heater that directs a substantial amount of its energy output in the form of infrared radiant energy into the area to be heated is a(an):
Chapter 2 – Definitions
What must be installed as an alternative to required guards?
304.11 Exception
If the quantity of refrigerant in an independent circuit exceeds the amounts in Table 1103.1, all components containing the refrigerant shall be located either outdoors or where?
1104.2
The term House Piping is defined as:
Chapter 2 – Definitions
Shutoff valves must be installed at connections to which type of expansion tanks?
1205.1.6
A vented self-contained, free-standing, nonrecessed appliance for furnishing warm air to the space in which it is installed, directly from the heater without duct connections, is a:
Chapter 2 – Definitions
Where must high-pressure-steam safety valves be vented?
1006.6
In the “Standby” mode of operation for automatically controlled enclosed parking garage ventilation systems, the minimum airflow rate shall be not less than how many CFM per square foot of floor area served?
404.1
Which appliance may be installed in a sleeping room if it is a direct-vent appliance?
303.3
For electrofusion joints, joint surfaces must be clean and free from moisture, and scoured to expose what material?
1210.6.6.2
When calculating clearances for indoor air-conditioning appliances, if the furnace plenum is adjacent to plaster on metal lath, where is the clearance measured if the specified clearance is 2 inches or less?
308.3.3
Electric duct furnaces must comply with which UL standard?
911.1
Household electric ranges must be listed and labeled in accordance with which UL standard?
917.1
The category of combustible liquids does not include which of the following?
Chapter 2 – Definitions
Single-wall metal pipe shall be constructed of galvanized sheet steel not less than what minimum thickness?
503.7.1
Elevation of the ignition source is not required for appliances that are listed as being resistant to what hazard?
305.3 (Exception)
The working pressure rating of solar system components must be not less than what specific pressure?
1402.3, 5
Joints, seams, and penetrations of grease ducts must be made with a continuous liquid-tight weld or braze made on which surface of the grease duct system?
506.3.2
What is the flammability characteristic of a Class 1 refrigerant?
Chapter 2 – Definitions
The passage(s) within an appliance through which combustion products pass from the combustion chamber to the draft hood inlet opening or appliance outlet is the:
Chapter 2 – Definitions
An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer’s quality control system is a:
Chapter 2 – Definitions
If a metal ventilating hood is installed above a cooking top to reduce vertical clearance to 24 inches, the hood must be constructed of sheet metal not less than what minimum thickness?
623.7
Combustion air includes what two components?
Chapter 2 – Definitions
Which duty is authorized and directed for the code official regarding permits?
104.3
Where a draft hood is required but not supplied by the manufacturer, and no instructions are available, the installed draft hood shall be of the same size as which other appliance component?
503.12.2.1
Which repair garage is exempt from the requirement for a source capture system for motor vehicle operation?
502.14 Exception 2
In an Induced Draft system, the fan, blower, or ejector is located where?
Chapter 2 – Definitions
Safety and relief valve discharge piping shall discharge through what device located in the same room as the appliance?
1006.6
What type of hazardous production materials (HPM) are allowed to have their gas cabinet ventilation system connected to a workstation ventilation system?
502.10.1
A valve in a line shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure.
406.1.4
Construction documents, engineering calculations, diagrams, and other data shall be submitted with each application for a permit in what minimum number of sets (unless digital submission is allowed)?
106.1
For horizontal 1 1/2-inch steel pipe, what is the maximum spacing of supports permitted in feet?
415.1; Table 415.1
Use of a corridor as a source of makeup air for exhaust systems in adjacent rooms is permitted, provided the corridor is directly supplied with outdoor air at what rate?
601.2 Exception
The required level platform on a sloped roof must be not less than how many inches in any dimension?
306.5.1
If the code official determines an installation has become hazardous to life, health, or property, he or she shall order in writing that such installation either be removed or:
113.6.1
An appliance designed and installed in such a manner that all of the products of combustion are conveyed directly from the appliance to the outdoor atmosphere through an approved chimney or vent system is a(an):
Chapter 2 – Definitions
If a term is not defined through the authorized methods, what meaning shall it have?
201.4
Mechanical ventilation for indoor storage areas exceeding maximum allowable quantities shall be provided at a rate of not less than how many CFM per square foot of floor area?
502.8.1.1
The concentration of airborne contaminants that poses a threat of death or immediate/delayed permanent adverse health effects is known as what?
Chapter 2 – Definitions
For strength testing of refrigeration piping systems, the piping shall be pressurized for a minimum of how many minutes?
1110.6
Exit and exit access doorways in machinery rooms must swing in the direction of egress travel and be equipped with what, regardless of the occupant load served?
1105.9
What is the minimum clearance required above an appliance or horizontal connector where the original required clearance was 36 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
As applied to gas, the ratio of the weight of a given volume to that of the same volume of air, both measured under the same condition, is defined as:
Chapter 2 – Definitions
Heat exchangers utilizing a nonfood-grade fluid must be separated from the potable water by what means?
1402.8.4.1, 16
Appliance and equipment vent terminals must be located such that doors cannot swing within what minimum horizontal distance of the terminal?
502.7.1
Used refrigerants shall not be reused in a different owner’s equipment unless tested and found to meet the purity requirements of which AHRI standard?
1102.2.2.3
Means for interrupting the electrical supply to an air-conditioning appliance and its remote cooling tower must be provided within sight of and not over what maximum distance from the equipment?
627.1
Cleanout openings in grease ducts are required to be spaced not more than how many feet apart for sections that are inaccessible from the hood or discharge openings?
506.3.8
The standby power source and its transfer switches for a smoke control system must be enclosed with fire barriers or horizontal assemblies having what minimum fire-resistance rating?
512.11.1
In mechanically ventilated hydrogen-generating locations, equipment and appliances having an ignition source shall be located such that the source of ignition is where relative to the mechanical ventilation outlet(s)?
304.5.2
In multistory common exhaust systems for clothes dryers, the rigid metal ductwork installed within the shaft shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.471 mm), which corresponds to what gauge?
614.11
Where appliances are installed in pits or excavations, the walls of the pit or excavation must be held back not less than what distance from the appliance?
303.7
Active or engineered smoke control systems must be capable of continued operation after detection of the fire event for a period of not less than 20 minutes or what alternative duration?
512.4.6
Each buffing machine in a tire rebuilding or recapping room must be connected to a dust-collecting system that prevents what?
502.17.1
Duct cleanouts must be located at the base of each vertical duct riser and at intervals not exceeding how many feet in horizontal sections of duct conveying combustible dust?
509.7.1
For permanent ladders installed to provide roof access, what is the minimum clear width required between rails?
306.5
The side railing of a permanent ladder providing roof access must extend above the parapet or roof edge or landing platform not less than how many inches?
306.5
A Self-Contained Refrigeration System is factory-assembled and tested, and does not have refrigerant-containing parts joined in the field by other than what?
Chapter 2 – Definitions
An appliance converted from the fuel specified on its rating plate for use with a different fuel requires reapproval from whom?
1301.3
Materials that, where tested in accordance with ASTM E136, meet criteria regarding temperature rise, flaming duration, and weight loss are defined as:
Chapter 2 – Definitions
What is the maximum length of overlap allowed for overlapping grease duct joints?
506.3.2.1
What is the capacity in cfh for 1 1/4-inch nominal semirigid copper tubing at 200 feet in length, operating at less than 2 psi inlet pressure with a 1.0 in. w.c. pressure drop?
402.4; Table 402.4(12)
Where shall valves NOT be installed on a fuel oil piping system?
1305.4
Which system is an exception to the requirement that air removed by mechanical exhaust systems must be discharged outdoors?
501.3 Exception
An application for a permit shall be deemed abandoned how many days after the date of filing, unless pursued in good faith or a permit has been issued?
105.3.1
In a multistory common exhaust system, the exhaust fan must run continuously and be connected to what type of backup system?
614.11
What is the maximum overall length permitted for a listed appliance fuel connector?
411.1.3.1
Chimney connectors are prohibited from passing through which building elements?
803.10.4, 26
What is the primary function of a Control device?
Chapter 2 – Definitions
Ambient air that enters a building through a ventilation system, intentional openings for natural ventilation, or by infiltration is defined as what?
Chapter 2 – Definitions
What is the minimum clearance required from the sides and rear of an appliance where the original required clearance was 36 inches, and the protection is 0.024-inch sheet metal over 1-inch glass fiber or mineral wool batts with ventilated airspace?
308.2; Table 308.2
Hazardous exhaust systems that penetrate a floor/ceiling assembly must be enclosed in what structure?
509.6.2
A listed smoke damper designed to resist the passage of smoke shall be provided at each point that a duct or air transfer opening penetrates a fire wall or fire barrier that serves as what?
607.5.1.1, 607.5.2.1
The board of appeals shall be appointed by whom?
112.1
The allowable clearance reduction for protective assemblies can be based on a labeled protective assembly that is listed and labeled in accordance with which standard?
308.4.1
What type of firestop system is required for penetrations of a fire-resistance-rated assembly when using a field-applied grease duct enclosure?
506.3.11.2
For existing buildings identified as historic, the provisions of this code are not mandatory provided the buildings are judged to be safe and in the public interest by the:
102.6
What electrical component is required at or near equipment located on a roof or elevated structure?
306.5.2
If a notice of violation is not complied with promptly, the code official shall request the legal counsel of the jurisdiction to institute the appropriate proceeding to restrain, correct, or:
113.3
The code official shall have the authority to authorize temporary connection of a system to a utility for what purpose?
109.2
Institutional occupancy is defined as premises from which occupants cannot readily leave without the assistance of others because they are disabled, debilitated, or what other condition?
1103.2
Electric pool and spa heaters must be tested in accordance with which UL standard?
916.1
Liquid-level indicating gauges for fuel oil systems must comply with which UL standard?
1306.4
What is the Refrigerant Safety Group Classification for R-410A (R-32/125, 50.0/50.0)?
Table 1103.1
Duct coverings shall not penetrate a wall or floor required to have what specific characteristic?
604.6
Elevation of the ignition source is NOT required for appliances that are listed as what?
304.3 Exception
For pneumatic leak tests where the maximum working pressure is at or above 125 psig (862 kPa gauge), the test pressure shall be not less than what minimum percentage of the maximum working pressure?
705.3.2
Where piping passes through concrete or masonry walls, what must be provided for protection?
704.1.2.3.7
Motors driving fans in smoke control systems must have a minimum service factor of what value?
512.10.5
For an appliance installed in a dwelling unit closet, the level service space required at the service side must be not less than 30 inches (762 mm) deep and what minimum height?
306.2 Exception
Dampers provided to balance airflow in hazardous exhaust systems must have securely fixed minimum-position blocking devices to prevent restricting the flow below what two required factors?
509.5.1
The code official is authorized to require the owner or owner’s authorized agent to provide what document to determine compliance with this code?
104.2.2
Large-diameter ceiling fans must be tested and labeled in accordance with AMCA 230, listed and labeled in accordance with UL 507, and installed according to what documentation?
930.1
For compensating hoods with makeup air supplied only from the front face discharge and side face discharge openings, what labeling information is NOT required?
508.2 Exception
Appliances must be supported and connected to the piping so as not to exert undue strain on which components?
305.12
Fans providing exhaust or outdoor air in Group R-2, R-3, and R-4 occupancies shall be listed and labeled to provide the minimum required air flow in accordance with which standard?
403.3.2.5
High-probability equipment using Group A2L, A2, A3, or B1 refrigerant must comply with UL 484, UL/CSA 60335-2-40, or which other standard?
1101.2.1
Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air, except under which condition?
403.2.1
For a copper brazed swaged fitting connection with a size of 1/2 inch, what is the required minimum cup depth?
Table 1107.5.1
For an appliance to be classified as Vented, how are the products of combustion conveyed to the outdoor atmosphere?
Chapter 2 – Definitions
Shield plates used to protect clothes dryer exhaust ducts from penetration damage must be of steel material having a minimum thickness of what gauge?
504.8.1
When sizing piping using the Longest Length Method, the pipe size is determined using the longest length of piping from the point of delivery to which point?
402.4.1
What is the minimum testing standard for electric residential clothes dryers?
913.1
A pressure regulator for controlling pressure to the manifold of the appliance is a:
Chapter 2 – Definitions
What is the minimum clearance required for radiant panels from an element when mounted on wood or steel framing?
927.3
A ventilation opening into a sauna room shall be provided, and the opening must be not less than what minimum size?
615.7
If the depth of an appliance pit or excavation exceeds 12 inches (305 mm) below adjoining grade, the pit walls must be lined with concrete or masonry extending not less than how far above adjoining grade?
303.7
Unfired pressure vessels having a volume of 5 cubic feet or less operating at pressures not exceeding 250 psi (1724 kPa) are exempt if located in all of the following occupancies EXCEPT:
1001.1 Exceptions
Household cooking appliances shall have a vertical clearance above the cooking top of not less than 30 inches (760 mm) to combustible material and metal cabinets, unless the clearance is reduced to 24 inches (610 mm) and what minimum thickness of insulating millboard is used for protection?
623.7
Pipe and duct insulation contained within plenums shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C411 at what minimum temperature?
602.3.9
Where vibration isolation of equipment and appliances is employed, what means shall be used to accomplish the required support and restraint?
301.13
Underground ducts must have a minimum slope to allow drainage to a point provided with access of not less than what slope?
603.8.1
How shall the depth of an opening below grade be measured for natural ventilation requirements?
402.4
If a grease duct is large enough for personnel entry, what are the minimum dimensions required for the approved opening in horizontal sections?
506.3.8.1
What is the minimum clearance required from the sides and rear of a single-wall metal pipe where the original required clearance was 18 inches, and the protection is 1-inch glass fiber or mineral wool batts sandwiched between two sheets of 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
A gas-tight joint obtained by the joining of metal parts in molten state is a:
Chapter 2 – Definitions
Where a closet is designed for a clothes dryer, what is the minimum area required for the opening in the closet enclosure for makeup air?
504.7
Where a separate means is used to supply ventilation air to a direct-fired industrial air heater, what must be provided to ensure the main burner does not operate without the air supply?
612.5
Every steam boiler must have a pressure gauge and what other component?
1010.2
Which of the following pressure vessels are exempt from the scope of Chapter 10?
1001.1 Exceptions
For connection to a masonry fireplace flue, the connector shall extend from the appliance such that the flue gases are exhausted directly into the flue, and the connector must be provided with access or be what?
801.10.3, 6
For a structure with a previously issued lawful permit, construction must have been pursued in good faith within how many days after the effective date of this code to avoid requiring changes?
105.4.6
When utilizing the airflow design method for smoke control, the airflow toward the fire shall not exceed what maximum velocity?
512.7.1
How long shall the code official retain one set of approved construction documents after the date of completion of the permitted work?
106.2
A pilot that operates during the lighting cycle and discontinues during main burner operation is a(an):
Chapter 2 – Definitions
Mechanical systems that are part of structures moved into or within the jurisdiction shall comply with provisions for which type of installations?
102.7
What type of valve is a Safety Valve used in a steam boiler?
Chapter 2 – Definitions
If a code provision is less restrictive than the conditions of the listing or the manufacturer’s instructions, which provisions shall apply?
304.2 Exception
The issuance of a permit or construction documents approval shall not be construed to be a permit for or an approval of any:
105.5.2
The connector shall not be smaller than what dimension provided by the appliance manufacturer?
803.3, 20
In a multistory common exhaust system, the finished cleanout opening located at the base of the shaft must be not less than what minimum size?
614.11
A valve requiring one-quarter round turn or less to open completely is considered to be what type of valve?
Chapter 2 – Definitions
Where demand-controlled ventilation is employed, the minimum quantity of outdoor air shall not fall below that determined from which column of Table 403.3.1.1?
403.3.1.3
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than what maximum degree from vertical at any point in the assembly?
805.4, 38
The treatment of air so as to control simultaneously the temperature, humidity, cleanness and distribution of the air to meet the requirements of a conditioned space is defined as:
Chapter 2 – Definitions
A Combination Fire/Smoke Damper must be capable of being positioned from where?
Chapter 2 – Definitions
Temporary uses, equipment, and systems shall conform to the requirements of this code as necessary to ensure what?
110.2
Where enclosures are not required, what is the minimum clearance required from noncombustible construction and gypsum wallboard attached to noncombustible structures for Type I hood grease duct systems?
506.3.6
Permit fees for work requiring a permit shall be paid in accordance with the schedule established by the:
108.2
Installations that are part of buildings moved into or within the jurisdiction shall comply with the provisions for:
102.7
Steam boilers must be protected with which type of safety device?
1006.1
In a return air system, where must the smoke detector be installed relative to filters, exhaust air connections, and outdoor air connections?
606.2.1
A heater in which all the products of combustion generated by the burners are released into the air stream being heated, with the purpose of offsetting building heat loss by heating only outdoor air, is a:
Chapter 2 – Definitions
For naturally ventilated hydrogen-generating operations, where must the upper of the two required permanent openings be located?
304.5.1.1
Shutoff valves shall be installed at connections to which type of expansion tank in ground-source loop piping systems?
1210.7.6
For flammable vapor areas, the spraying equipment shall be interlocked with the ventilation such that spraying operations cannot be conducted unless the ventilation system is in operation. This system must be kept in operation until when?
502.7.3.1
For fuel-burning units, the required label information includes the hourly rating in Btu/h (W), the required clearances, and what specific fuel detail?
301.9
Connecting offices, waiting rooms, ticket booths, and similar uses accessory to a public garage must be maintained at what specific pressure condition?
404.2
An air dispersion system is a diffuser system designed to convey air and diffuse air into a space while operating under what pressure characteristic?
Chapter 2 – Definitions
What is the minimum separation distance required for the atmospheric venting of Compressed Natural Gas (CNG) from buildings?
413.10.2.3; Table 413.10.2.3
If a code provision is less restrictive than the conditions of the equipment listing, which requirement shall apply?
305.1
Joints between CPVC plastic pipe or fittings for ground-source heat pump systems must be what two specific types of joints?
1210.6.4
When two or more appliances are connected, what is the maximum horizontal length permitted for a 7-inch diameter connector?
504.3.2; Table 504.3.2
The content of a technical opinion and report shall analyze the properties of the design, operation, or use of the building or premises to identify and propose what?
104.2.2.3
A heater in which all the products of combustion generated by the burners are released into the air stream being heated, with the purpose of offsetting building heat loss by heating outdoor air, and, if applicable, indoor air, is a:
Chapter 2 – Definitions
In System A for combustible wall pass-through, what is the required clearance to combustibles?
Table 803.10.4, 27
Plenums shall be limited to uninhabited crawl spaces, above a ceiling or below the floor, attic spaces, mechanical equipment rooms, and what other construction features?
602.1.1
When interpreting this code, words used in the masculine gender shall be construed to include which other gender(s)?
201.2
A Welded Joint is a gastight joint obtained by joining metal parts in what state?
Chapter 2 – Definitions
Air being removed from any space, appliance, or piece of equipment and conveyed directly to the atmosphere by means of openings or ducts is known as what?
Chapter 2 – Definitions
When using compression-type mechanical joints on plastic piping, an internal tubular rigid stiffener shall be used and must be located flush with which part of the pipe?
403.1
Appliances installed in pits or excavations shall be installed not less than how many inches above the pit floor?
303.7
Recirculating direct-fired industrial air heaters shall be listed to which standard?
612.1
Additions, alterations or repairs shall not cause an existing installation to become:
102.4
Hydrogen piping systems shall be marked with the name of the contents and a direction-of-flow arrow at intervals not exceeding what maximum distance?
704.1.2.2
What must an organization concerned with product evaluation maintain for the Labeled items?
Chapter 2 – Definitions
Who must be notified prior to making a change of refrigerant in an existing system to a refrigerant with a different refrigerant designation?
1101.7
Electrical wiring, controls, and connections to equipment and appliances regulated by this code must be in accordance with which standard?
301.1
A change in a system that involves an extension, addition or change to the arrangement, type or purpose of the original installation is a(an):
Chapter 2 – Definitions
For equipment with a capacity over 20 tons up to 40 tons of refrigeration, what is the minimum required condensate pipe diameter?
Table 307.2.2
Boilers shall be designed, constructed, and certified in accordance with the ASME Boiler and Pressure Vessel Code, Section I or which other section?
1004.1
What is the closed cup flash point range for Class II Combustible Liquids?
Chapter 2 – Definitions
Ventilation in dry cleaning plants must be adequate to protect employees and the public in accordance with this section and which other referenced standard, where applicable?
502.6
What is the capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(5)
What is excluded from being construed as air ducts in the definition of a Duct?
Chapter 2 – Definitions
A blower or fan used for the purpose of distributing supply air to a room, space or area is a(an):
Chapter 2 – Definitions
The flash point of transfer fluid in a hydronic piping system shall be not less than what minimum temperature above the maximum system operating temperature?
1207.1
A space is considered indirectly heated or cooled if it is separated from conditioned spaces by what specific feature?
Chapter 2 – Definitions
For each elbow up to and including 45 degrees in the common vent of a multiple appliance system, the maximum common vent capacity must be reduced by what percentage?
504.3.6
Condensate pumps located in uninhabitable spaces, such as attics and crawl spaces, must be connected to the appliance served such that when the pump fails, the appliance will be prevented from what?
307.3
The vent termination point for a horizontal mechanical draft system shall not be located closer than what minimum distance to an interior corner formed by two perpendicular walls?
804.3.4, 33
What is the minimum clearance to combustibles required for connectors serving oil and solid-fuel domestic-type appliances?
Table 803.10.6, 30
Fasteners used to join domestic dryer exhaust ducts are prohibited from protruding more than what maximum distance into the inside of the duct?
614.9.2
Air removed by mechanical exhaust systems shall not be exhausted into an attic, a crawl space, or be directed onto what other location?
501.3
A shaft enclosure for a grease duct must be sealed around the grease duct at the point of penetration and vented to the outside of the building through what means?
506.3.11.1
What is the capacity in thousands of Btu/h for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(27)
Who is responsible for furnishing the apparatus, instruments, material, and labor required for testing an installation?
111.3.2
What is the minimum diameter for a Large-Diameter Ceiling Fan?
Chapter 2 – Definitions
A Permanent Mechanical Joint that incorporates an elastomeric seal and corrosion-resistant grip or bite ring is called a what?
Chapter 2 – Definitions
Which type of vent is listed and labeled for use with appliances with draft hoods and other Category I appliances that are listed for use with that specific vent type?
Chapter 2 – Definitions
The procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements is defined as:
Chapter 2 – Definitions
An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn which type of fuel?
503.5.7.1
For existing buildings located in flood hazard areas undergoing reconstruction or repair, the code official shall determine if the proposed work constitutes substantial improvement or what?
104.3.1
A Pellet Fuel-Burning Appliance is equipped with what type of mechanism for burning processed pellets of solid fuel?
Chapter 2 – Definitions
A burner designed to supply gaseous fuel to an appliance originally designed to utilize another fuel is known as what?
Chapter 2 – Definitions
What is the minimum clearance required on the control side of a floor furnace?
910.4
A manual or automatic device designed to regulate the gas, air, water or electrical supply to, or operation of, a mechanical system is a:
Chapter 2 – Definitions
Materials, equipment, and devices may be reused only if they are in good working condition and:
104.9.1
One set of approved construction documents shall be retained by the code official for a period of not less than how many days from the date of completion of the permitted work?
106.2
In the brazing process, how is the filler material distributed between the closely fitted surfaces of the joint?
Chapter 2 – Definitions
The inside lower edge of canopy-type Type I and II commercial hoods must overhang or extend a horizontal distance of not less than how many inches beyond the edge of the top horizontal surface of the appliance on all open sides?
507.1.6.1
Chimneys shall extend not less than what minimum vertical distance above the highest connected appliance draft hood outlet or flue collar?
503.5.4
Which type of system is exempt from the requirement for an expansion tank in a hot water system?
1009.1 Exception
Fuel gas devices, equipment, and appliances used with refrigeration systems must be installed in accordance with which code?
1101.5
Heat-fusion joints for polyethylene pipe used in ground-source loops must be joined in accordance with which ASTM standard?
1210.6.6.1
The term that refers to a blower or fan used for the purpose of distributing supply air to a room, space, or area is what?
Chapter 2 – Definitions
Requirements for gas appliances and related accessories must include installation, venting, connections to piping systems, and:
101.2.4
What is the primary purpose of a Chimney?
Chapter 2 – Definitions
The use of what medium is prohibited when removing debris from the interior of a piping system?
404.18
Each individual radiant tubing circuit must have a tag or label affixed to each manifold outlet to indicate the areas served and what other specific information?
1209.6.2
Which vented appliance category operates with a nonpositive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent?
Chapter 2 – Definitions
What is the minimum clearance required above an appliance where the original required clearance was 12 inches, and the protection is 0.024-inch sheet metal with ventilated airspace over 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
What is the capacity in thousands of Btu/h for 2-inch nominal Schedule 40 metallic pipe at 500 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 3.0 psi pressure drop?
402.4; Table 402.4(26)
A record of approvals shall be maintained by the code official and made available for public inspection during business hours in accordance with:
104.7.1
Chimneys for medium-heat appliances shall extend not less than what horizontal distance higher than any portion of any building within 25 feet?
503.5.4
When calculating the minimum required volume using the Known Air-Infiltration-Rate Method (304.5.2), what is the maximum air infiltration rate (ACH) that shall be used in the equations?
304.5.2
In a High-Probability System, leakage of refrigerant from a failed connection will enter where?
Chapter 2 – Definitions
The cutting, notching, and boring of holes in structural steel framing members shall be as prescribed by whom?
302.5.1
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 18 inches, and the protection is 3 1/2-inch-thick masonry wall without ventilated airspace?
308.2; Table 308.2
Common venting systems for appliances located on more than one floor level are prohibited, except where all served appliances are located in rooms that are accessed only from where?
801.19, 14
Appliances using forced draft venting and incorporating integral venting means must maintain what minimum clearance between vent terminals and openings through which combustion products enter the building?
804.2.1, 31
Factory-built fireplaces must be listed and labeled and tested in accordance with which UL standard?
903.1
What is the maximum capacity in cfh for 4-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(2)
Which type of thermostat is an automatic device, actuated by temperature changes, in which the thermal actuating element is an integral part of the device?
Chapter 2 – Definitions
A wall, floor, ceiling or other assembly constructed of one or more component materials that are not defined as noncombustible is a:
Chapter 2 – Definitions
A venting system designed to remove flue or vent gases under nonpositive static vent pressure entirely by natural draft is a:
Chapter 2 – Definitions
System components that might be subjected to a vacuum during operation or shutdown must either be designed to withstand such vacuum or be protected with what?
1402.3.2, 6
A Floor Furnace takes air for combustion from where?
Chapter 2 – Definitions
Flue lining systems for use with residential-type and low-heat appliances must resist flue gases and condensate at temperatures up to what maximum temperature?
501.12
Equipment and ductwork for exit enclosure ventilation located exterior to the building must be directly connected to the exit enclosure by ductwork enclosed in construction as required by the International Building Code for what purpose?
601.3
Tapes and mastics used to seal fibrous glass ductwork must be listed and labeled in accordance with which UL standard?
603.9
Reduced clearance protective assemblies, including structural and support elements, must be constructed of what type of material?
308.3
If an attic passageway is unobstructed and not less than 6 feet (1829 mm) high and 22 inches (559 mm) wide, what is the maximum length allowed?
306.3 Exception
Once issued, approved construction documents shall not be changed, modified, or altered without authorization from the:
105.5.1
What is the capacity in thousands of Btu/h for 1/2-inch nominal copper tubing (K & L) at 500 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(29)
Where must the makeup air supply system for a commercial kitchen be automatically controlled to start and operate?
508.1
For natural gas calculations using the equation factors listed, what is the value designated as Y?
402.4; Table 402.4
Refrigerants reprocessed to the same specifications as for new refrigerants by means including distillation are classified as what?
Chapter 2 – Definitions
Equipment and appliances having an ignition source and located in private garages must be elevated such that the source of ignition is not less than how many inches above the floor surface?
304.3
Which of the following piping materials is listed in Table 1107.4 for use as refrigerant pipe?
Table 1107.4
A person shall not make energy source connections to mechanical systems that have been disconnected or ordered to be discontinued until whom authorizes the reconnection and use?
114.6.3
What must oil-fired appliances be equipped with to stop burner operation if the venting system is obstructed?
801.21, 15
Grease filters must be installed at a minimum angle of how many degrees from the horizontal?
507.2.8.2
What is the capacity in thousands of Btu per hour for 1/2-inch nominal O.D. Polyethylene plastic tubing (SDR 7) at 200 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(37)
When sizing a single appliance vent where the maximum capacity determined from the tables is used, and an additional elbow up to and including 45 degrees is added, the maximum capacity listed must be reduced by what percentage?
504.2.3
In addition to being experienced in conducting and supervising tests, personnel employed by an approved agency must be educated in evaluating what?
301.8.2.3
The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used for what purpose?
801.17, 10
Where a combination system requires water for space heating at temperatures higher than 140F, a temperature-actuated mixing valve conforming to ASSE 1017 must be provided to temper the potable hot water distribution system water to what maximum temperature?
1002.2.2
For natural ventilation in hydrogen-generating locations, the maximum rated output capacity of hydrogen-generating appliances shall not exceed 4 standard cubic feet per minute (0.00189 m3/s) of hydrogen for each how many square feet of floor area?
304.5.1
According to Table 1009.2, what is the required pressurized diaphragm type expansion tank capacity in gallons for a system volume of 2,000 gallons?
Table 1009.2
What is the minimum clearance required between a single-wall metal pipe connector and combustible material when serving a residential boiler with a listed gas conversion burner and a draft hood?
503.10.5; Table 503.10.5
Soft annealed copper tubing larger than what outside diameter shall not be used for field-assembled refrigerant piping unless it is protected from mechanical damage?
1107.4
Apparatus and devices other than appliances are defined as:
Chapter 2 – Definitions
A water-level detection device conforming to UL 508 must be provided to shut off the equipment served if installed in which location?
307.2.3
What is the minimum clearance required from the sides and rear of a single-wall metal pipe where the original required clearance was 6 inches, and the protection is 0.024-inch sheet metal with ventilated airspace over 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
Temporary uses, equipment, and systems must conform to the requirements of this code as necessary to ensure health, safety, and:
110.2
Unless ready access is provided for complete inspection at the site, in-plant inspections of prefabricated systems shall be conducted by the code official or an independent, approved inspection agency to ensure conformance to the approved evaluation report.
111.2.5.2
What is the minimum distance required between the lowest edge of a grease filter and an exposed charcoal and charbroil type cooking surface?
Table 507.2.8
The design and operation of a hazardous exhaust system must ensure that flammable contaminants are diluted to maintain concentrations in the exhaust flow below what percentage of the contaminant’s lower flammability limit (LFL)?
509.3
Ducts for domestic cooking exhaust equipment must be constructed of sheet metal and equipped with what flow control device?
505.3
For Type IV and V dry cleaning systems, the automatically activated exhaust ventilation system must maintain a minimum air velocity of not less than how many feet per minute through the loading door when the door is opened?
502.6.2
Where a vent connector for a Category I appliance with a draft hood passes through an unconditioned space (like an attic) in an area with a 99-percent winter design temperature of 5°F or higher, which type of pipe is permitted to be used within the exterior walls?
503.10.2.2 (Exception)
Where one chimney flue serves gas appliances and liquid fuel-burning appliances, and two or more openings are provided into the flue, they must be located at different:
503.5.7.2
When an automatically operated fuel-burning appliance is in operation, an Automatic Vent Damper Device is designed to perform what action?
Chapter 2 – Definitions
Duct furnaces shall be listed in accordance with which ANSI/CSA or UL standard?
610.1
Refrigerant circuit access ports located outdoors must be fitted with what type of cap?
1101.9
When testing at a pressure of 10 psig (68.95 kPa gauge) or less, the testing gauge must have increments of what maximum amount?
705.3.6
Air being removed from any space or piece of equipment or appliance and conveyed directly to the atmosphere by means of openings or ducts is defined as:
Chapter 2 – Definitions
Brazed joints in fuel oil piping systems must use a filler metal conforming to which AWS standard?
1303.3.1
A hearth and fire chamber of solid masonry units or reinforced concrete, provided with a suitable chimney, is a:
Chapter 2 – Definitions
Air transferred from occupiable spaces is permitted to serve as makeup air for required exhaust systems in spaces such as kitchens, baths, toilet rooms, elevators, and which other space?
403.2.2
If the Maximum Primary Outdoor Air Fraction [$Max (Z_p)$] for a multiple zone recirculating system is 0.15 or less, what is the System Ventilation Efficiency ($E_v$)?
Table 403.3.1.1.2.3.2
When replacing an existing heating appliance serving an occupied portion of a structure, a request for inspection must be filed with the department within how many hours after replacement work is completed to avoid prohibiting the operation of the appliance?
111.2
In a Low-Probability System, where will a leakage of refrigerant from a failed connection NOT enter?
Chapter 2 – Definitions
What type of clearance must chimneys and vents have to combustibles, according to the International Building Code and manufacturer’s instructions?
801.18.4, 13
What inert gas must be used to purge air from piping being brazed to remove oxygen?
1108.3.1
What is the purpose of a Flue Liner (Lining)?
Chapter 2 – Definitions
Hydrogen piping located inside of buildings must be installed in exposed locations and provided with ready access for visual inspection, except for which condition?
704.1.2.3.2
Exemption from the permit requirements of this code shall not be deemed to grant authorization for work to be done in violation of what?
105.2
During occupied conditions, the normal mechanical ventilation system must exhaust not less than 0.5 cfm per square foot (0.0025 m3/s × m2) of machinery room area or what other minimum rate per person?
1105.6.3.1
The use of ventilating hoods and exhaust systems to vent appliances is generally limited to industrial appliances and appliances installed in which type of application?
503.2.1
What is the maximum capacity in thousands of Btu/h for 4-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, for undiluted propane operating at 10.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(25)
For an MP regulator located indoors, what device must be equipped if the regulator is not vented to the outdoors?
410.2
For intake openings in residential occupancies, the minimum opening size in louvers, grilles, and screens must be greater than or equal to what dimension?
Table 401.5
What is the maximum length allowed for a transition duct connecting a domestic dryer to the exhaust duct system?
504.9.3
Every hot water boiler must have which two gauges, or a combination gauge?
1010.1
A Unit Heater is designed for the delivery of warm air where?
Chapter 2 – Definitions
What must be provided in an attic passageway to an appliance, which must be not less than 24 inches (610 mm) wide?
306.3
A hand-operated device that provides a means for connecting and disconnecting an appliance or an appliance connector to a gas supply and is equipped with an automatic means to shut off the gas supply when disconnected is a:
Chapter 2 – Definitions
Where single-wall metal pipe passes through a combustible exterior wall serving a listed appliance with a draft hood, the ventilated metal thimble must be not less than 4 inches larger in diameter than the metal pipe, unless a minimum horizontal pipe run of 6 feet is provided in the open, in which case the thimble can be not less than how much larger in diameter than the metal pipe?
503.7.7
A vented appliance designed for installation within the fire chamber of a vented fireplace, wherein the primary function lies in the aesthetic effect of the flames, is defined as a:
Chapter 2 – Definitions
A permanently mounted, manually operated device that provides the means for connecting and disconnecting an appliance to the supply piping, and is designed so that disconnection only occurs when the manually operated valve is in the closed position, is a:
Chapter 2 – Definitions
A water spray test performed on a grease duct system must use a water pump capable of a flowing outlet pressure of not less than how many PSI?
506.3.2.5.2
Shutoff valves are not required in the supply and return piping for a system having which specific type of boiler?
1005.1 Exception
Return air for heating or air-conditioning systems shall not be taken from which two types of locations?
601.5
What creates the pressure difference in a Natural Draft system?
Chapter 2 – Definitions
Energy recovery ventilation systems shall not be used in commercial kitchen exhaust systems serving which type of hood?
513.2
What is the capacity in cfh for 3-inch nominal Schedule 40 metallic pipe at 1,500 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(7)
If equipment replacements or repairs must be performed in an emergency situation, the permit application shall be submitted within what timeframe?
105.1 Exception
Variable air volume air distribution systems, other than those supplying 100-percent outdoor air, must be provided with controls to regulate the flow of outdoor air to maintain the flow rate at not less than that required by what section?
403.3.1.4
The aggregate input rating of all unvented appliances installed in a room or space shall not exceed what maximum Btu/h per cubic foot of volume of such room or space?
621.5
The total horizontal distance of a vent plus the horizontal vent connector serving draft-hood-equipped appliances shall be not greater than what percentage of the vertical height of the vent?
503.6.10.2
Remote control of refrigeration compressors, refrigerant pumps, and normally closed, automatic refrigerant valves located in the machinery room must be provided by a clearly identified switch of the break-glass type or with what other device?
1106.5.1
What is the maximum input rating allowed for a single wall-mounted unvented room heater installed in a bedroom?
303.3
What test medium is prohibited from use when pressure testing gas piping systems?
406.2
Scrubbing tubs, scouring, brushing or spotting operations in dry cleaning plants must be located such that solvent vapors are captured and exhausted by which system?
502.6.3
For all environmental air exhaust, what is the minimum termination distance from mechanical air intakes?
501.3.1
A system or material used to form the inside surface of a flue in a chimney or vent, for the purpose of protecting the surrounding structure and conveying combustion products without leakage, is a:
Chapter 2 – Definitions
Equipment and appliances installed at grade level must be supported on a level concrete slab or other approved material extending not less than what distance above adjoining grade?
305.7
Semirigid conduit of copper, copper-alloy aluminum, plastic or steel is defined as:
Chapter 2 – Definitions
For smoke control systems using the exhaust method in large enclosed volumes, the height of the lowest horizontal surface of the accumulating smoke layer must be maintained not less than how many feet above any walking surface that forms a portion of a required egress system?
512.8.1
Which of the following is NOT one of the rooms or spaces from which fuel-fired appliances shall not obtain combustion air?
303.3
Flexible connectors, expansion, and vibration control devices and fittings must be of what specific characteristic?
1202.7
Refrigeration systems containing more than what weight of refrigerant require additional stop valves at locations like the inlet of each liquid receiver?
1109.6.2
A joint made in thermoplastic piping by heating the parts sufficiently to permit fusion of the materials when the parts are pressed together is a:
Chapter 2 – Definitions
Raised face flanges shall not be joined to which type of flat-faced flange?
403.11.5
What is the maximum acceptable flame spread distance for combustible electrical wires and cables exposed within a plenum when tested in accordance with NFPA 262?
602.3.3
Appliances such as coffee brewers and coffee urns, food and dish warmers, hot plates, griddles, and waffle bakers designed for installation on or in a counter are defined as:
Chapter 2 – Definitions
If a notice of violation is not complied with promptly, the code official shall request legal counsel to institute appropriate proceedings at law or in equity to perform what action?
114.3
A mechanical system that is unsafe, constitutes a fire or health hazard, or is otherwise dangerous to human life is declared to be what?
114.6
What is the capacity in cfh for 1/2-inch nominal Schedule 40 metallic pipe at 700 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(4)
Condensate drains shall not discharge into a plumbing fixture other than a floor sink, floor drain, trench drain, mop sink, hub drain, standpipe, utility sink or which other sink type?
307.2.1.1
A device responsive to changes in pressure, temperature or level for turning on, shutting off or throttling the gas supply to an appliance is a:
Chapter 2 – Definitions
The imposition of violation penalties shall not preclude the legal officer of the jurisdiction from instituting appropriate action to prevent what?
114.5
Connectors shall connect to a chimney flue at a point not less than how many inches above the lowest portion of the interior of the chimney flue?
801.12, 7
The fuel gas piping, valves and fittings from the outlet of the point of delivery to the outlets of the appliance shutoff valves is defined as the:
Chapter 2 – Definitions
Permanently installed electric space heaters must be listed and labeled in accordance with which UL standard?
912.1
Where vents pass through attic space, the insulation shield must terminate not less than what vertical distance above the insulation materials?
502.4
Forced draft systems and portions of induced draft systems under positive pressure must be designed and installed to be what characteristic to prevent leakage of combustion products?
804.3.1, 32
After prescribed tests and inspections indicate the work complies, who shall issue a notice of approval?
107.1
Nonrecirculating direct-fired industrial air heaters shall be listed to which standard?
611.1
Truss members and components shall not be cut, drilled, notched, spliced, or otherwise altered without whose written concurrence and approval?
302.4
Electrical connections between appliances and building wiring, including grounding of the appliances, must conform to which standard?
309.2
A Positive Displacement Compressor achieves an increase in pressure by changing what component?
Chapter 2 – Definitions
Permanently fixed-in-place outdoor decorative appliances shall be listed in accordance with which ANSI standard?
635.1
In fuel-dispensing areas, the bottom of an air inlet or exhaust opening shall be located not more than how many inches above the floor?
502.1.2
Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), where must the permanent label or tag identifying the length be located?
504.9.5
Equipment, appliances, and supports that are exposed to wind must be designed and installed to resist wind pressures determined in accordance with which code?
301.15
What is the maximum temperature for hot water furnished by a Low-Pressure Hot-Water-Heating Boiler?
Chapter 2 – Definitions
Packaged oil-fired boilers must be listed and labeled in accordance with which UL standard?
1004.1
What is the maximum pressure for a low-pressure boiler supplying hot water?
Chapter 2 – Definitions
For a single-appliance venting configuration, if the height (H) is less than 6 feet or greater than shown in the tables, what method must be used to calculate the vent capacity?
504.2.16
A device that functions to maintain a desired draft in the appliance by automatically reducing the draft to the desired value is a:
Chapter 2 – Definitions
What is an alternative term sometimes used for Lower Flammable Limit (LFL)?
Chapter 2 – Definitions
What is the minimum openable area to the outdoors required for natural ventilation of an occupied space?
402.2
Materials, equipment, and devices approved by the code official shall be constructed and installed in accordance with what?
104.9
Which vented appliance category operates with a positive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent?
Chapter 2 – Definitions
To verify compliance with listing standards, the listing standard and manufacturer’s instructions shall be made available to the code official when required to verify:
104.2.1
Condensate waste and drain line size shall be not less than what minimum pipe size?
307.3
Where refrigerants of Groups A2, A3, B2, and B3 are used, the machinery room must conform to what hazardous location classification requirements of NFPA 70?
1106.3
When the free area of a louver or grille is not known, what percentage free area shall be assumed for metal louvers and grilles?
304.5.1.2
Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where what occurs?
304.4
Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances is defined as what?
Chapter 2 – Definitions
Which valve controls the gas supply to the main burner manifold?
Chapter 2 – Definitions
The person to whom an annual permit is issued shall keep a detailed record of alterations made under such permit that shall be accessible to the code official at all times or:
105.1.2
For a single appliance vented by a masonry chimney using a Type B double-wall connector (Table 504.2(3)), if the height (H) is 15 feet and the lateral (L) is 15 feet, what is the minimum input rating (FAN Min) for a 9-inch diameter connector?
504.2; Table 504.2(3)
If there is insufficient evidence of compliance with the provisions of this code, the code official shall have the authority to require what as evidence of compliance?
104.2.2.4
What must be excluded from use when calculating required clearances to combustibles?
304.9
What is a device that transfers heat from one medium to another?
Chapter 2 – Definitions
Approved plastic pipe or tubing for heating panels embedded in concrete must be rated at 100 psi (689 kPa) at what specific temperature?
1209.1
Factory-built chimneys for appliances that operate at a positive vent pressure must be listed for such application in accordance with which UL standard?
503.5.1
Field drilling and tapping of pipe fittings must only be performed on systems having operating pressures of what maximum amount?
403.9.5
What phenomenon is NOT listed as a cause of pressure differences resulting in infiltration?
Chapter 2 – Definitions
Hydrogen Generating Appliances utilize which of the following processes to generate gaseous hydrogen?
Chapter 2 – Definitions
Approved construction documents shall not be changed, modified, or altered without authorization from whom?
105.4.1
If actual flow rate or pressure drop values in a ground-source loop system test differ from calculated design values by more than what percentage, must the cause be identified and corrective action taken?
1210.1
What must be done to abandoned inlet openings in chimneys and vents?
801.8
Which fluid is explicitly excluded from the definition of Heat Transfer Liquid?
Chapter 2 – Definitions
A pressure regulator set in series with another pressure regulator for the purpose of preventing an overpressure in the downstream piping system is a:
Chapter 2 – Definitions
Who is responsible for the maintenance of mechanical systems?
102.3
For multiple-appliance common venting systems, where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced, and the horizontal length of the offset shall not exceed 1 1/2 feet for each inch of which component diameter?
504.3.5
If a person violates a provision of this code after due notice has been served, how is the continuation of that violation measured?
114.4
Where the scope of a referenced standard includes subject matter also within the scope of this code, the provisions of this code shall:
102.8.2
What Zone Air Distribution Effectiveness is permitted for systems with a floor supply of cool air and ceiling return, provided displacement ventilation achieves unidirectional flow and thermal stratification?
Table 403.3.1.1.1.2 Note e
What is the maximum operating pressure allowed by these regulations for natural gas piping systems?
101.2.3
Solid-fuel-fired water heaters must comply with which UL standard?
1002.1
The abbreviation for British thermal unit is:
Chapter 2 – Definitions
What is the minimum clearance required above an appliance where the original required clearance was 18 inches, and the protection is 1/2-inch insulation board with ventilated airspace?
308.2; Table 308.2
Stud wall cavities utilized as air plenums shall not convey air from more than how many floor levels?
602.2.1
Documentation of the final decision of the code official regarding modifications shall be kept in the official records and shall be in what format?
104.7.3
An indirect open-spray system is not required to be classified as a high-probability system if the pressure of the secondary coolant is at all times greater than what other pressure?
1103.3.2 Exception
What does this document establish to provide a reasonable level of safety, health, property protection and general welfare?
101.3
Solid fuel furnaces must be tested in accordance with which UL standard?
918.1
The assembled ground-source loop system must be pressure tested with water at 100 psi (689 kPa) for a minimum of how long before backfilling connection header trenches?
1210.1
An alternative material, design, or method of construction must comply with:
104.2.3.3
For permanent ladders installed to provide roof access, what is the maximum spacing allowed for rungs on center?
306.5
How many members shall the board of appeals consist of?
113.1
A low-water cutoff is not required for coil-type and water-tube-type boilers that require forced circulation, provided they are protected with what specific control?
1007.1 Exception
Which type of temperature relief valve automatically opens a relief vent at a predetermined temperature and must be manually returned to the closed position?
Chapter 2 – Definitions
Which decorative appliance is exempt from the requirement to use a flame safeguard device?
602.2
The code official is authorized to give permission for temporary service utilities in accordance with which section?
110.3
An attic passageway that is not less than 6 feet high for its entire length shall be not greater than what maximum length?
306.3 (Exception 2)
Air distribution, ventilation, and exhaust systems must be provided with means to adjust the system to achieve the design airflow rates and shall be balanced by what method?
608.1
If the vapor concentration monitor shuts down during unmanned spray operations where recirculation is permitted, what volume of air specified in Section 509 must be automatically exhausted?
502.7.3.2 Exception 1
Which types of equipment or appliances require condensate drain systems?
307.2
For a roof slope of Flat to 6/12, what is the minimum required vertical height (H) above the roof to the lowest discharge opening?
503.6.5; Figure 503.6.5 (Table)
Required ventilation systems for dip tank operations shall be arranged such that the failure of any ventilating fan will automatically stop what component?
502.7.4
Where must the exhaust from stationary local contaminant sources discharge?
401.6
A condition where thermal energy is not transferred from a solar thermal collector by means of the flow of a heat transfer fluid is known as what?
Chapter 2 – Definitions
The code official is authorized to issue an annual permit for alterations to an already approved system to any person, firm, or corporation regularly employing how many qualified tradespersons?
105.1.1
Protective assemblies shall not be placed less than how many inch(es) from the mechanical appliances, devices, or equipment?
308.3
Which type of LP-gas appliances and equipment is generally outside the scope of this code?
101.2.5
Gas piping is prohibited from being used as which type of electrical component?
309.1
Where recirculation of air from a space is prohibited (Note b, Table 403.3.1.1), all air supplied to such spaces, including air in excess of that required, shall be what?
403.2.1
Which types of copper or copper-alloy tube (Type K, L or M) are listed as acceptable piping materials in Table 1202.4?
Table 1202.4
What are prohibited from being exhausted through the same hazardous exhaust system?
509.4
Official records related to this code shall be retained for not less than 5 years or for as long as:
104.7
When using Type B double-wall gas vent connected directly to a single Category I appliance, if the vent height (H) is 6 feet and the vent diameter (D) is 4 inches, what is the maximum input rating (NAT Max) for a Natural Draft appliance?
504.2; Table 504.2(1)
For a single draft-hood-equipped appliance connected directly to a single-wall metal pipe (Table 504.2(5)), if the vent height (H) is 20 feet and the lateral (L) is 15 feet, what is the maximum input rating in thousands of Btu/h for a 7-inch diameter vent?
504.2; Table 504.2(5)
A Pressure Relief Valve is held closed by a spring or other means and designed to relieve pressure automatically in excess of what?
Chapter 2 – Definitions
The maximum horizontal length of a single-wall connector shall be what percentage of the height of the chimney or vent?
503.10.9
Exhaust ducts for domestic clothes dryers must be constructed of metal with a minimum thickness of how many inches?
504.9.1
A record of approvals shall be maintained by the code official and shall be available for public inspection during business hours in accordance with what?
104.7.1
Where connecting an appliance to a masonry fireplace flue, the connector must be designed to allow access or be removable for inspection and cleaning of both the connector and the flue.
501.7.3
Solar thermal systems must be listed and labeled in accordance with which standard?
1401.4, 4
Factory-built chimneys installed in dwelling units with solid fuel-burning appliances must comply with the Type HT requirements of which UL standard?
805.2, 37
Gas composed predominately of propane, propylene, butanes or butylenes, or mixtures thereof that is gaseous under normal atmospheric conditions, but is capable of being liquefied under moderate pressure at normal temperatures, is defined as:
Chapter 2 – Definitions
Mechanical ventilation systems for enclosed parking garages shall operate continuously or shall be automatically operated by means of carbon monoxide detectors applied in conjunction with what other detector type?
404.1
If the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length must be identified on a permanent label located within what maximum distance of the exhaust duct connection?
614.9.5
An appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber or heat exchanger is a(an):
Chapter 2 – Definitions
What is the minimum density required for mineral wool batts (blanket or board) when used as part of a clearance reduction system?
308.2
What is strictly prohibited from being used to line ducts or plenums from the exit of a cooling coil to the downstream end of the drain pan?
604.13
Floor furnaces installed in upper stories must be separated from the nonhabitable space below by an enclosure constructed of what type of material?
609.6
An approved automatic fire suppression system is required in hazardous exhaust ducts, except where the largest cross-sectional diameter of the duct is less than how many inches?
509.7 Exception 3
Access to equipment on a roof shall not require walking on roofs having a slope greater than what ratio?
306.5
Where terms are not defined through authorized methods, such terms shall have what kind of meanings, as the context implies?
201.4
An appliance used to reduce combustible refuse material to ashes and that is manufactured, sold and installed as a complete unit is an:
Chapter 2 – Definitions
For gas cabinets containing highly toxic or toxic compressed gases in any quantity, what is the minimum acceptable ventilation velocity at any point at the access port or window?
502.9.7.1
A Combustible Assembly is constructed of one or more component materials that are not defined as what?
Chapter 2 – Definitions
Oil-fired appliances shall be provided with combustion air in accordance with which specific standard?
701.1
Shutoff valves serving movable appliances (such as cooking appliances) are considered provided with access when installed where?
409.5.1
What is the maximum on-center spacing allowed for permanent ladder rungs?
306.5
When are exhaust fans serving separate dwelling or sleeping units permitted to be connected to a common duct or shaft?
501.6
What is defined as the rapid oxidation of fuel accompanied by the production of heat or heat and light?
Chapter 2 – Definitions
If a safety/relief valve discharge termination point is not readily visible and observable, what is required?
1006.6
An independent and objective technical review conducted by an approved third party is defined as a:
Chapter 2 – Definitions
Combination potable water-heating and space-heating systems must be sized to prevent the space-heating load from diminishing what other required capacity?
1002.2.1
How shall defective material or parts be replaced or repaired?
301.14
Guards are required where components that require service are located within 10 feet (3048 mm) of a roof edge and that edge is located more than how many inches above the floor, roof, or grade below?
304.11
If roof-mounted solar collectors also serve as a roof covering, they must conform to the requirements for roof coverings in accordance with which code?
1402.8.1.3, 13
For fumes or vapors that are heavier than air, exhaust for hazardous material storage shall be taken from a point within how many inches of the floor?
502.8.1.1
In a common multistory duct system for clothes dryers, the exhaust fan must run continuously and be connected to what?
504.11
The maximum horizontal length of a Type B double-wall connector shall be what percentage of the height of the chimney or vent?
503.10.9
For Group R-2, R-3, and R-4 occupancies, mechanical ventilation air requirements shall be provided by which system configuration?
403.1
An object placed in an appliance to change the direction of or retard the flow of air, air-gas mixtures or flue gases is a:
Chapter 2 – Definitions
What is the minimum net airflow required for Type II hoods used for dishwashing appliances, per linear foot of hood length?
507.3.4.2
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 6-inch radius smooth 90-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
When a mechanical draft system is used with manually fired appliances and fireplaces, what specific device must be installed that produces visible and audible warning upon failure of the draft device or loss of electrical power?
804.3.8, 36
The opening provided in a draft hood to permit the ready escape of flue products in the event of no draft, back draft or stoppage, and to permit air into the draft hood in the event of a strong chimney updraft, is the:
Chapter 2 – Definitions
Which of the following is considered a Heavy-Duty Cooking Appliance?
Chapter 2 – Definitions
A tee fitting used for pressure measurement or as a sediment trap must be installed not less than 10 pipe diameters downstream of the MP regulator, unless which alternative condition is met?
410.2
Suspended-type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches at the sides, 12 inches at the bottom, and what minimum distance above the top if the unit heater has an internal draft hood?
620.4
Where single-appliance venting tables show a lateral length (L) of zero (0), how many elbows are included in the venting configuration capacity listed in the table?
504.2.3
For a light test on a grease duct system, the lamp used must have a rating of not less than how many lumens?
506.3.2.5.1
Hazardous exhaust systems are required if a vapor, gas, fume, mist, or dust with a health-hazard rating of 4 is present at what concentration?
509.2
In addition to keeping concentrations below 25 percent of the LFL, what is the minimum required average air velocity through all openings for an open face or open front spray booth?
502.7.3.3.1
Where solar thermal equipment is exposed to vehicular traffic, what is the minimum height it must be installed above the finished floor?
1402.6, 10
Exhaust outlets serving Type II hoods that terminate above a roof must terminate not less than how many inches above the roof surface?
506.4.2
Any person commencing work on a mechanical system before obtaining necessary permits shall be subject to a fee that is:
108.4
What authority does the code official have regarding temporary uses, equipment, or systems permits?
110.4
What minimum unobstructed width is required for passageways around all sides of boilers, unless otherwise approved?
1004.3
A hood and exhaust system is not required for protection from refrigerant decomposition if the refrigerant detector is used to automatically stop the combustion process in the event of what?
1104.3.4 Exception 3
What nominal pipe size requires displacement with an inert gas for any length of piping removed from service?
406.7.1.1; Table 406.7.1.1
A permit shall not be valid until:
108.1
For a roof slope between Over 10/12 to 11/12, what is the minimum required vertical height (H) above the roof to the lowest discharge opening?
503.6.5; Figure 503.6.5 (Table)
Before replacing an existing appliance, the chimney passageway must be examined to ascertain that it is clear and free of obstructions and must be cleaned if previously used for venting which types of appliances?
503.5.6
Connections from a utility, source of energy, fuel, or power to any system regulated by this code for which a permit is required shall not be made until authorized by whom?
109.1
The code official is authorized to accept reports of approved agencies, provided such agencies satisfy the requirements as to qualifications and what other factor?
111.2.4
At the point where tee or wye fittings connect to a common vent, the opening size of the fitting must be equal to the size of which component?
504.3.9
A metal-joining process wherein coalescence is produced by the use of a nonferrous filler metal having a melting point above 1,000°F (538°C), but lower than that of the base metal being joined, is:
Chapter 2 – Definitions
Stud wall cavities and joist space plenums are prohibited from being utilized for what specific air movement?
602.2.1
Which occupancy group is exempt from the requirement to provide space-heating systems capable of maintaining 68°F (20°C)?
309.1 Exception
A manually operated solid fuel ignition appliance for installation in a vented solid fuel-burning fireplace is a:
Chapter 2 – Definitions
Equipment used in residential occupancies is excepted from the human comfort refrigerant restriction if it contains a maximum of how many pounds of refrigerant?
1104.3.1 Exception 1
What is the minimum height required for the lettering of the identification label on refrigerant piping?
1109.2.7
Protective shield plates must be placed where there is less than what minimum distance between the clothes dryer exhaust duct and the finished face of the framing member?
614.8
In areas where stationary motor vehicles are operated, a source capture system must be provided that connects directly to what?
502.14
If treatment of exhaust for air pollution control is necessary, manifolding of ducts is allowed if what finishing material is specifically prohibited from being used?
502.7.3.5 Exception 2
What type of fitting may be used to separate air streams between intake air openings and living space exhaust air openings of an individual dwelling unit where the separation distance is less than 3 feet?
401.4
Members of the board of appeals shall not be what?
112.3
A free-standing heating unit used for direct heating of the space in and adjacent to that in which the unit is located is a:
Chapter 2 – Definitions
Electric Heating Appliances produce heat energy by the application of electric power to resistance elements, refrigerant compressors, or what other mechanism?
Chapter 2 – Definitions
Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, handling, or dispensing of which materials occurs?
305.2
What is the minimum letter height required for the permanent warning notice attached to the outside of a commercial sauna room?
914.5.1
Where heat or radiant energy sensors are used in hood systems consisting of multiple hoods served by a single exhaust system, where must the sensors be provided?
507.1.1.1
For exterior masonry chimneys serving two or more Category I appliances (NAT+NAT) with Type B double-wall connectors, if the vent height is 15 feet and the internal area is 78 square inches, what is the maximum combined input rating in thousands of Btu per hour?
504.3; Table 504.3(6a)
The board of appeals shall not have the authority to perform what action regarding the requirements of this code?
112.2
Reports not complying with Section 104.2.3.6.1 must describe criteria and justify:
104.2.3.6.2
Valves in hydronic piping systems must be constructed of materials compatible with the piping material and fluids, and rated for what two system characteristics?
1202.6
In an Indirect Refrigeration System classified as an Open-Spray System, the secondary coolant is circulated in what kind of contact with the air or other substance to be cooled or heated?
Chapter 2 – Definitions
Oil-fired vented wall furnaces must be tested in accordance with which UL standard?
909.1
Pumps that are not part of an appliance must be of what specific type?
1302.7
The remaining space surrounding a chimney liner installed within a masonry chimney flue is prohibited from being used to vent another appliance.
503.5.10
Metal chimneys shall be constructed and installed in accordance with which specific NFPA standard?
806.1, 41
The holder of a permit for partial construction proceeds at risk without assurance that the permit for the entire installation will be granted, provided that adequate information and detailed statements have been filed complying with all pertinent requirements of this code, and the partial permit has been issued by the:
105.5.1
If intake openings are located less than 10 feet horizontally from streets, alleys, parking lots, and loading docks, they must be located not less than how many feet vertically above such locations?
401.4
The building or structure must be left in a safe structural condition in accordance with the International Building Code if which part of the structure is altered or replaced during system installation or repair?
302.1
For appliances located in attics, the required unobstructed passageway must be not less than 30 inches high and 22 inches wide and not more than what length measured along the centerline?
306.3
What component of systems is NOT included in the definition of Equipment?
Chapter 2 – Definitions
A method of interlock between an exhaust hood system and cooking appliances shall NOT involve or depend on what component?
507.1.1
What is the primary difference between Ready Access (To) and Access (To)?
Chapter 2 – Definitions
Labeling procedures are set forth in Sections 301.8.1 through which final subsection?
301.8
With the exception of smoking lounges, the ventilation rates in Table 403.3.1.1 are based on the absence of what in occupiable spaces?
403.3.1.1
In an Indirect Evaporative Cooling system, how is heat removed from a primary air stream?
Chapter 2 – Definitions
Type L vents must terminate not less than how many feet higher than any portion of a building within 10 feet (3048 mm)?
802.5, 17
Freeze protection for system components must be provided in accordance with which standard?
1402.4, 6
If not notified prior to utility disconnection, how soon thereafter shall the owner, owner’s authorized agent or occupant be notified in writing?
109.3
Regarding modifications in flood hazard areas, the code official shall not grant a modification unless a determination has been made that failure to grant the variance would result in exceptional hardship by rendering the lot what?
104.2.4.1
Required test and inspection records shall be available to the code official at all times during the erection of the building and the fabrication of the:
111.2.5.3
Round metallic ducts must be mechanically fastened by means of not less than how many sheet metal screws or rivets spaced equally around the joint?
603.4.1
Copper and copper alloy pipe shall not be used if the gas contains more than what average amount of hydrogen sulfide per 100 standard cubic feet of gas?
403.3.3
For natural gas systems, which device is installed by the serving gas supplier to reduce and limit the service line pressure to delivery pressure?
Chapter 2 – Definitions
Portable residential spas and portable residential exercise spas must comply with UL 1563 or which other CSA standard?
916.1 Exception
For vertical terminations of mechanical draft systems, the vent shall terminate not less than how many feet above any forced air inlet located within 10 feet horizontally?
804.3.5, 34
What is the maximum capacity in cubic feet per hour (cfh) for 1-inch nominal Schedule 40 metallic pipe at 150 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
The total of all Group A2, B2, A3, and B3 refrigerants in all occupancies shall not exceed what maximum weight, except where approved?
1104.3.3
Thermal Resistance (R) is defined as the reciprocal of what measure?
Chapter 2 – Definitions
The minimum internal dimension allowed for any shaped single-wall metal pipe used for venting must be not less than what dimension?
503.7.10
Domestic electric water heaters must comply with which UL standard(s)?
1002.1
Who has the authority to waive the submission of construction documents, calculations, or other data if review is not necessary to determine compliance?
106.1 (Exception)
Masonry fireplaces must be constructed in accordance with which code?
902.1
What is the minimum required depth for a grease duct reservoir?
506.3.7.1
What is the minimum required pipe size for a condensate waste and drain line?
307.2.2
The payment of a permit fee for construction, alteration, removal, or demolition does not relieve the applicant from payment of:
108.5
Stationary fuel cell power systems having a power output not exceeding 10 MW must be tested in accordance with which standard?
924.1
Subslab soil exhaust system ducts must terminate not less than how many feet from any operable openings or air intake?
511.4
Appliances shall not be located in a hazardous location unless they are listed and approved for the:
303.2
Mechanical systems can be located below the required flood elevation if they are designed and installed to prevent water from entering or accumulating within components and to resist what other loads and stresses?
301.16 Exception
When are permit applications for appliance and equipment replacements and repairs required to be submitted if the work was performed in an emergency situation?
105.1 (Exception)
What is the minimum clearance required above an appliance where the original required clearance was 36 inches, and the protection utilized is 1/2-inch insulation board over 1-inch glass fiber or mineral wool batts?
308.2; Table 308.2
Ducts shall not be installed in or within what minimum distance of the earth, unless they comply with Section 603.8 (Underground Ducts)?
603.14
What is the capacity in cfh for CSST Flow Designation 30 at 500 feet in length, operating at 2 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(18)
Where combustion air openings are provided with volume, smoke, or fire dampers, the dampers must be interlocked with what component of the appliance?
701.2
For a Nail salon, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than how many CFM per station?
Table 403.3.1.1 Note h
For non-residential occupancies, the maximum opening size in louvers, grilles, and screens protecting air intake openings must be less than or equal to what dimension?
Table 401.5
Pipe insulation installed in buildings must have a maximum flame spread index of what value when tested in accordance with ASTM E84 or UL 723?
1204.1
A continuous open passageway from the flue collar or draft hood of an appliance to the outdoor atmosphere for the purpose of removing flue or vent gases is a:
Chapter 2 – Definitions
What is NOT included in the calculation of Net Floor Area?
Chapter 2 – Definitions
When two or more connectors enter a common vent or chimney, where shall the smaller connector enter?
803.7, 22
What type of organization must an Approved Agency be, in addition to being acceptable to the code official?
Chapter 2 – Definitions
Which openings are NOT allowed in the combustion chamber of a Closed Combustion Solid-Fuel-Burning Appliance?
Chapter 2 – Definitions
Joints between steel pipe or fittings are required to be mechanical joints made with an approved elastomeric seal, or which two other types of joints?
1203.11
Posts 3 feet (914 mm) or less in height supporting illuminating appliances shall not be smaller than what minimum size Schedule 40 steel pipe?
628.3
If manufacturer’s instructions for a refrigerator are unavailable, what is the minimum clearance required above the top of the refrigerator?
625.1
What must be installed on drain and fill valves in the solar loop?
1402.8.6.2, 18
The equipment in Section 1106.5.1 must be automatically shut off whenever the refrigerant vapor concentration in the machinery room exceeds the vapor detector’s upper detection limit or what maximum percentage of the LEL, whichever is lower?
1106.5.1
A low-heat appliance (residential appliance) is defined as any appliance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of:
Chapter 2 – Definitions
The use of gypsum boards to form air shafts (ducts) is limited to which type of air system?
603.5.1
For vertical 3/4-inch steel pipe, how often must supports be spaced?
415.1; Table 415.1
Which constituent is specifically excluded from the definition of Combustion Products?
Chapter 2 – Definitions
Requirements necessary for public safety, health and general welfare that are not specifically covered by this code shall be determined by the:
102.9
Roof-mounted solar thermal equipment shall not obstruct or interfere with the operation of which items?
1402.2, 4
Where hazardous materials capable of emitting hazardous vapors are stored, contaminated exhaust air shall not be recirculated to occupied areas unless what condition is met?
502.8.1.1
Where a duct furnace conveys air to areas outside its space, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
610.2
Acceptable to the code official is the definition of which term?
Chapter 2 – Definitions
Which of the following is NOT one of the required labeling descriptions for heat exchangers?
1404.4, 23
For an Elevator car in public spaces, what is the required Exhaust Airflow Rate in CFM/ft squared?
Table 403.3.1.1
The code official shall take action without delay in accordance with the decision of the:
112.4
Gas piping systems other than CSST must be considered bonded where they are connected to one or more appliances that are connected to which conductor of the circuit supplying the appliance?
310.1
What is the minimum size required for the bonding jumper used for CSST piping systems?
310.2.2
Where an appliance is connected to a chimney flue serving a fireplace, what must be provided below the point of connection to prevent entry of room air into the flue?
801.10.1, 5
Where damage to any building components could occur from overflow of the primary condensate system, what is one auxiliary protection method that must be provided?
307.2.3
Where a single appliance has more than one draft hood outlet or flue collar, and manufacturer instructions are absent, the vent connectors must have a minimum rise of what distance?
503.10.3.2
Which type of floor furnace depends primarily on circulation of air by gravity and includes those equipped with booster-type fans that do not materially restrict free circulation when not operating?
Chapter 2 – Definitions
If the code official determines that the valuation provided by the applicant is underestimated, what action may be taken?
108.3
Air conveyed within energy recovery systems shall not be considered as recirculated air if the system is constructed to limit cross-leakage between air streams to less than what percentage of the total airflow design capacity?
513.4
A single unit providing complete, independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation, is a:
Chapter 2 – Definitions
Protective shield plates for clothes dryer exhaust ducts must be constructed of steel and have a minimum thickness of 0.062 inch (1.6 mm).
614.8
Interpretations, policies, and procedures adopted by the code official shall not have the effect of:
104.2
The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction, provided the alternative is not specifically prohibited by this code and has been what?
104.2.3
A manual shutoff control for hazardous exhaust systems in storage rooms must be provided outside the room adjacent to the access door, and what must the switch be labeled?
502.8.1.1
Solid fuel-burning appliances must be provided with combustion air in accordance with what documentation?
701.1
Flammable gas cylinders in occupancies regulated by the International Residential Code shall not exceed what maximum volume at normal temperature and pressure (NTP)?
703.2.1
Permits for temporary uses, equipment, and systems shall be limited as to time of service but shall not be permitted for more than how many days?
110.1
Air dispersion systems must be listed and labeled in compliance with which UL standard?
603.17
What is the maximum circuit length allowed for 5/8-inch nominal tube size radiant heating tubing from a supply-and-return manifold arrangement?
Table 1209.6.1
Which of the following details is NOT required to appear on the permanent factory-applied nameplate affixed to appliances?
301.9
Unvented room heaters shall not have an input rating in excess of what maximum amount?
621.3
When shall a notice of approval be issued by the code official?
107.1
A valve of the plug and barrel type provided with means for maintaining a lubricant between the bearing surfaces is a:
Chapter 2 – Definitions
The highest stress level that the component will tolerate without rupture is defined as what?
Chapter 2 – Definitions
The meter, valve, regulator, piping, fittings and equipment installed by the service gas supplier before the point of delivery is the:
Chapter 2 – Definitions
Additives contained in a Food-Grade Fluid must be listed in accordance with what code reference?
Chapter 2 – Definitions
Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be based on a listed occupancy classification most similar in terms of occupant density, activities, and what third factor?
403.3.1.1
Masonry chimneys shall be constructed in accordance with which code?
801.3
What is the minimum clearance required from noncombustible construction and gypsum wallboard attached to noncombustible structures for a shaft enclosure used for a grease duct?
506.3.11.1
Disconnection of utility service is authorized by the code official in case of emergency where necessary to eliminate which condition?
109.3
Sauna heaters must be equipped with a thermostat that will limit room temperature to what maximum temperature?
615.6
For ducts conveying explosive or flammable vapors, fumes or dusts, what is the minimum termination distance from combustible walls and operable openings into buildings that are in the direction of the exhaust discharge?
501.3.1
Which appliance type is classified as a Light-Duty Cooking Appliance?
Chapter 2 – Definitions
External hood joints, seams, and penetrations for Type I hoods must be made with a continuous external liquid-tight weld or braze to where?
507.2.5
Ozone gas generators having a maximum ozone-generating capacity of 1/2 pound (0.23 kg) or more over a 24-hour period must be mechanically ventilated at a rate of not less than how many air changes per hour?
502.9.9
Minor alterations to existing mechanical systems shall meet the provisions for new construction unless the work is done in the same manner as the existing system, is not hazardous, and is what?
102.4
For structures located in flood hazard areas, plenum spaces located below the required elevation must be capable of resisting what loads and stresses?
602.4
Where a closet is designed for a clothes dryer installation, the required makeup air opening in the closet enclosure must have an area of not less than what minimum size?
614.7.1
What is the minimum exhaust rate per lamp for xenon motion picture projectors without an exhaust connection?
502.11.2
For residential-type appliances, if not installed in unconditioned areas, a vent connector made of aluminum (1100 or 3003 alloy) sheet must be not less than what minimum thickness?
503.10.2.3
Approved smoke and heat vents must be installed in the roofs of one-story buildings where required by which code?
311.1
Gas vents 12 inches or less in size and located not less than 8 feet from a vertical wall must terminate above the roof in accordance with Figure 503.6.5.
503.6.5
A sediment trap must be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical, except for which common appliance?
408.4
When the design and free area of louvers and grilles are unknown, what free area percentage is assumed for metal louvers and grilles in combustion air calculations?
304.1
For a corrugated metallic chimney liner system installed in a masonry chimney, the maximum capacity determined from the Type B vent tables shall be reduced by what percentage?
504.2.7
Cooling towers and evaporative condensers must be equipped with drift eliminators that have a maximum drift rate of what percentage of the circulated water flow rate?
908.8.2
Who shall keep a record of each inspection made, including notices and orders issued?
104.7.2
Exhaust outlets serving Type II hoods must terminate not less than how many feet in any direction from openings into the building?
506.4.2
What are the parts of a refrigerating system subject to condenser pressure?
Chapter 2 – Definitions
For institutional occupancies, the maximum allowable refrigerant amounts shown in Table 1103.1 must be reduced by what percentage?
1104.2.1
To consider the volumes of spaces in different stories as communicating spaces for combustion air, what is the total minimum free area required for connecting openings in doors or floors, based on total appliance input rating?
304.5.3.2
Where two or more appliances are connected to a vertical vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material.
503.10.4
A specific heating, or heating and ventilating, furnace incorporating an integral total enclosure and using only outside air for combustion is a(an):
Chapter 2 – Definitions
Horizontal upper combustion air ducts shall not slope in which direction toward the source of combustion air?
304.11
The pressure difference created by the action of a fan, blower or ejector that is located between the appliance and the chimney or vent termination is defined as:
Chapter 2 – Definitions
Solar thermal equipment and appliances must conform to the requirements of Chapter 14 and which specific standard?
1401.4
Which ASTM standard applies to Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) plastic pipe?
Table 1202.4
Which location is required to have a stop valve on refrigeration systems containing more than 6.6 pounds (3.0 kg) of refrigerant?
1109.6.1
What electrical requirement must be provided at or near the appliance location in an attic?
306.3.1
Vented gas fireplace heaters shall be listed in accordance with which ANSI/CSA standard?
605.1
Exemption from permit requirements shall not grant authorization for work to be done in violation of:
105.2
The instrument installed to measure the volume of gas delivered through it is the:
Chapter 2 – Definitions
In concealed locations, protective steel shield plates for vents installed through holes or notches in framing members must have a minimum thickness of 0.0575 inch, which corresponds to what gauge?
502.7
The code official has authority to grant extensions for time limitations on a permit application for additional periods, not exceeding how many days each?
105.3.1
For piping installed in concealed locations, shield plates are required if the pipe is less than how far from the nearest edge of the wood framing member?
305.5
Piping that is located in a concealed location is defined as:
Chapter 2 – Definitions
Who is authorized and directed to enforce the provisions of this code?
104.1
Subslab soil exhaust system duct material must be air duct material listed and labeled to the requirements of UL 181 for which air duct class?
511.2
What is the minimum vertical height required for vents to terminate above the highest connected appliance flue collar?
802.6, 17
Which valve controls the gas supply to an individual main burner?
Chapter 2 – Definitions
A steel vent connector for a medium-heat appliance with a vent gas temperature exceeding 1,000°F and a diameter of 18 inches or less must be lined with medium-duty fire brick that is not less than how thick?
503.10.2.5
Mechanically extracted outlets for mechanically formed tee fittings must have a height not less than what multiple of the thickness of the branch tube wall?
1203.3.8
Suspended-type unit heaters are prohibited in corridors, exit access stairways and ramps, exit stairways and ramps, and patient sleeping areas in which two specific occupancy types?
920.4
What is the required People Outdoor Airflow Rate in the Breathing Zone in CFM/person for a Booking/waiting area in a correctional facility?
Table 403.3.1.1
When testing at a pressure greater than 10 psig (68.98 kPa gauge) but less than or equal to 100 psig (689.5 kPa gauge), the testing gauge must have increments of what maximum amount?
705.3.6
Uninhabited spaces, such as crawl spaces and attics, must be provided with natural ventilation openings as required by the International Building Code or a mechanical exhaust and supply air system with a mechanical exhaust rate of not less than how many CFM per square foot of horizontal area?
406.1
For a Main entry lobby in an office occupancy, what is the required Area Outdoor Airflow Rate in the Breathing Zone in CFM/ft squared?
Table 403.3.1.1
Work shall not be done beyond the point indicated in each successive inspection without first obtaining whose approval?
111.2.3
Gasket and sealing materials for cleanout doors in grease ducts must be rated for not less than what temperature?
506.3.8
A device used in piping to control the gas supply to any section of a system of piping or to an appliance is a:
Chapter 2 – Definitions
Appliances serving different areas of a building than where they are installed must be permanently marked in an approved manner that uniquely identifies the appliance and what else?
304.12
A Thermoplastic is a plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature. What is the characteristic of a Thermosetting plastic?
Chapter 2 – Definitions
If there is insufficient evidence of compliance, who has the authority to require tests as evidence of compliance?
104.2.2.4
Domestic cooking exhaust equipment with integral downdraft exhaust systems must be listed and labeled in accordance with which standard?
505.2
Individual radiant tubing circuit lengths shall be installed with a variance of not more than what percentage from the design length?
1209.6
Provisions of this code are not mandatory for existing historic buildings where the code official judges the building to be safe and in the public interest of what?
102.6
A self-contained appliance for heating air by transfer of heat of combustion through metal to the air, and designed to supply heated air through ducts to spaces remote from or adjacent to the appliance location, is a:
Chapter 2 – Definitions
In a Private dwelling, single and multiple, if the exhaust system for a Toilet room operates intermittently, what is the required exhaust rate in CFM?
Table 403.3.1.1 Note f
Pressurized water storage tanks must bear a label showing the manufacturer’s name and address, model number, serial number, and what specific characteristics related to operating conditions?
1404.2, 22
In areas designated as Zone AO where a depth number is not specified on the flood hazard map, the design flood elevation depth number shall be taken as being equal to:
Chapter 2 – Definitions
What is the minimum exhaust rate required per square foot of floor area for spaces containing cooking appliances that do not require Type II hoods, such as those that produce only heat or moisture?
507.1 Exception 2
For permanent ladders installed to provide roof access, the side railing shall extend above the parapet or roof edge not less than what minimum height?
306.5
What is the capacity in cfh for CSST Flow Designation 62 at 30 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(19)
Ducts and air transfer openings penetrating fire barriers must be protected with listed fire dampers, unless the duct system has a required fire-resistance rating of 1 hour or less, is in areas other than Group H, is in a fully sprinklered building, AND is constructed of sheet steel not less than what minimum thickness?
607.5.2 Exception 3
Gaskets and sealing materials used for grease duct-to-exhaust fan connections must be rated for continuous duty at a minimum temperature of what?
506.3.2.3
For pneumatic leak tests of gaseous hydrogen systems where the maximum working pressure is less than 125 psig (862 kPa gauge), what is the minimum required test pressure?
705.3.2
What is the capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 900 feet in length, operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(5)
What is the minimum clearance required from combustible materials for ducts serving commercial clothes dryers?
504.1
Condensate drain lines must be configured to permit the clearing of blockages and performance of maintenance without requiring what action?
307.2.5
Refrigerants with different refrigerant designations may only be mixed if the resulting mixture does not change what characteristic?
1102.2.1
Air from a swimming pool and associated deck areas shall not be recirculated to other spaces where more than what percentage of the resulting supply airstream consists of air recirculated from these spaces?
403.2.1
Space within a dwelling unit utilized for living, sleeping, eating, cooking, bathing, washing and sanitation purposes is defined as:
Chapter 2 – Definitions
After a pressure test, minor repairs and additions shall not be required to be pressure tested provided the connections are tested with a noncorrosive leak-detecting fluid or what other method?
406.1.2
What is the maximum allowable exhaust duct length for a domestic clothes dryer when using the specified length method, excluding transition duct length?
504.9.4.1
When entering an occupied structure or premises for inspection, the code official must first present credentials to the occupant and do what?
104.4
A person who continues any work after being served with a stop work order, except work directed to remove a violation, shall be subject to:
114.4
What specific type of fluid is strictly prohibited from being utilized as a heat transfer fluid in a solar system?
1403.5, 21
TABLE 614.9.4.1 QUESTION: What is the longest equivalent length required by the table for a single duct fitting in a domestic dryer exhaust duct system?
614.9.4.1; Table 614.9.4.1
A structure utilized or intended for supporting or sheltering any occupancy is defined as what?
Chapter 2 – Definitions
What is a device or apparatus that is manufactured and designed to utilize energy and for which this code provides specific requirements?
Chapter 2 – Definitions
A listed shutoff valve shall be installed immediately ahead of which device?
409.4
An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and the roof, is a:
Chapter 2 – Definitions
Where the space above a suspended ceiling is continuous and part of the supply or return air plenum system, how is this space treated in volume calculations?
1104.4.3
What is the maximum allowable quantity of refrigerant determined by Section 1104 based on?
1102.1
Piping to be embedded in concrete must be pressure tested prior to pouring concrete, and during pouring, the pipe must be maintained at what pressure?
1209.2
All air handled by a nonrecirculating direct-fired industrial air heater, including combustion air, shall be ducted directly from which location?
611.4
Where two or more meters are installed on the same premises but supply separate consumers, interconnection is prohibited on which side of the meters?
401.6
Above-grade underfloor spaces or basements in LP-gas distribution facilities where portable containers are used or stored must be provided with what?
502.9.10.1
If a room without openings to the outdoors is ventilated through an adjoining room, what is the minimum required unobstructed area of the opening to the adjoining room?
402.3
A balanced damper device attached to a chimney, vent connector, breeching or flue gas manifold to protect combustion appliances by controlling chimney draft is known as a:
Chapter 2 – Definitions
A pressure relief valve installed on the low-pressure side of a hydronic piping system (where pressure has been reduced) must be set at what pressure?
1205.2
Fuel oil piping and equipment located in flood hazard areas must be capable of resisting hydrostatic and hydrodynamic loads and stresses, including what specific effect?
1305.2.1
Machinery rooms must be mechanically ventilated to what location?
1105.6
In case of emergency, the code official has the authority to authorize disconnection of utility service where necessary to eliminate what?
109.3
Which chimney flues are exempt from the cleanout requirement if access is provided through the fireplace opening?
801.13 Exception, 7
What is the minimum clearance required to a mechanical air supply inlet (Clearance I) for a vent terminal?
503.8; Table 503.8
What must the code official carry when inspecting structures or premises in the performance of duties under this code?
104.5
Construction or work for which a permit is required shall be subject to inspection by the code official and shall remain visible and able to be accessed for inspection purposes until when?
111.1
What is the capacity in thousands of Btu per hour for 4-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 1,000 feet in length, for undiluted propane operating at 2.0 psi inlet pressure with a 1.0 psi pressure drop?
402.4; Table 402.4(36)
An installation regulated by this code constituting a hazard to health, safety, or welfare by reason of inadequate maintenance, fire hazard, or abandonment is declared to be a(an):
113.6
Underground inspection shall be made after trenches or ditches are excavated and bedded, piping installed, and before what action is taken?
111.2
What is the maximum difference allowed between the inside cross-sectional dimensions of overlapping sections of grease duct?
506.3.2.1
When using the Two-Permanent-Openings Method (304.6.1) and communicating with the outdoors through horizontal ducts, what is the minimum free area required for each opening per 2,000 Btu/h of total appliance input rating?
304.6.1
Where are manual dampers prohibited from being installed in connectors?
803.5, 21
The pressure difference that causes a continuous flow of air and products of combustion through the gas passages of the appliance to the atmosphere is defined as what?
Chapter 2 – Definitions
The provisions of this code are prohibited from nullifying the provisions of:
102.1
Interior spaces intended for human occupancy must be provided with active or passive space-heating systems capable of maintaining an indoor temperature of not less than how many degrees Fahrenheit?
309.1
Which type of boilers are required to be protected with a low-water cutoff control?
1007.1
The furnace must be placed such that a drapery or similar combustible object will not be nearer than what minimum distance to any portion of the register of the floor furnace?
910.2
What is a pipe that connects a fuel-burning appliance to a chimney?
Chapter 2 – Definitions
Which method defines a Low-Probability Pump designed to prevent atmospheric release of the pumped fluid?
Chapter 2 – Definitions
According to Table 509.8, what is the minimum nominal thickness required for a duct diameter of 19–30 inches conveying abrasive materials?
Table 509.8
If the depth of an appliance pit exceeds 12 inches (305 mm) below adjoining grade, the walls of the pit or excavation must be lined with what material?
303.7
Hot water storage tanks must be insulated with an R-value of not less than what minimum value?
1402.8.5.1, 17
Mechanical systems shall be tested as required in this code and observed by whom?
111.3
Packaged electric boilers must be listed and labeled in accordance with which UL standard?
1004.1
Balancing baffles must be mechanically locked in the desired position before placing the appliance in operation.
503.13.1
If ready access is not provided to mechanical systems in prefabricated assemblies, who shall conduct in-plant inspections as frequently as necessary?
111.2.5.2
Ducts used to convey dust, stock, and refuse must be supported at intervals not exceeding what maximum distance?
509.9
A relief device must be located so that a section of the pressurized system cannot be valved off or otherwise isolated from what component?
1402.3.1, 5
For Group A2L and B2L refrigerant detectors, at a concentration less than or equal to the OEL, what is the maximum required response time in seconds to signal an alarm?
Table 1106.4.2
A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under nonpositive static vent pressure is a:
Chapter 2 – Definitions
Where connected to rigid piping, a union fitting must be installed within what maximum distance of either side of an MP regulator?
410.2
New mechanical systems and parts of existing systems that have been altered, extended, renovated, or repaired shall be tested as prescribed to disclose what?
111.3.1
A venting system designed to remove flue or vent gases by mechanical means, consisting of an induced draft portion or a forced draft portion, is a:
Chapter 2 – Definitions
What is the capacity in thousands of Btu/h for 1 1/4-inch nominal Schedule 40 metallic pipe at a length of 100 feet, for undiluted propane with an inlet pressure of 11.0 in. w.c. and a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(28)
What is the maximum horizontal spacing allowed for supporting steel tubing?
Table 305.4
Ladders over 30 feet (9144 mm) in height must be provided with offset sections and landings capable of withstanding what minimum load?
306.5
Guards shall be provided where components requiring service are located within what distance of a roof edge or open side of a walking surface located more than 30 inches above the surface below?
306.6
Interpretations, policies, and procedures adopted by the code official must comply with the intent and purpose of this code and must not have the effect of doing what?
104.2
Stationary fuel-cell power systems having a power outlet not exceeding 10 MW shall be tested in accordance with which ANSI/CSA standard?
633.1
What is the minimum clearance required from the sides and rear of a vertical connector where the original required clearance was 12 inches, and the protection is 3 1/2-inch-thick masonry wall without ventilated airspace?
308.2; Table 308.2
Any suit or criminal complaint instituted against an officer because of an act performed in the lawful discharge of duties shall be defended by:
104.8.1
For a sauna heater, the heat-sensing element of the room temperature thermostat must be located within what maximum distance of the ceiling?
615.6
For appliances in a dwelling unit basement, the unobstructed passageway must be large enough to allow removal of the largest appliance and measure not less than what minimum width?
306.2 (Exception)
Where enforcement of a code provision would violate the conditions of the listing of the equipment, what shall apply?
102.8 Exception
A commercial kitchen grease duct serving a Type I hood must be enclosed when it penetrates what feature?
506.3.11
A rigid conduit of iron, steel, copper, copper-alloy or plastic is defined as:
Chapter 2 – Definitions
Joints between different piping materials shall be made with what type of fitting?
1203.1.1
Upon issuance of a stop work order, the cited work shall:
114.2
Taking return air from an indoor swimming pool enclosure is not prohibited if what condition is met?
601.5 Exception 1
What is the minimum air velocity required within a grease duct system?
506.3.4
If a separate overflow drain line is connected to the equipment drain pan, at what level must it connect relative to the primary drain connection?
307.2.3
A permit shall not be extended more than:
105.5.4
A floor furnace must be placed so that a door, drapery, or similar object cannot be nearer than what minimum distance to any portion of the register of the furnace?
609.2
The code official shall designate the evaluation service of an approved agency as the evaluation agency and review the agency’s evaluation report for adequacy and:
111.2.5.1
When is the use of the space between the corridor ceiling and the floor or roof structure above permitted as a return air plenum, specifically related to the fire suppression system?
601.2.1
Which type of vent is listed for use with oil-burning appliances and gas appliances listed for venting with Type B vents?
Table 802.2, 16
For an Animal exam room (veterinary office), what is the estimated maximum occupant load rate per 1,000 square feet?
Table 403.3.1.1
Clearances to combustible construction must be reduced only in accordance with which section?
304.9
Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, which requirements shall apply?
102.8 (Exception)
A packaged and completely assembled appliance containing a toilet that incinerates refuse instead of flushing it away with water is a:
Chapter 2 – Definitions
If an installation is maintained in violation of this code and in violation of a notice, the code official shall institute appropriate action to prevent, restrain, correct, or:
113.6.3
What is the minimum exhaust rate per lamp for electric arc motion picture projectors without an exhaust connection?
502.11.2
Rooms containing appliances must be provided with an unobstructed passageway measuring not less than what minimum width and height?
306.2
High-density polyethylene (HDPE) pipe fittings for ground-source loops must conform to which standards, including ASTM D2683 and ASTM D3261?
Table 1210.5
Where a smoke damper is installed within a duct, the smoke detector or sampling tubes must be located within what maximum distance of the damper?
607.3.3.2
Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances is a:
Chapter 2 – Definitions
What is the capacity in cfh for 1/2-inch nominal semirigid copper tubing at a length of 70 feet, for natural gas at less than 2 psi inlet pressure and 0.3 in. w.c. pressure drop?
402.4; Table 402.4(8)
What is the minimum clearance required from combustible construction for a Type I hood?
507.2.6
Tests conducted to demonstrate equivalency in support of an alternative design application must be of a scale that is sufficient to predict the performance of the:
104.2.3.5
Duct smoke detectors must report only as a supervisory signal, not as a fire alarm, in facilities required to be monitored by what location?
606.4.1
If one or more temperature or radiant energy sensors are used to activate a Type I hood exhaust fan, the fan must activate not more than how many minutes after the first appliance served by that hood has been turned on?
507.1.1
Devices used for making CSST bonding connections shall be listed for the application in accordance with which UL standard?
310.2.5
Automatic dampers shall be listed and labeled in accordance with which UL standard for oil-fired heating appliances?
803.6, 21
Which venting system is required for unlisted appliances?
503.4; Table 503.4
What is the minimum open area required for the passageway of dryer exhaust duct terminals?
504.4.2
A Pollution-Control Unit (PCU) is manufactured equipment installed in a grease exhaust duct system for the purpose of extracting smoke, grease particles and what other contaminants?
Chapter 2 – Definitions
The permit or a copy shall be kept on the site of the work until the:
105.5.7
Connectors shall connect to a masonry chimney flue at a point not less than what vertical distance above the lowest portion of the interior of the chimney flue?
501.9
Sauna heaters must be listed and labeled in accordance with which UL standard?
914.2
For Type IV and V dry cleaning units, if an exhaust hood is installed immediately outside of and above the loading door, the required airflow rate is calculated by multiplying 100 by what factor?
502.6.2
To determine compliance with this code, the code official is authorized to require the owner or owner’s authorized agent to provide a:
104.2.2
Appliances located in public garages or repair garages shall be installed not less than what distance above the floor?
305.4
Multiple spray booths are allowed to have a common exhaust system if their combined frontal area is what maximum size, provided identical spray-finishing material is used?
502.7.3.5 Exception 1
A device or group of devices essentially forming an integral unit for the final conveyance of gas or a mixture of gas and air to the combustion zone, and on which combustion takes place to accomplish the function for which the appliance is designed, is a:
Chapter 2 – Definitions
Gas vents must terminate not less than what minimum vertical distance above any forced air inlet located within 10 feet horizontally?
503.6.8
Where conflicts occur between the provisions of this code and the referenced standards, which provisions shall apply?
102.8.1
Group A2 and B2 refrigerants shall not be used in which type of refrigeration system?
1104.3.2
Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts, unless an exception applies. Which term defines this prohibition?
601.2
Refrigerant piping and tubing greater than what maximum diameter shall be tested in accordance with ASHRAE 15?
1110.6
What is the maximum vapor pressure that Flammable Liquids are permitted to have at 100°F (38°C)?
Chapter 2 – Definitions
Nonmetallic ducts shall be constructed with which classes of duct material?
603.5
The amount of gas that occupies 1 cubic foot (0.02832 m3) when at a temperature of 60°F (16°C), saturated with water vapor and under a pressure equivalent to that of 30 inches of mercury (101 kPa), is defined as a:
Chapter 2 – Definitions
When the design and free area of louvers and grilles are unknown, what free area percentage is assumed for wood louvers in combustion air calculations?
304.1
In which specific occupancy and condition are solid fuel-burning fireplaces and appliances prohibited?
901.4
Air systems serving a plenum must be ducted directly from the boundary of the fire area served to what equipment?
602.1.2
What is the primary function of a Commercial Cooking Recirculating System?
Chapter 2 – Definitions
Outdoor or return air for forced-air heating and cooling systems shall not be taken closer than what minimum distance from an appliance vent outlet?
618.3
Openings through concrete or masonry building elements for pipe penetrations must be protected by what?
1206.4
A small flame that is utilized to ignite the gas at the main burner or burners is a:
Chapter 2 – Definitions
Provisions in the appendices shall apply only when specifically what?
101.2.1
What is the portion of a building included between the upper surface of the topmost floor and the ceiling or roof above?
Chapter 2 – Definitions
Gas-fired appliances shall be vented in accordance with which other code?
801.1
Outdoor air inlets serving a nonresidential portion of a building must be covered with a screen having openings larger than 1/4 inch (6.4 mm) and not larger than what maximum size?
618.4
What is the maximum vertical spacing allowed for supporting Copper or copper-alloy pipe?
Table 305.4
In indirect solar thermal hot water heating systems, what is prohibited from being connected to the solar heating loop?
1402.5.1, 8
Uninsulated single-wall metal pipe is prohibited from being used outdoors for venting appliances in regions where the 99-percent winter design temperature is below what temperature?
503.7.2
Penetrations of floor/ceiling assemblies and assemblies required to have a fire-resistance rating must be protected in accordance with the:
302.2
Where an exterior masonry chimney serves two or more draft-hood equipped space-heating appliances (NAT+NAT) in a climate zone with a Local 99% Winter Design Temperature of 5 to 16°F, with a vent height of 10 feet and an internal area of 50 square inches, what is the minimum allowable input rating in thousands of Btu per hour?
504.3; Table 504.3(6b)
Which type of vent is listed and labeled for use with listed Category II, III and IV appliances?
Chapter 2 – Definitions
Full-face flange gaskets must be used with all flanges made of which type of material?
403.12
That portion of an appliance designed for the attachment of a draft hood, vent connector or venting system is the:
Chapter 2 – Definitions
Hangers and anchors for piping support must be attached to the building construction in what manner?
305.3
A nonadjustable device built into an appliance, or made as part of the vent connector from an appliance, that is designed to provide for ready escape of flue gases in the event of no draft, backdraft, or stoppage is a:
Chapter 2 – Definitions
Stainless steel pipe and tubing for hydronic systems must conform to which specific set of ASTM standards?
Table 1202.4
For the purposes of this code, if a word is used in the present tense, it includes which other tense?
201.2
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 4-inch radius mitered 45-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
Which portions of a hydronic piping system are an exception to the requirement that the entire system must be designed and installed to permit draining?
1206.2 Exception
Factory-built solar thermal collectors must bear a label showing the manufacturer’s name and what two other pieces of information?
1404.1, 21
All of the written, graphic and pictorial documents prepared or assembled for describing the design, location and physical characteristics of the elements of the project necessary for obtaining a mechanical permit are:
Chapter 2 – Definitions
Coverage for piping systems extends from the point of delivery to the outlet of which component?
101.2.3
An employee charged with the enforcement of this code is relieved from personal liability provided they are acting for the jurisdiction in good faith and without what?
104.8
Which joint type is explicitly excluded from the first definition of a Mechanical Joint?
Chapter 2 – Definitions
For a Pet shop (animal areas), recirculation of air is prohibited and mechanical exhaust is required based on which Table 403.3.1.1 note?
Table 403.3.1.1 Note b
Explosion control systems must be designed and installed in accordance with which section of the International Fire Code?
310.1
Appliances installed in outdoor locations must be either listed for outdoor installation or provided with protection from:
303.6
Class IC Flammable Liquids have a flash point at or above 73°F (23°C) and below what maximum temperature?
Chapter 2 – Definitions
What is defined as a single unit providing complete, independent living facilities, including permanent provisions for living, sleeping, eating, cooking and sanitation?
Chapter 2 – Definitions
When granting modifications due to practical difficulties, the code official must first find that the modification does not lessen which requirement?
104.2.4
Occupiable spaces may be combined into a single Zone if they share similar occupancy classification (Table 403.3.1.1), occupant density, zone air distribution effectiveness, and what fourth factor?
Chapter 2 – Definitions
Which type of hood is NOT allowed to be used over extra-heavy-duty cooking appliances?
507.2.10.1
Mechanical systems shall not be located in which specific building element?
303.8
A pipe or other conduit composed of factory-made components, containing a passageway for conveying combustion products and air to the atmosphere, listed and labeled for use with a specific type or class of appliance, is a:
Chapter 2 – Definitions
Shutoff valves are not required at heat exchangers that are integral with a boiler, or capable of being isolated by supply and return valves required by which section?
1205.1.1 Exception
Where earthquake loads are applicable, supports for appliances must be designed and installed for seismic forces in accordance with the requirements of the:
301.12
Every boiler or modular boiler must have a shutoff valve in which two piping components?
1005.1
If an alternative material, design, or method of construction is not approved, the code official shall respond in writing stating what?
104.2.3.2
Condensate piping from condensing fuel-burning appliances must maintain a minimum horizontal slope in the direction of discharge of not less than what slope?
307.1
Which inert gas is permitted as the test medium for R-744 refrigeration systems?
1110.3
Transition ducts connecting a domestic dryer to the exhaust duct system shall not be more than what maximum length?
614.9.3
What is the minimum test duration required for each 500 cubic feet (14.2 m3) of pipe volume or fraction thereof in a gaseous hydrogen system?
705.3.5
An agency seeking approval must disclose all possible conflicts of interest to confirm its what?
301.8.2.1
The approval and installation of fuel gas distribution piping, equipment, fuel gas-fired appliances, and their venting systems shall be in accordance with which other code?
301.6
Provisions contained in the appendices shall apply only if they are:
101.2.1
What is the capacity in cfh for 1-inch nominal Schedule 40 metallic pipe at 500 feet in length, operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(7)
Where laboratory burners and gas lights are installed such that the aggregate input rating exceeds 20 Btu per hour per cubic foot of volume of the room, what must be provided?
501.8
For a single appliance vented by a masonry chimney using a single-wall metal connector (Table 504.2(4)), if the height (H) is 8 feet and the lateral (L) is 8 feet, what is the maximum input rating (NAT Max) for a 12-inch connector?
504.2; Table 504.2(4)
When required for alternative materials or designs, a peer review report must be prepared by a peer reviewer who is approved by the:
104.2.3.7
A gas-burning, automatically operated appliance for supplying cooled air, dehumidified air, or both, or chilled liquid is a(an):
Chapter 2 – Definitions
Panel Heating usually consists of warm water piping, warm air ducts, or what other element embedded in or located behind ceiling, wall or floor surfaces?
Chapter 2 – Definitions
Outlets for exhaust that exceed 600°F (315°C) shall be designed as what feature in accordance with Table 510.2?
510.2
Where the fuel supply line is taken from the top of a tank that is above the level of the burner inlet connection, what must be installed in lieu of the shutoff valve?
1301.4
Where plastic piping is used to vent a listed appliance, the appliance manufacturer’s instructions must identify what characteristic of the plastic piping?
503.4.1
An Evaporative Cooler is a device used for reducing the sensible heat of air for cooling by the process of evaporation of water into what?
Chapter 2 – Definitions
Flexible ducts and air connectors are prohibited from passing through what type of building assembly?
607.7
Exhaust ducts under positive pressure, chimneys, and vents are prohibited from extending into or passing through which other duct components?
601.4
Ventilation Air is that portion of supply air that comes from the outside (outdoors), plus any recirculated air that has been treated to maintain what?
Chapter 2 – Definitions
Materials, equipment, and devices shall not be reused unless they are in good working condition and meet what other requirement?
104.9.1
Heat-fusion joints for polypropylene (PP) pipe and tubing joints in ground-source systems must be installed in accordance with which ASTM standard?
1210.6.7.1
Lead pipe requires continuous support in the horizontal direction and what maximum spacing in the vertical direction?
Table 305.4
An installation of pipe, valves or fittings installed on a premises or in a building and utilized to convey fuel gas is defined as:
Chapter 2 – Definitions
Which material is explicitly prohibited from being reused in ground-source heat pump loop systems?
1210.2
Threaded and flanged connections in hydrogen service piping are prohibited except in which two locations?
704.1.2.4
Pipe insulation installed in buildings must have a maximum smoke-developed index not exceeding what value?
1204.1
Collectors and separators for dust, stock, and refuse systems must be located on the exterior of the building or structure and not nearer than how many feet to combustible construction or unprotected wall/floor opening?
510.1.1
Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with which code?
301.11
For ducts having a static pressure classification of less than 2 inches of water column (500 Pa), additional closure systems are not required for continuously welded joints and seams and locking-type joints and seams, but this exception does not apply to which joint types located outside of conditioned spaces?
603.9 Exception
If the outdoor air ventilation system in a dwelling unit does not operate continuously, what is the minimum required operation time within each 4-hour period?
403.3.2.1 Exception 1
The register of a floor furnace with a horizontal warm-air outlet shall not be placed closer than what minimum distance to the nearest wall?
609.2
For equipment with a capacity over 125 tons up to 250 tons of refrigeration, what is the minimum required condensate pipe diameter?
Table 307.2.2
Solder joints in a metal pipe transitioning to PE-RT pipe shall not occur within what minimum distance of the transition point?
1203.16.2
A Class B Toxicity classification for a refrigerant indicates what characteristic?
Chapter 2 – Definitions
Alternative materials, designs, or methods of construction are permitted provided the alternative is not specifically prohibited by this code and has been:
104.2.3
What is the minimum separation distance required for the atmospheric venting of CNG from CNG dispensers?
413.10.2.3; Table 413.10.2.3
What must an approved agency periodically perform to verify that labeled equipment and appliances are representative of those tested?
301.8.2
A Duct Furnace depends on a blower not furnished as part of the furnace for what purpose?
Chapter 2 – Definitions
When using Type B double-wall gas vent connected directly to a single Category I appliance, if the vent height (H) is 10 feet and the vent diameter (D) is 6 inches, what is the maximum input rating (FAN Max) for a Fan-Assisted Combustion System?
504.2; Table 504.2(1)
What is the minimum horizontal distance required between exhaust outlets for grease ducts and adjacent property lines?
506.3.13.3
Solvent cement conforming to ASTM F493 shall be applied to all joint surfaces for which plastic pipe material?
1203.3.4
If the code official finds the proposed work conforms to requirements and fees have been paid, what action shall be taken?
105.4
Appliance connections to a chimney or vent equipped with a power exhauster must be made on which side of the exhauster?
801.14, 8
Local exhaust to capture leakage from indoor portable tanks containing highly toxic or toxic compressed gases must be located where?
502.9.8.2
When using the Combination Indoor and Outdoor Combustion Air method, how is the outdoor opening size reduction factor determined?
304.7.3
A field-constructed chimney of metal is a:
Chapter 2 – Definitions
When vents pass through insulated assemblies, what must be installed to provide clearance between the vent and the insulation material?
802.8, 18
Before a permit is issued, the code official is authorized to perform what action?
105.3.1
For natural gas systems, where is a system shutoff valve considered to be if it is provided after the outlet of the service meter assembly?
Chapter 2 – Definitions
The code official is authorized and directed to perform which primary action regarding the provisions of this code?
104.1
What is the minimum test duration required for a gaseous hydrogen system test?
705.3.5
The ventilation system for gas rooms, exhausted enclosures, and gas cabinets must be designed to operate at what pressure relative to the surrounding area?
502.8.2
A warm-air furnace normally installed in an air distribution duct to supply warm air for heating, depending for air circulation on a blower not furnished as part of the furnace, is a:
Chapter 2 – Definitions
The occupant load utilized for the design of a ventilation system shall be not less than the number determined from what source?
403.3.1.1
Where a factory-built chimney passes through insulated assemblies, the insulation shield shall be constructed of steel having a minimum thickness of 0.0187 inch, which is equivalent to what gauge?
503.5.11
A Type B-W gas vent shall terminate not less than what minimum vertical height above the bottom of the wall furnace?
503.6.6
Equipment, materials, products or services included in a list published by an organization acceptable to the code official that maintains periodic inspection of production or evaluation of services is defined as:
Chapter 2 – Definitions
What is the approximate length of the threaded portion required to be cut for a 1 1/4-inch iron pipe size?
403.8.2; Table 403.8.2
Where conflicts occur between this code and the conditions of listing or manufacturer’s instructions, which provisions shall generally apply?
304.2
According to Table 308.4.2, what is the reduced clearance for a vertical combustible assembly if the required clearance without protection is 18 inches and the protection is 3 1/2-inch brick wall against the combustible wall?
Table 308.4.2
Where is a Double Island Canopy Hood placed?
Chapter 2 – Definitions
For piping systems having a volume of more than 24,000 cubic feet (680 m3), the duration of the pressure test shall not be required to exceed what maximum period?
705.3.5
The minimum distance through air measured between the heat-producing surface of the mechanical appliance, device or equipment and the surface of the combustible material or assembly is defined as:
Chapter 2 – Definitions
What is the capacity in thousands of Btu/h for 2-inch nominal Schedule 40 metallic pipe at 1,000 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(28)
Appliances equipped with draft hoods or atmospheric burners shall not be located in the same room or space containing a Type I or Type II hood unless the appliance is located in what?
507.1.3
Commercial clothes dryers (Type 2) installed in multiple installations require the exhaust fan to operate continuously or be interlocked to operate when what condition occurs?
614.1
Factory-built chimneys for medium-heat appliances producing flue gases above 1,000°F (538°C) measured at the entrance to the chimney must comply with which UL standard?
805.6, 39
A room or space in which people sleep, which can also include permanent provisions for living, eating and either sanitation or kitchen facilities, but not both, is a:
Chapter 2 – Definitions
It shall be the duty of the permit holder to provide access to and means for inspection of such work that is required by this code and to notify the code official when the work is:
111.2.2
Subslab soil exhaust system ducts shall have a minimum slope in the direction of discharge of not less than what slope?
511.3
Which portion of the piping is NOT required to be insulated in a solar thermal system?
1402.8.3.1 Exception, 15
Where conflicts occur between provisions of this code and the referenced standards, which provisions shall apply?
102.8.1
What is the minimum finished dimension required for a cleanout opening located at the base of the shaft in a common multistory duct system for clothes dryers?
504.11
For PEX piping systems, testing with a compressed gas is permitted as an alternative to hydrostatic testing only if specifically authorized by what documentation?
1208.1 Exception
If excavated soil contains rubble that would damage the piping, clean backfill shall be required where?
111.2
During the brazing operation, the inert gas supply must be maintained through the piping at a minimum pressure of 1.0 psi (6.89 kPa) and what maximum pressure?
1108.3.1
Louvers that protect air intake openings in structures located in hurricane-prone regions, as defined in the International Building Code, shall comply with which standard?
401.5
Venting systems must be designed and constructed to develop a positive flow adequate to convey all combustion products to where?
801.4
The operating mechanism for natural ventilation openings shall be provided with ready access so that the openings are readily controllable by whom?
402.1
Draft hoods and barometric draft regulators must be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the hood or regulator and which system?
503.12.5
What is the maximum temperature for the metallic mixtures or alloys used in a Soldered Joint?
Chapter 2 – Definitions
Fuel oil pumps (not integral to an appliance) must be listed and labeled in accordance with which UL standard?
1302.7
In a Brazed Joint, the metallic mixtures or alloys used to join metal parts must melt at a temperature above what threshold?
Chapter 2 – Definitions
On down-flow units that do not have provisions to install a secondary drain pan, where must a water-level monitoring device be installed?
307.2.3.1
The installation of conversion burners must conform to which standard?
919.1
Who is the designated authority charged with the administration and enforcement of this code?
Chapter 2 – Definitions
Crimp joints for round and oval metal ducts must be lapped not less than what minimum dimension?
603.4.2
Where equipment, other than piping, is located outside a building and within what minimum distance of any building opening, shall such equipment be governed by the occupancy classification of the building?
1103.2
For structures located in flood hazard areas, appliances, equipment, and system installations must be located at or above the elevation required by which section of the International Building Code?
301.11
Condensate from cooling coils shall be conveyed to an approved place of disposal and shall not discharge into a street, alley, or other areas so as to cause what?
307.2.1
Appliances installed in other than indoor locations must be listed and labeled for what type of installation?
303.6
Which two CGA standards, along with CGA S-1.3, govern the sizing and selection of pressure relief devices for gaseous hydrogen systems?
703.3
Equipment, materials or products to which have been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory or approved agency is defined as:
Chapter 2 – Definitions
Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending not less than how many inches above adjoining grade?
304.1
The issuance of a permit based on construction documents shall not prevent the code official from thereafter requiring the correction of what?
105.4.2
Nonmetallic pipe utilized for fuel oil systems must conform to which standard listed in Table 1302.3?
1302.3
What is the maximum capacity in cfh for 2 1/2-inch nominal Schedule 40 metallic pipe at 400 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(1)
A joint made in thermoset plastic piping by the use of an adhesive substance that forms a continuous bond between the mating surfaces without dissolving either one of them is a:
Chapter 2 – Definitions
The connection of solid fuel appliances to chimney flues serving fireplaces must comply with which two specific sections?
905.2
In System D for combustible wall pass-through, what is the required minimum clearance to combustibles?
Table 803.10.4, 27
What is the maximum capacity in cfh for 3/4-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 500 feet in length, operating at less than 2 psi inlet pressure with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(20)
Domestic booster fans are prohibited from being installed in which system?
504.6
If an appliance creates a positive pressure in the venting system using a forced or induced draft system, the venting system must be designed and listed for what specific application?
801.9
A flame, spark or hot surface capable of igniting flammable vapors or fumes is a(an):
Chapter 2 – Definitions
Which plastic pipe material is specifically prohibited from use in supplying fuel gas?
403.5
What must be provided where a spill or accidental release of highly toxic liquids can be expected to release highly toxic vapors at normal temperature and pressure?
502.9.6.1
Any portions of construction that do not comply with this code shall be corrected and shall not be covered or concealed until authorized by the:
111.2.3
Commercial electric cooking appliances must be listed and labeled in accordance with which UL standard?
917.1
Where do Direct-Vent Appliances derive all air for combustion?
Chapter 2 – Definitions
What is the capacity in cfh for 2-inch nominal Schedule 40 metallic pipe at 500 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(4)
For a round galvanized steel duct with a diameter of 18 inches operating at 1-inch water gauge static pressure in a single dwelling unit, what is the minimum sheet metal thickness required?
Table 603.4
Members of the board of appeals must be qualified by experience and training on matters pertaining to the provisions of this code and must not be:
112.3
Any material not defined as noncombustible is defined as:
Chapter 2 – Definitions
A notice of violation served by the code official shall direct the discontinuance of the illegal action or condition and the:
113.2
For a Type B double-wall vent serving two or more Category I appliances with single-wall metal connectors (Table 504.3(2)), if the vent height (H) is 10 feet and the connector rise (R) is 1 foot, what is the minimum input rating (FAN Min) for a 5-inch connector?
504.3; Table 504.3(2)
What is the maximum spacing of supports (in feet) required for horizontal smooth-wall copper tubing with a 5/8-inch outside diameter (O.D.)?
415.1; Table 415.1
If the code official determines a mechanical system has become hazardous to life, health, or property, what must be specified in the written order to remove or restore the system?
114.6.1
Any person who begins work on a mechanical system before obtaining necessary permits shall be subject to what fee, in addition to the required permit fees?
108.4
Products of combustion from appliances plus excess air plus dilution air in the vent connector, gas vent or chimney above the draft hood or draft regulator are defined as:
Chapter 2 – Definitions
Where must the design outdoor air balance be included in design plans for a facility with a commercial kitchen ventilation system?
508.1.3
Exhaust ducts for domestic clothes dryers must have a smooth interior finish and be constructed of metal not less than what minimum thickness?
614.9.1
What is the primary function of a Stop Valve?
Chapter 2 – Definitions
When the code official finds work regulated by this code being performed in a manner contrary to the provisions of this code, the code official is authorized to issue what?
115.1
The piping in a solar loop must be insulated in accordance with the requirements of which code?
1402.8.3.1, 15
Where return air risers serve two or more stories and are part of a return air system having a design capacity greater than 15,000 cfm (7.1 m3/s), where must smoke detectors be installed?
606.2.3
A primarily vertical structure containing one or more flues, for the purpose of carrying gaseous products of combustion and air from an appliance to the outside atmosphere is a:
Chapter 2 – Definitions
Piping and piping system components for hydronic systems shall be sized based on what factor?
1201.2
Commercial-industrial-type incinerators shall be constructed and installed in accordance with which NFPA standard?
607.1
Which of the following is considered Solid Fuel for commercial cooking applications?
Chapter 2 – Definitions
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter larger than 16 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than what multiple of the test pressure?
406.4
The code official has the authority to waive the submission of construction documents if the nature of the work is such that reviewing the documents is not necessary to determine what?
106.1 Exception
A listed and labeled ductless range hood is permitted in Group I-1 and I-2 occupancies where a charcoal filter is provided for what purpose?
505.7 Exception, 505.8 Exception
The installation of liquid-fueled stationary internal combustion engines and gas turbines, including exhaust and fuel piping, must meet the requirements of which standard?
915.1
Factory-built cremation furnaces and commercial direct-fed incinerators must be listed and labeled in accordance with which UL standard?
907.1
What does a notice of violation or order issued by the code official direct the responsible person to do?
114.2
This code shall not require changes to the construction documents or construction of a structure for which a lawful permit was issued, provided the construction was pursued in good faith within how many days after the effective date of this code?
105.5.6
An automatic shutoff valve installed in the gas supply piping that shuts off when unsafe conditions occur and remains closed until manually reopened is a(an):
Chapter 2 – Definitions
Which systems are not required to comply with Chapter 11?
1101.1.2
Air that is introduced into a draft hood and is mixed with the flue gases is defined as:
Chapter 2 – Definitions
Hydrogen-generating and refueling appliances must be installed and located in accordance with their listing and what other documentation?
304.5
The purpose of an Energy Recovery Ventilation System is to preheat, precool, humidify, or dehumidify outdoor ventilation air prior to supplying such air to a space using what mechanism?
Chapter 2 – Definitions
Where grease duct enclosures are not required, what is the minimum clearance required from combustible construction for Type I hood grease duct systems?
506.3.6
Commercial refrigerators, freezers, beverage coolers, and walk-in coolers must be tested in accordance with UL 471 or which other standard?
Table 1101.2
Masonry chimneys used to vent fuel-fired appliances shall be located, constructed and sized as specified in what documentation?
801.15, 8
Oil-fired appliances shall be vented in accordance with this code and which specific standard?
801.2.1
Access points for dampers must be permanently identified on the exterior by a label having letters not less than what height?
607.4.2
What is the capacity in cfh for CSST Flow Designation 48 at 200 feet in length, with an initial supply pressure of 11.0 in. w.c. or greater and a 6.0 in. w.c. pressure drop?
402.4; Table 402.4(17)
A Ductless Mini-Split System is comprised of one or multiple indoor evaporator/air-handling units and an outdoor condensing unit that is connected by refrigerant piping and what other feature?
Chapter 2 – Definitions
Where the area beneath a veranda, porch, deck, or balcony is open on not less than two sides, what is the minimum clearance (Clearance K) required to the underside of that structure for a vent terminal?
503.8; Table 503.8
In an Absorption Refrigeration System, an Indirect System circulates a brine coil cooled by the refrigerant to the material or space refrigerated, or utilizes it to cool what?
Chapter 2 – Definitions
When a change in occupancy is made, who must certify that the structure meets the intent of governing law for the proposed new occupancy and does not result in any hazard?
102.5
A field-constructed chimney composed of solid masonry units, bricks, stones or concrete is a:
Chapter 2 – Definitions
When is the code official authorized to make a disconnection of a defective installation immediately without written notice?
113.6.1
For residential-type appliances, if not installed in unconditioned areas, a vent connector made of galvanized sheet steel must be not less than what minimum thickness?
503.10.2.3
Which type of appliance is explicitly stated to not be governed by the methods of providing combustion air detailed in Chapter 7?
701.1
Which venting system is permitted for listed combination gas and oil-burning appliances?
503.4; Table 503.4
A vented appliance wherein the primary function lies in the aesthetic effect of the flames is a:
Chapter 2 – Definitions
Clothes dryer installations exhausting more than how many CFM shall be provided with makeup air?
504.7
An occupant or person having charge of a premises shall not fail or neglect to permit entry by the code official if the code official has first obtained a:
104.4.1
Where a connector passes through an unheated space, what type of construction shall the connector NOT be?
803.2, 19
A device placed in a gas line for reducing, controlling and maintaining the pressure in that portion of the piping system downstream of the device is a:
Chapter 2 – Definitions
What is the minimum temperature of the products of combustion at the point of entrance to the flue for a High-heat appliance under normal operating conditions?
Chapter 2 – Definitions
The code official shall designate the evaluation service of an approved agency to review the evaluation report for adequacy and conformance to this code. What is this designated agency known as?
111.2.5.1
A unit consisting of a burner and its controls for installation in an appliance originally utilizing another fuel is a:
Chapter 2 – Definitions
What is the minimum outside diameter (O.D.) tube size for corrugated stainless steel tubing (CSST) that is approved for a gas flow of 245 cfh at 25 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(16)
What causes the formation of Condensate?
Chapter 2 – Definitions
Steam bath equipment must be listed and labeled in accordance with which UL standard?
931.1
A conductor installed to electrically connect metallic gas piping to the grounding electrode system is a:
Chapter 2 – Definitions
What is the primary integral feature of Compensating Hoods?
Chapter 2 – Definitions
An automatically operated assembly of integrated systems for generating electrical energy and recoverable thermal energy that is permanently connected and fixed in place is a:
Chapter 2 – Definitions
The prohibition of fuel-fired appliances in certain rooms does not apply to direct-vent appliances that obtain all combustion air from where?
303.3 Exception
For 1/2-inch nominal OD Polyethylene plastic tubing (SDR 7) at a length of 100 feet, what is the capacity in cubic feet per hour (cfh) for natural gas with a 0.3 in. w.c. pressure drop?
402.4; Table 402.4(23)
To prevent the accumulation of flammable vapors during floor resurfacing, what is the minimum mechanical ventilation rate required per square foot of area being finished?
502.7.7
Joints between polyethylene plastic pipe and tubing for ground-source heat pump loop systems must be heat-fusion joints, electrofusion joints, or what third type of joint?
1210.6.6
What is the capacity in cfh for 3-inch nominal Schedule 40 metallic pipe at 250 feet in length, with an initial supply pressure of 8.0 in. w.c. or greater and a 3.0 in. w.c. pressure drop?
402.4; Table 402.4(3)
What is the minimum air gap required between a clearance reduction system using a ventilated airspace and combustible walls and ceilings?
308.2
Ducts used in systems exhausting nonflammable corrosive fumes or vapors must be constructed of nonmetallic materials that exhibit what maximum flame spread index?
509.8
Limited spraying spaces must have positive mechanical ventilation that provides not less than how many complete air changes per hour?
502.7.2
Where the maximum horizontal length of a connector (for multiple appliances) is exceeded, the maximum capacity (FAN Max or NAT Max) of the vent connector must be reduced by what percentage for each additional multiple of the allowed length?
504.3.3
The loss in pressure due to friction or obstruction in pipes, valves, fittings, regulators and burners is defined as:
Chapter 2 – Definitions
Which type of refrigeration system is defined as having a high probability that leaked refrigerant could enter an occupied area?
1103.3.2
What material is specified as a required thermal break where a heated slab meets a foundation wall or other conductive slab?
1209.5.1
Where two or more openings are provided into one chimney flue or vent, the connectors must be attached to the vertical portion at an angle of not more than how many degrees relative to the vertical?
503.10.4.1
Which commercial appliances are an exception to the general requirement to discharge products of combustion to a vent, factory-built chimney, or masonry chimney?
801.2 Exception, 507
Products of combustion plus excess air in appliance flues or heat exchangers are defined as:
Chapter 2 – Definitions
For a chimney serving low-heat appliances (1,000°F normal operation), what is the minimum required clearance to combustible construction for interior installation?
Table 510.2
Which process is typically used at a field job site or local service shop to reduce contaminants for Recycled Refrigerants?
Chapter 2 – Definitions
For all environmental air exhaust, what is the minimum termination distance from a property line?
501.3.1
Smoke detectors are not required in the return air system if all portions of the building served by the air distribution system are protected by what type of system?
606.2.1 Exception
What is the capacity in thousands of Btu/h for 1 1/2-inch nominal Schedule 40 metallic pipe at a length of 100 feet, for undiluted propane with an inlet pressure of 10.0 psi and a 1.0 psi pressure drop?
402.4; Table 402.4(25)
What is the minimum inside diameter required for a fuel oil supply line pipe?
1305.1
An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere is a(an):
Chapter 2 – Definitions
When calculating minimum capacity for a single appliance installed at high altitude, which input rating shall be used?
504.2.5
Where shall the listing and labeling of equipment and appliances used for refrigeration be in accordance with?
301.7 Exception
Exhaust ventilation for powder-coating operations must be sufficient to maintain the atmosphere below what concentration of the minimum explosive concentration?
502.7.6
Where multiple air-handling systems share common supply or return air ducts or plenums, smoke detectors are required if the combined design capacity is greater than what rate?
606.2.2
A permit issued by the code official for temporary uses, equipment, and systems shall not be permitted for more than how many days?
110.1
In the definition of Commercial Cooking Appliances, what is the criteria regarding the preparation of food?
Chapter 2 – Definitions
Where a device having an open flame or surface temperature greater than 800°F (427°C) is used in a room containing more than 6.6 pounds (3 kg) of refrigerant in a single independent circuit, what must be provided?
1104.3.4
A Drain-Back System is a solar thermal system in which the fluid in the solar collector loop is gravity drained into a holding tank under what circumstances?
Chapter 2 – Definitions
Guards shall be constructed so as to prevent the passage of a sphere of what maximum diameter?
304.11
An exception permits fuel-burning appliances in a machinery room if the combustion air is ducted from outside and sealed, or if what device is employed to automatically shut off the combustion process?
1105.5 Exception 2
Relief valve discharge piping must terminate not more than how many inches above the floor or flood level rim of the waste receptor?
1006.6
The liquid that condenses from a gas (including flue gas) caused by a reduction in temperature or increase in pressure is defined as:
Chapter 2 – Definitions
As an alternative to prescriptive ventilation methods for hydrogen-generating operations, air supply for ventilation and dilution of flammable gases may be provided by what type of system?
304.5.3
What must be provided for existing chimneys and vents in accordance with the International Building Code?
801.18.4.1, 14
Single-wall metal pipe must extend not less than 2 feet above the highest point where it passes through a roof and not less than what minimum height higher than any portion of a building within a horizontal distance of 10 feet?
503.7.3
Which regulator reduces gas pressure from the range of greater than 0.5 psig (3.4 kPa) and less than or equal to 5 psig (34.5 kPa) to a lower pressure?
Chapter 2 – Definitions
The container placed at a low point in a system of piping to collect condensate and from which the condensate is removable is a:
Chapter 2 – Definitions
If means for isolation of vibration of an appliance is installed, what else must be provided?
301.8
Mechanically ventilated shafts using a refrigerant detector must activate the ventilation at a maximum refrigerant concentration of what percentage of the lower flammable limit (LFL) of the refrigerant?
1109.3.2
Where vents pass through attic space, how high above the insulation materials must the insulation shield terminate?
802.8, 18
Ducts in a private garage that penetrate a wall or ceiling separating a dwelling from the garage must be constructed of sheet steel having a minimum thickness of not less than what gauge?
603.7
The purpose for which a building, or portion thereof, is utilized or occupied is defined as the:
Chapter 2 – Definitions
What is the minimum distance required between an air intake opening and a lot line or building on the same lot?
401.4
For appliances in attics, the continuous solid flooring of the passageway must be not less than what minimum width?
306.3
Mechanical ventilation shall be provided by a method of supply air and what other air type, except for certain residential occupancies?
403.1
In conjunction with a request to use an alternative material, the code official is authorized to require submittal of a report prepared by a peer reviewer acceptable to the code official. What type of report is this?
104.2.3.7
Which material fittings are strictly prohibited from being used in fuel oil piping systems?
1303.1
Applications for alternative materials, design, and methods of construction and the final decision of the code official shall be:
104.7.3
A gas having a moisture and hydrocarbon dew point below any normal temperature to which the gas piping is exposed is defined as:
Chapter 2 – Definitions
Where the refrigerant-containing parts of a system are located in one or more spaces that do not communicate through permanent openings or HVAC ducts, the volume of which space determines the permissible refrigerant quantity?
1104.4.1
What is the maximum acceptable average optical density for combustible electrical wires and cables exposed within a plenum, when tested in accordance with NFPA 262?
602.3.3
What is the minimum clearance required to combustibles for hazardous exhaust ducts conveying exhaust gases with temperatures between 100°F and 600°F?
Table 509.8.2
Oil-fired water heaters must comply with which UL standard?
1002.1
Where a single meter supplies gas to more than one building or tenant, what type of valve must be provided for each building or tenant?
409.3
Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used, and where a weld opens during the cutting or threading operation, that portion of the pipe shall not be used.
403.8.1
Defective material or parts must be replaced or repaired in a manner that preserves which characteristic?
301.9
A manually operated valve in the gas line for the purpose of completely turning on or shutting off the gas supply to the appliance, except to pilot(s) provided with independent shutoff, is a(an):
Chapter 2 – Definitions
A valve designed to activate when the fuel gas passing through it exceeds a prescribed flow rate is a(an):
Chapter 2 – Definitions
What is the minimum required clearance from the top of a hot water-heating boiler with manholes on top to the ceiling?
Table 1004.3.1
An employee charged with the enforcement of this code is relieved from personal liability for damages if acting for the jurisdiction in good faith and without:
104.8
An operation performed to verify the gastight integrity of gas piping following its installation or modification is a:
Chapter 2 – Definitions
For ducts conveying explosive or flammable vapors, fumes or dusts, what is the minimum termination distance from a property line?
501.3.1
What is the minimum fire-resistance rating required for a grease duct enclosure?
506.3.11
What is strictly prohibited from connecting to a chimney passageway venting another appliance?
801.11, 6
Which category of condensing appliances must be provided with an auxiliary drain pan where damage to any building component will occur as a result of a stoppage?
307.5
An unvented gas log heater can only be installed in a factory-built fireplace if the system has been specifically tested, listed, and labeled for such use in accordance with which standard?
903.3
Welding on pressure vessels must be performed by an R-Stamp holder in accordance with the National Board Inspection Code, Part 3, or what other requirement?
1003.3
Linings must be interrupted at the area of operation of a fire damper and not less than how many inches upstream and downstream of electric-resistance and fuel-burning heaters?
604.8
The code official shall issue all necessary notices or orders to ensure:
104.6
Vented gas fireplaces shall be listed in accordance with which ANSI/CSA standard?
604.1
When soldering on the metal portion of a PEX plastic tubing system, the solder joints shall be performed not less than what minimum distance from a plastic-to-metal adapter in the same water line?
1203.9.2
For a mechanically ventilated refrigerant pipe shaft with a cross-sectional area of 30 square inches, what is the minimum ventilation velocity required?
Table 1109.3.2
After an installation has been ordered disconnected by the code official, a person may not make energy source connections until who authorizes the reconnection and use of the installation?
113.6.3
A completely self-contained heating unit that is designed to supply heated air to spaces remote from or adjacent to the appliance location is a:
Chapter 2 – Definitions
For appliance shutoff valves located at a manifold, what is the maximum distance allowed between the manifold and the appliance served?
409.5.3
What is the capacity in cfh for 3-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 100 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(21)
The approval of unlisted appliances must be based on:
301.3
The board of appeals shall not have the authority to:
112.2
Appliances located in public garages or repair garages shall be installed not less than how many feet above the floor?
304.6
A self-contained package of integrated systems for generating electrical energy and recoverable thermal energy that is permanently connected and fixed in place is defined as what?
Chapter 2 – Definitions
Joints between different metallic fuel oil piping materials must be made with approved dielectric fittings or what other type of fitting?
1303.1.1
Safety and safety relief valves must be set at not greater than what value of the boiler or pressure vessel?
1006.4
In areas designated as Zone AO where a depth number is not specified on the flood hazard map, the depth number used for the Design Flood Elevation shall be taken as equal to what value?
Chapter 2 – Definitions
In naturally ventilated hydrogen-generating locations, equipment and appliances having an ignition source shall be located such that the source of ignition is not within how many inches of the ceiling?
304.5.1
What specific type of gauge is prohibited on a fuel oil tank if, when broken, it would permit the escape of oil?
1306.5
A fuel cell generator of electricity, which is not fixed in place, utilizes a cord and plug connection to a grid-isolated load and has an integral fuel supply is a:
Chapter 2 – Definitions
Any heating appliance or equipment that heats potable water and supplies such water to the potable hot water distribution system is a:
Chapter 2 – Definitions
Clearance is measured as the minimum distance through air between the heat-producing surface of a mechanical appliance and what other surface?
Chapter 2 – Definitions
If a request for an alternative material or design is not approved, how shall the code official respond?
104.2.3.2
In areas containing flammable vapors or dusts, motors driving exhaust fans shall be of a type approved for what?
503.1
What is the minimum exhaust ventilation rate required for a repair garage used for compressed natural gas, liquefied natural gas, or other lighter-than-air motor fuel (other than hydrogen)?
502.16.2.1
In the Zone Outdoor Airflow rate calculation (Equation 4-2), the Breathing Zone Outdoor Airflow is divided by what value?
403.3.1.1.1.3
The code official is authorized to revoke a notice of approval if it is determined that the building or structure is in violation of what?
107.2
For a multiple zone recirculating system, if the Maximum Primary Outdoor Air Fraction [$Max (Z_p)$] is 0.40, what is the System Ventilation Efficiency ($E_v$)?
Table 403.3.1.1.2.3.2 Note b
Appliances shall not be converted to utilize a different fuel gas unless complete instructions for such conversion are provided by which source?
301.7.1
Air filters must be installed such that all return air, outdoor air, and makeup air is filtered upstream from what two components?
605.1
A technical opinion and report required by the code official shall be provided to the jurisdiction:
104.2.2.1
How shall articles being sprayed be positioned within a spray booth?
502.7.3.4
What is the maximum acceptable smoke-developed index for duct coverings and linings, including adhesives?
604.3
Where openings below grade provide required natural ventilation, the outdoor horizontal clear space measured perpendicular to the opening shall be what multiple of the depth of the opening?
402.4
Copper tubing joints that are embedded in a portion of the building (like concrete or plaster) must be joined by which method?
1209.3.2
When automatically operated, the ventilation system for an enclosed parking garage must cycle to a “Full-on” mode at an airflow rate of not less than how many CFM per square foot of floor area served?
404.1
From which of the following spaces shall return air for heating or air-conditioning systems NOT be taken?
601.5
What is the temperature range of the products of combustion at the point of entrance to the flue for a Medium-heat appliance?
Chapter 2 – Definitions
What is the maximum capacity in cfh for 1 1/2-inch nominal Schedule 40 metallic pipe at 750 feet in length, operating at less than 2 psi inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(2)
Naturally ventilated refrigerant pipe shafts (Group A2L or B2L) must have a pipe, duct, or conduit connecting the lowest point of the shaft to the outdoors, with a minimum diameter of what size?
1109.3.2
What is the capacity in cfh for 1 1/4-inch nominal OD Polyethylene plastic pipe at a length of 200 feet, for natural gas with an inlet pressure less than 2 psi and a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(21)
Appliance and equipment vent terminals must be located such that doors cannot swing within what minimum horizontal distance of the vent terminals?
802.9, 19
A device for the final conveyance of the gas, or a mixture of gas and air, to the combustion zone is a:
Chapter 2 – Definitions
Alterations such as cuts, notches, and holes bored in trusses or I-joists are prohibited except where permitted by the manufacturer’s recommendations or where the effects are specifically considered in the design of the member by whom?
302.3.1
A yellow insulated copper tracer wire or other approved conductor must be installed adjacent to underground nonmetallic piping. The minimum tracer wire size shall be not less than:
404.17.3
An operation performed on a gas piping system to verify that the system does not leak is a:
Chapter 2 – Definitions
Floor registers shall resist, without structural failure, a concentrated load of how many pounds?
603.18.1
Reports of inspection conducted by approved agencies or individuals shall be submitted in writing and certified by:
104.7.2
In the One-Permanent-Opening Method (304.6.2), the single opening must commence within what distance of the top of the enclosure?
304.6.2
For a rectangular aluminum duct with a dimension of 17 inches operating at 1/2-inch water gauge static pressure in a single dwelling unit, what is the minimum sheet metal thickness required?
Table 603.4
For listed and labeled appliances, clearances shall not be reduced where reduction is specifically prohibited by what?
308.2
The details of the written request for and action granting modifications must be recorded and entered into the files of the:
104.2.4
What is the minimum clearance required above a paved sidewalk or paved driveway located on public property (Clearance J) for a vent terminal?
503.8; Table 503.8
Which general term includes salamanders, barbecues and other appliances cooking primarily by radiated heat, excepting toasters?
Chapter 2 – Definitions
Section 308 governs the reduction in required clearances to combustible materials and assemblies for vents, kitchen exhaust equipment, mechanical appliances, and what other component?
308.1
What is the capacity in thousands of Btu per hour for CSST Flow Designation 37 at 300 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(32)
When combining indoor spaces on the same story for combustion air, one permanent opening shall commence within 12 inches of the top of the enclosure, and where must the other permanent opening commence?
304.5.3.1
Performing work on a mechanical system in conflict with or in violation of any provision of this code shall be deemed what type of act?
114.1
Piping run from a pressure-regulating device to the outdoors, designed to provide a reference to atmospheric pressure, is defined as:
Chapter 2 – Definitions
What is the minimum length (in feet) of nominal 2 1/2-inch piping that, when removed from service, must have its residual fuel gas displaced with an inert gas?
406.7.1.1; Table 406.7.1.1
What is the minimum clearance required above an appliance where the original required clearance was 6 inches, and the protection is 0.024-inch sheet metal with ventilated airspace?
308.2; Table 308.2
That which enables a device, appliance or equipment to be directly reached, without requiring the removal or movement of any panel, door or similar obstruction is defined as:
Chapter 2 – Definitions
For a Private dwelling, single and multiple, what is the required continuous exhaust rate for a Kitchen?
Table 403.3.1.1 Note f
Evaluation reports used to support alternative material approvals shall be issued by which entity?
104.2.3.6.1
The action of a control from its maximum to minimum position in either predetermined steps or increments of movement as caused by its actuating medium is defined as:
Chapter 2 – Definitions
Discrete electrical, plumbing, and mechanical products having exposed combustible material and located in a plenum must be listed and labeled for such use in accordance with which UL standard?
602.3.6
Closed-type expansion tanks for systems designed to have an operating pressure in excess of 30 psi (207 kPa) must be constructed and certified in accordance with which standard?
1009.2
An alternative material or design must be equivalent to that prescribed in this code with respect to strength, effectiveness, durability, safety, and which other criterion?
104.2.3.4
What must masonry chimneys be provided with, and this material must be compatible with the type of appliance connected?
801.16, 9
Flared joints shall be used only in systems constructed from what type of piping material?
403.9.4
What is the minimum depth required for an auxiliary drain pan?
307.2.3
What is the maximum capacity in thousands of Btu per hour for 1 1/2-inch nominal O.D. Polyethylene plastic pipe (SDR 11) at 500 feet in length, for undiluted propane operating at 11.0 in. w.c. inlet pressure with a 0.5 in. w.c. pressure drop?
402.4; Table 402.4(35)
How must inside tanks that are provided with fill and vent pipes be gauged to indicate when the oil has reached a predetermined safe level?
1306.3
Elements of the smoke management system relying on volatile memories must be supplied with uninterruptible power sources of sufficient duration to span how long of a primary power interruption?
512.11.2
A permittee holding an unexpired permit shall have the right to apply for an extension of time. Provided there is reasonable cause, the code official shall extend the time for a period not exceeding how many days?
105.4.4
Where are shutoff valves required on a heat exchanger?
1205.1.1
Hydronic piping systems must be tested hydrostatically at what minimum pressure?
1208.1
What is the required Exhaust Airflow Rate in CFM/ft squared for a Wood/metal shop in an education facility?
Table 403.3.1.1
Where valves are identified by a numbering or lettering system, where must the legend(s) or key(s) for the valve identification be located?
1109.6.4
What is the maximum height above grade personnel must climb to access equipment or appliances on a roof or elevated structure before an interior or exterior means of access is required?
306.5
A system designed to act to shut off the gas supply to the main and pilot burners if the oxygen in the surrounding atmosphere is reduced below a predetermined level is a(an):
Chapter 2 – Definitions
If an emergency exists, what is the code official not required to give prior to stopping the work?
115.3
Where commercial cooking appliances are vented by a fan-powered exhaust hood system, the appliances must be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating.
505.1.1
A Volume Damper is a device that restricts, retards, or directs the flow of air in a duct or what other products?
Chapter 2 – Definitions
The pressure difference existing between the appliance or any component part and the atmosphere, that causes a continuous flow of air and products of combustion, is defined as:
Chapter 2 – Definitions
In which residential occupancy is the use of corridors for conveying return air permitted?
601.2 Exception
What is the minimum separation distance required for the atmospheric venting of CNG from lot lines?
413.10.2.3; Table 413.10.2.3
For a hydrostatic leak test of a gaseous hydrogen system, what is the minimum required test pressure?
705.3.1
What is the estimated maximum occupant load rate per 1,000 square feet for a General examination room in an outpatient healthcare facility?
Table 403.3.1.1
Boilers shall be mounted on floors of noncombustible construction, unless what condition is met?
1004.5
Mechanical exhaust systems, where required in other than Group R-3 occupancies and dwelling units in Group R-2, must maintain the space with what pressure characteristic?
501.4
What specific piping must be removed when fuel oil tanks are abandoned or removed?
1301.5
What is the maximum circuit length allowed for 3/4-inch nominal tube size snow- and ice-melt tubing from a supply-and-return manifold arrangement?
Table 1209.7.1
Plenum enclosure construction materials exposed to the airflow must have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with which standard?
602.2
Tests required by this code shall be made by the permit holder and observed by the:
111.3
What is the capacity in thousands of Btu per hour for CSST Flow Designation 60 at 10 feet in length, for undiluted propane operating at 5.0 psi inlet pressure with a 3.5 psi pressure drop?
402.4; Table 402.4(34)
A through-the-wall direct-vent terminal serves an appliance rated at 40,000 Btu/h. What is the minimum clearance required to an openable window (Clearance B)?
503.8; Table 503.8
What is the primary function of the code compliance agency?
103.1
Piping, tubing, and fittings must be tested by an approved third-party testing agency or certified by which other type of agency?
301.5
What components shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance?
803.1, 19
In the absence of recognized test standards, who shall approve the testing procedures?
104.2.2.4
Fuel oil piping must be tested in accordance with which NFPA standard?
1308.1
What is the minimum number of bottom blowoff valves required for a steam boiler where the maximum allowable working pressure exceeds 100 psig (689 kPa)?
1008.1
Dry Cleaning Systems classified as Type III use Class III combustible liquid solvents having a flash point at or above 140°F (60°C) and below what maximum temperature?
Chapter 2 – Definitions
What is the approximate length of the threaded portion required to be cut for a 1-inch iron pipe size pipe?
403.8.2; Table 403.8.2
Motors for fans used to convey flammable vapors or dusts must be located outside the duct or protected with what?
503.1
A self-contained appliance for supplying steam or hot water is defined as a:
Chapter 2 – Definitions
Food-grade fluid used as a heat transfer fluid containing additives must be third-party listed by an approved agency to the appropriate section of which regulations?
1403.3, 20
A vent connector installed without dips or sags must slope upward toward the vent or chimney not less than what minimum distance per foot?
503.10.8
Domestic clothes dryer installations exhausting more than what volumetric rate must be provided with makeup air?
614.7
Exhaust duct terminations for clothes dryers, where the manufacturer’s instructions do not specify a location, shall terminate not less than what minimum distance in any direction from openings into buildings?
614.4.1
Condensate pumps located in uninhabitable spaces shall be connected to the appliance served such that when the pump fails, the appliance or equipment will be prevented from:
307.7
Condensate drains from venting systems serving Category II and IV appliances shall be installed in accordance with whose instructions?
503.9
A completely self-contained furnace suspended from the floor of the space being heated, taking air for combustion from outside such space and with means for observing flames and lighting the appliance from such space, is a:
Chapter 2 – Definitions
What is the maximum height above grade plane for Group R-2, R-3, and R-4 occupancies that must be provided with outdoor air and local exhaust in accordance with Section 403.3.2?
403.3
What type of exhaust systems are prohibited from sharing common shafts with other duct systems?
509.4
A self-contained vented appliance designed for incorporation in or permanent attachment to the structure, furnishing heated air circulated by gravity or by a fan directly into the space, excluding floor furnaces, unit heaters and central furnaces, is a:
Chapter 2 – Definitions
For ozone cabinets, what is the minimum average ventilation velocity required at makeup air openings with the cabinet doors closed?
502.9.9
What is the capacity in cfh for 2-inch nominal OD Polyethylene plastic pipe at a length of 500 feet, for natural gas with an inlet pressure of 2.0 psi and a 1.0 psi pressure drop?
402.4; Table 402.4(22)
Which vented appliance category operates with a nonpositive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent?
Chapter 2 – Definitions
A general form of gas-tight joints obtained by the joining of metal parts through a positive-holding mechanical construction is a:
Chapter 2 – Definitions
Standard air is defined as air at a temperature of 70°F (21°C) and what pressure?
Chapter 2 – Definitions
A valve, installed by the serving gas supplier between the source of supply and the point of delivery, to shut off the entire piping system, is a:
Chapter 2 – Definitions
Large mercantile occupancy is defined as premises where more than how many persons congregate on levels above or below street level to purchase personal merchandise?
1103.2
Which characteristic is true of a Ground Source Heat Pump Loop System?
Chapter 2 – Definitions
Where corrosive materials exceeding the maximum allowable quantity are dispensed or used, what specific type of exhaust ventilation must be provided?
502.9.2
For an attic passageway to an appliance, what is the maximum length allowed if the passageway is at least 30 inches high and 22 inches wide?
306.3
A flux conforming to which ASTM standard must be applied to a soldered joint?
1203.3.3
Vented wall furnaces must be located so that a door cannot swing within what minimum distance of an air inlet or air outlet of the furnace?
909.3
Single-wall metal pipe is prohibited from passing through any attic, inside wall, concealed space or:
503.7.6
When installing or repairing gas piping, the finished floors, walls, and ceilings that are required to be changed or replaced must be left in a safe structural condition in accordance with the requirements of the:
302.1
What is strictly prohibited in hazardous exhaust ducts?
509.6.1
In the context of this code, which term refers to the rapid oxidation of fuel accompanied by the production of heat or heat and light?
Chapter 2 – Definitions
The code official has authority to suspend or revoke a permit if the permit was issued in error or on the basis of:
105.5.5
What is the minimum melting point required for solder used in sweat fittings if they were permitted in fuel oil lines (though such joints are prohibited)?
1303.1
An annual permit may be issued for alterations to an already approved system upon application to any person, firm, or corporation regularly employing at least how many qualified tradespersons?
105.1.1
A Grease Duct serves which type of hood?
Chapter 2 – Definitions
Direct-fired industrial air heaters shall incorporate a means to supply outside ventilation air to the space at a rate of not less than 4 cubic feet per minute per what unit of rated input of the heater?
612.5
In Group H occupancies, fire dampers are not required at penetrations of fire partitions where the partition is penetrated by a duct system having a maximum area of what size?
607.5.3 Exception 3
Appointment of a deputy code official requires the concurrence of the:
103.3
What must be provided to solar thermal equipment for maintenance purposes?
1402.2, 4
Mechanical ventilation for ambulatory care facilities and Group I-2 occupancies shall be designed and installed in accordance with this code, NFPA 99, and which other standard?
407.1
Appliances constructed and installed so that all air for combustion is derived directly from the outdoor atmosphere and all flue gases are discharged directly to the outdoor atmosphere are defined as:
Chapter 2 – Definitions
What documentation must an approved testing laboratory provide when a product is Third-Party Tested?
Chapter 2 – Definitions
Heat-fusion joints for polypropylene (PP) pipe and tubing joints must be installed in accordance with which ASTM standard?
1203.15.1
Which classification of clothes dryer is primarily used in a family living environment and is usually the smallest unit physically and in function output?
Chapter 2 – Definitions
The code official shall have the authority to suspend or revoke a permit if it was issued on the basis of incorrect, inaccurate, or what other type of information?
105.4.5
Freeze-protection valves must discharge in a manner that does not create what two potential issues?
1402.4.2, 8
The passageway of domestic dryer exhaust duct terminals shall be undiminished in size and shall provide an open area of not less than what minimum size?
614.4.2
Grease duct-to-hood joints must be made with continuous internal or external liquid-tight welded or brazed joints that are smooth, without grease traps, and available for what?
506.3.2.2
Ducts that operate at temperatures exceeding 120°F (49°C) must have sufficient thermal insulation to limit the exposed surface temperature to what maximum temperature?
604.2
Where provided within a dwelling unit, controls for outdoor air ventilation systems must include text or a symbol indicating what?
403.3.2.4
Required test and inspection records for prefabricated mechanical systems shall be available to the code official at all times during the fabrication of the system and what other process?
111.2.5.3
Mechanical outdoor air intake openings shall be located not less than how many feet horizontally from any hazardous or noxious contaminant source?
401.4
Where must cleanouts serving horizontal sections of grease ducts be located if other locations are not available?
506.3.9
What is the Occupational Exposure Limit (OEL) in ppm for R-134a?
Table 1103.1
Which type of appliance must be used in a dwelling unit kitchen where the kitchen and living spaces are in a single room, and return air is taken within 10 feet of the cooking appliance?
601.5 Exception 2
Drain-back systems must be designed and installed to allow for manual gravity draining of fluids from areas subject to freezing to locations not subject to freezing, and what else?
1402.4.1, 7
What is the minimum thickness required for galvanized steel vent connectors?
803.8, 22
A required technical opinion and report shall be prepared by a party acceptable to the code official, such as a qualified engineer, specialist, laboratory, or what other type of organization?
104.2.2.2
What must be provided for the control circuit of a boiler that is capable of being locked in the off position?
1006.8
Where are fireplaces and solid fuel-burning appliances prohibited from being installed?
901.3
The maximum length of a domestic clothes dryer exhaust duct shall be 35 feet (10 668 mm) from the connection to the transition duct to the outlet terminal, before reductions for fittings.
614.9.4.1
The requirements for combustion and dilution air for gas-fired appliances must be in accordance with which code?
701.1
In coastal high-hazard areas and coastal A zones, mechanical systems and equipment shall not be mounted on or penetrate walls intended to do what under flood loads?
301.16.1
What specific type of damper is explicitly prohibited from being installed in combustion air ducts?
701.2
Which material is exempted from carrying the identification of the manufacturer on each length of pipe and tubing?
401.9 (Exception 1)
The code official is authorized to accept reports of approved agencies provided such agencies satisfy the requirements for qualifications and:
111.2.4
Electric kilns must comply with which UL standard?
923.1
Thread lubricant, pipe-joint compound or thread tape must be applied only on which part of a threaded joint?
1108.3.4
A permit is not required for a self-contained refrigeration system provided it contains no more than 10 pounds (4.5 kg) of refrigerant or is actuated by motors of what maximum size?
105.2
Equipment or machinery at lumber yards that generates combustible dust must be provided with an approved dust-collection and exhaust system installed in accordance with this section and what other code?
509.2.1
For exterior masonry chimneys serving two or more Category I appliances (FAN+NAT) with Type B double-wall connectors, if the vent height is 30 feet and the internal area is 113 square inches, what is the maximum combined input rating in thousands of Btu per hour?
504.3; Table 504.3(7a)
A floor furnace (excluding wall register models) shall not be placed closer than what minimum distance to the nearest wall?
910.2
Fans in systems handling materials that are capable of clogging the blades, such as buffing or woodworking exhaust systems, must be of which fan type?
503.2
If a clothes dryer is installed in a residential bathroom, what is the minimum required area for the permanent opening communicating with a space outside of a sleeping room, bathroom, toilet room or storage closet?
303.3
Air intake openings on structures in flood hazard areas must be located at or above the elevation required by which section of the International Building Code?
401.4
A device for controlling and maintaining a uniform supply pressure, either pounds-to-inches water column (MP regulator) or inches-to-inches water column (appliance regulator), is a:
Chapter 2 – Definitions
A pipe in a hydronic piping system in which the exterior temperature exceeds 250{F} must have a minimum clearance of what distance to combustible materials?
1206.5
Who has the duty to notify the code official when work is ready for inspection?
111.2.2
What is the combination of outdoor and transfer air intended to replace exhaust air and exfiltration?
Chapter 2 – Definitions
What is required to be installed where space for a domestic clothes dryer is provided but the dryer is not installed at the time of occupancy?
504.9.6
A Flexible Air Connector is limited in its use, length, and location for transferring air between an air duct or plenum and what other components?
Chapter 2 – Definitions
What is the minimum required thickness (in inches) for a galvanized steel vent connector with a diameter of 8 inches, serving a low-heat appliance?
503.10.2.4; Table 503.10.2.4
For a sloped roof (3 units vertical in 12 units horizontal or greater) where an appliance is installed and the roof edge is more than 30 inches above grade, a level platform must be provided on which side(s) of the appliance?
306.5.1
What concentration characteristic defines highly abrasive particulate that is classified as Abrasive Materials?
Chapter 2 – Definitions
Tests conducted to demonstrate equivalency for an alternative material must be of a scale that is sufficient to predict what aspect of the end use configuration?
104.2.3.5
What is the maximum pressure for steam furnished by a Low-Pressure Steam-Heating Boiler?
Chapter 2 – Definitions
If manufacturer’s instructions for a refrigerator are unavailable, what is the minimum clearance required between the back of the refrigerator and the wall?
625.1
The top of a guard required on a roof or elevated structure shall be located not less than how many inches above the elevated surface adjacent to the guard?
304.11
The greater of the following two areas: the area within a floodplain subject to a 1 percent or greater chance of flooding in any given year, or the area designated as a flood hazard area on a community’s flood hazard map, is the definition of:
Chapter 2 – Definitions
An existing chimney flue liner, inner wall, or vent inner wall must be continuous and free of cracks, gaps, perforations or other damage that would allow the escape of combustion products, including gases, moisture and:
501.15.2
Solar thermal collectors and panels must be listed and labeled in accordance with which specific standard?
1401.4.1, 12
Which components are prohibited from being attached to vented wall furnaces unless listed as part of the appliance?
909.4
Any apparatus or device that utilizes a fuel or a raw material as a fuel to produce light, heat, power, refrigeration or air conditioning is a(an):
Chapter 2 – Definitions
Return air taken from a closet smaller than 30 square feet (2.8 m2) shall require the closet door to be undercut not less than what dimension?
601.5
The imposition of penalties prescribed shall not preclude the legal officer from instituting appropriate action to prevent unlawful construction or to:
113.5
Where two bottom blowoff valves are provided, consisting of one quick-opening valve and one slow-opening valve in series, which valve must be installed closest to the boiler?
1008.1
Plastic ducts used for underground installation must be constructed of PVC having a minimum pipe stiffness of what value at 5-percent deflection?
603.8.3
What is the minimum clearance to combustibles required for chimney connectors serving medium-heat oil and solid-fuel appliances?
Table 803.10.6, 30
What is the minimum thickness required for a chimney connector serving a medium-heat appliance with an equivalent round diameter of 17 inches (Area 202–254 sq in), according to Table 803.9(2)?
Table 803.9(2), 24
Water supply and discharge connections associated with refrigeration systems must be made in accordance with this code and which other specific code?
1101.4
For Group A2L and B2L refrigerant detectors, if the concentration is less than or equal to the refrigerant concentration level (RCL), the alarm reset must be what type?
Table 1106.4.2
Indoor mechanical exhaust intake openings must be located where refrigerant leakage is likely to concentrate based on the refrigerant’s relative density to air and what other factors?
1105.6.1.1
Which classification of Dry Cleaning Systems uses Class I flammable liquid solvents?
Chapter 2 – Definitions
The clearance reduction methods in Table 308.4.2 shall not reduce the required clearance to less than how many inches for solid fuel-burning appliances labeled for installation with clearances greater than 12 inches?
308.4.2.1
Which term refers to the means that first requires the removal or movement of a panel or similar obstruction to reach a device or equipment?
Chapter 2 – Definitions
For an appliance connected by rigid metallic pipe, what is the maximum distance the union fitting can be located from the appliance?
411.1.6
For “other product-conveying outlets,” what is the minimum termination distance from exterior walls and roofs?
501.3.1
Which component is part of a Duct System?
Chapter 2 – Definitions
When inspecting structures or premises, the code official shall carry:
104.5
TABLE 614.9.4.1 QUESTION: What is the equivalent length reduction required for a 10-inch radius smooth 45-degree elbow in a domestic dryer exhaust duct?
614.9.4.1; Table 614.9.4.1
Which type of floor furnace is equipped with a fan that provides the primary means for circulating air?
Chapter 2 – Definitions
What components must be installed to allow the solar loop to be isolated from the remainder of the system?
1402.8.6.1, 18
The use of gypsum boards to form plenums is limited to systems where the air temperatures do not exceed what maximum temperature?
602.2
What is the minimum required thickness (in inches) for a steel vent connector serving a medium-heat appliance with an area between 201 and 254 square inches?
503.10.2.5; Table 503.10.2.5
A connection from a utility, source of energy, fuel, or power shall not be made to any regulated building or system for which a permit is required until authorized by the:
109.1
Water heaters utilized for both potable hot water and space-heating applications must be listed and labeled for such applications and installed in accordance with the manufacturer’s instructions and which other code?
1002.2
Plastic fire sprinkler piping exposed within a plenum shall be used only in which type of fire suppression system?
602.3.4
During what time period shall ventilation be provided for a room or space?
401.3
Which component is generally NOT included in an air distribution system?
Chapter 2 – Definitions
Which entity determines if something is “Approved” for the purposes of this code?
Chapter 2 – Definitions
Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in what structure?
1109.2.5
A room heater of the type designed for insertion in or attachment to a wall or partition that discharges all products of combustion through the front into the room being heated is a:
Chapter 2 – Definitions
Vent caps for liquid fuel vent pipes shall not employ screens finer than what mesh size?
1305.7
Piping located in a flood hazard area must be capable of resisting what three types of loads and stresses during the occurrence of flooding to the design flood elevation?
1206.9.1
The termination of concealed condensate piping must be marked to indicate whether the piping is connected to which two types of drain?
307.1.1
What air component, required by Section 403.3, shall not be recirculated?
403.2.1
What is the minimum termination distance required for chimneys or vents equipped with power exhausters from the lot line or adjacent buildings?
804.3.3, 33
A location that cannot be accessed without damaging permanent parts of the building structure or finish surface is a:
Chapter 2 – Definitions
When using the Two-Permanent-Openings Method (304.6.1) and communicating directly with the outdoors, what is the minimum free area required for each opening per 4,000 Btu/h of total appliance input rating?
304.6.1
For gas cabinets and exhausted enclosures containing highly toxic or toxic compressed gases, what ventilation function are they specifically prohibited from serving?
502.9.7.1, 502.9.7.2
Where unvented infrared heaters are installed, outdoor ventilation air must be provided at a rate of not less than 4 cfm per what unit of the aggregate input rating of all such heaters installed in the space?
630.3
When installing a floor furnace, what is the minimum clearance required on the control side of the unit?
609.4
Motorized louvers must be interlocked with the appliance to ensure they are proven to be in the full open position prior to:
304.1
An appliance regulated by this code that was legally installed prior to the effective date of the code is classified as what?
Chapter 2 – Definitions
Appliances must not be located in a hazardous location unless they are listed and approved for what?
303.2
When combining indoor spaces on the same story for combustion air, what is the minimum free area required for each opening?
304.5.3.1
Ducts required for systems regulated by this code must be designed and installed in accordance with the:
301.13
Electric motors driving exhaust fans in spray-finishing operations shall not be placed in which locations?
502.7.3.6
In industrial refrigerating systems, if the quantity of any Group A2, B2, A3, or B3 refrigerant in a single independent circuit would exceed 25 percent of the LFL upon release, electrical equipment must conform to what hazardous location classification requirements of NFPA 70?
1104.2.2
What are the maximum input ratings for an individual module of a Modular Boiler for oil fuel?
Chapter 2 – Definitions